SPECIFICATION SUBMITTAL
CLCS Overview-13 10.30.06
Centralized Lighting Control System Overview
GRAFIK Systems
Additional Notes
Viseo
• Used for local operation and programming of lighting values on a single processor
• Viseo cannot communicate to more than one processor
• Viseo does not support hierarchical spaces; it displays all spaces as a single list. For example, a hierarchical
space designated Floor 1 may have East, West, North, and South sub-spaces. When viewing Floor 1, the
Viseo will not display any zones programmed into sub-spaces East, West, North, or South. To view these
zones, the user must select one of those sub-spaces.
• Viseo can not control or display partitioned or hidden spaces
• If Lighting Zone Controller zones are programmed into a scene, they can be operated by scene control from
the Viseo; Viseo can not display Lighting Zone Controller data
• Viseo can only support ASCII 7-bit characters (26 capital and lowercase letters ‘A’ to ‘Z’, and 10 numbers
‘0’ to ‘9’)
Handheld Pr
ogrammers (HHP)
• Handheld programmers (HHP) do not support hierarchical spaces; they display all spaces as a single list.
For example, a hierarchical space designated Floor 1 may have East, West, North, and South sub-spaces.
When viewing Floor 1, the HHP will not display any zones programmed into sub-spaces East, West, North,
or South. To view these zones, the user must select one of those sub-spaces
• If Lighting Zone Controller zones are programmed into a scene, they can be operated by scene control from
the HHP; handheld programmers can not display Lighting Zone Controller data
• Handheld programmers can only support ASCII 7-bit characters (26 capital and lowercase letters ‘A’ to ‘Z’,
and 10 numbers ‘0’ to ‘9’)
EcoSystem
Integration
• EcoSystem ballasts and modules connect to a GRAFIK 7000 system via contact closures, which allows a
GRAFIK 7000 system to sweep on or off EcoSystem ballasts. The EcoSystem Bus closure inputs must be
set up and programmed via the EcoSystem Programmer
• A maximum of 64 EcoSystem ballasts or modules may be connected on one EcoSystem Bus. Each
EcoSystem Bus acts independently and cannot be interconnected to other EcoSystem busses
Note: Connections from EcoSystem to GRAFIK 7000 is limited to only 2 contact closures per EcoSystem
Bus. No digital communication is done between the GRAFIK 7000 system and any controlled load.
Sivoia Integration
• Shade integration is via an SO-SVC, which allows control of a single or multiple shades; a separate SO-SVC
is required for each shade zone
• SO-SVC is an output device only; it cannot communicate shade position back to the centralized lighting
control Processor