Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 3 10.12.2016
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sources/Load Types
Operate these sources with a smooth, continuous
Square Law dimming curve or in a full-conduction,
non-dim state:
Dimming Modules
• 80 BTUs/hour maximum per module.
• RTISS
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/− 10% change in RMS voltage/cycle and +/−2% Hz
change in frequency/second.
• Rated to handle a fully loaded electrical circuit (16 A
max). 4 outputs per module. Maximum of 16 A on an
output.
• Can operate HID sources in a full conduction,
non-dim state.
• When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
• If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
Adaptive Dimming Modules
• 115 BTUs/hour maximum per module.
• RTISS-TE
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/− 10% change in RMS voltage/cycle and +/−2% Hz
change in frequency/second.
• Rated to handle a fully loaded electrical circuit (16 A
max). 4 outputs per module. Maximum of 10 A on an
output.
• When programmed to “auto” mode, the unit starts in
reverse-phase and if an incompatible load is detected,
it will convert to forward-phase.
• When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
• If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
0-10 V Dimming Modules (TVM)
• Two 0 –10 V- circuits per module.
• Sink or source 50 mA per output (~25 ballasts/drivers;
maximum 750 mA total per twenty-four outputs).
• 5 BTUs/hour maximum per module.
• DIN rail mounted.
• Able to control:
– 0 –10 V-, IEC
® Standard 60929
– 10 – 0 V-
– PWM (Pulse Width Modulation), IEC
® Standard
60929
– DALI
® (Broadcast only), IEC® Standard 62386
• Must be used in conjection with a dimming module or
XP switching module.
XP Switching Modules*
• Able to control 20 A receptacles.
• Switch legs rated at 20 A.
• Four switch legs per module.
• Patented Softswitch
® circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to 1,000,000 cycles
at 16 A.
• 10 BTUs / hour per module.
• For additional information, see Lutron
® XP
Specication Submittal (P/N369345e).
Load
• When controlling receptacles, the XP Switching
Module may be used with, but is not limited to, the
following:
– Motors
– Fans
– Humidiers
– Printers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
• When controlling receptacles, the XP Switching
Module may NOT be suitable for use with devices that
require any of the following:
– Shut-down process before power is interrupted (e.g.,
computers)
– Cool-down process before power is interrupted (e.g.,
projectors)
– Programming (e.g., clocks, DVRs)
– Long warm-up cycle
• The XP Switching Module is NOT for use with loads
that present a hazard if automatically energized (e.g.,
heaters).
• Any receptacles that are controlled by an automatic
control device must be marked with “u” located on
the controlled receptacle outlet where visible after
installation as stated in 2014 NEC
® Article 406.3(E).
Module Specifications