Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 1 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
CCP Custom Combination Panels: 120 V~
Custom Combination Panels are pre-assembled and tested
power panels that are configurable to control multiple load
types. They are ideal for projects with many small loads.
Features
• Panels are pre-wired and tested prior to shipping.
• Feed-through panels and panels with breakers are
available.
• Supports various load types using remote power modules
(RPMs):
Dimming Module: Works directly with incandescent,
forward-phase electronic low-voltage (ELV), magnetic
low-voltage (MLV), LutronR 2-wire LED drivers,
switched lighting loads, switched LED drivers, switched
fluorescent ballasts and compatible forward-phase
dimmable LEDs.
Adaptive Module: Works directly with incandescent,
ELV (forward- and reverse-phase), MLV, LutronR 2-wire
LED drivers and compatible forward- and reverse-phase
dimmable LEDs.
XP Switching Module: Works with many switchable
load types including, but not limited to, resistive,
inductive, motor loads, switched LED drivers and
fluorescent ballasts. Also rated to control 20 A general
purpose receptacles at 120 V~.
Motor Module: Works with 3-wire 120 V~ motors.
Fan Speed Module: Works with ceiling fans at 120 V~.
0-10 V- Dimming Module: (12 modules, 24dimming
legs total per panel, max). Works with 010V-
dimming ballasts and drivers. Works in conjunction
with a dimming module or an XP switching module.
Also capable of outputting DALI
® intensity broadcast to
control DALIR drivers and ballasts.
Panels are rated for 120 V~ input power.
Bypass jumpers included for load mis-wire protection.
Front cover provided to maximize thermal performance
without needing a fan.
19 modules (Dimming, Adaptive, XP, Motor, Fan) for 436
controllable outputs.
Panels have a circuit selector that allows panels to be
compatible with:
GRAFIK Eye
® 4000 series control units and operate on
the same link as GP and XP panels.
— Quantum
® systems.
— DMX512 dimming systems via the 2LINK
TM option.
LUT-ELI-3PH for emergency applications requiring a
listed device to comply with UL924 or CSA C22.2
No. 141-02.
Each panel provides power and dimming for
4–36controllable outputs.
1
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 2 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
UL® Listed (Reference: UL File E42071).
CSA Certied.
Seismic certied panels can be provided upon
request. Contact Lutron for details.
Other certicates may apply.
Power
Input power: 120 V~. All voltages 50/60 Hz, phase-to-
neutral
Branch circuit breakers (AIC ratings):
120 V~ 10,000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Short-Circuit Current Ratings (other ratings
available)
Panel Size Voltage Standard SCCR Rating
All other sizes 120 V~ 25,000 A
24 in enclosure with
breakers
120 V~ 10,000 A
Wiring
Internal: Prewired by Lutron.
System communications: IEC PELV/NEC
® Class 2
wiring connects dimming panels to other components.
Line voltage: Feed and load wiring only. No other
wiring or assembly required.
Setup
Circuit selector digitally assigns controllable outputs to
zones and sources. Permits reassignment of zones
and sources without rewiring.
Physical Design
Enclosure: NEMA-Type 1, IP-20 protection; 16 U.S.
gauge steel. Indoor use only.
Maximum Weight:
Small panel (24 in) = 27 lbs (12 kg)
Standard panel (59 in) = 80 lbs (36 kg)
Seismic Certication Limits: SDS = 2.5 g, z/h = 1.0,
IP = 1.5. Panels containing fan or motor modules are
limited to SDS = 1.5 g. Contact Lutron for details.
Panel Specifications
Mounting
Surface mount or recess mount between 16 in (40cm)
studs.
Allow clearance around panel for ventilation.
Line Voltage (Mains) Connections
Use copper wire only, supply conductors 60 °C to
75 °C (140 °F to 167 °F).
• Feed-through panels
DIN rail-mounted terminal blocks provided for
line-voltage (mains) power to RPMs and to circuit
selector power supply.
DIN rail-mounted terminal blocks provided for load
wiring.
• Breaker panels
Main breaker or main lug provided for line-voltage
(mains) power. Power is distributed to branch circuit
breakers, modules, and control gear via internal
wiring installed by Lutron.
DIN rail-mounted terminal blocks provided for load
wiring.
Wire Sizing
Refer to wiring page for wire sizes.
Main breakers vary in size depending on modules in
the panel. Consult with Lutron for wire sizes
accommodated.
Main lugs vary in size depending on modules in the
panel. Consult with Lutron for wire sizes that can be
accommodated.
Environment
32 104 °F (040 °C). Relative humidity less than 90%,
non-condensing.
* For more information on load ratings, please refer to Application Note#201 at www.lutron.com/TechnicalDocumentLibrary/048-201.pdf
** Not all LED and CFL loads available today are dimmable. Visit www.lutron.com/LEDtool for a list of loads that have been tested by Luton to be compatible
with this product.
2
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 3 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sources/Load Types
Operate these sources with a smooth, continuous
Square Law dimming curve or in a full-conduction,
non-dim state:
Dimming Modules
80 BTUs/hour maximum per module.
RTISS
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/− 10% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
Rated to handle a fully loaded electrical circuit (16 A
max). 4 outputs per module. Maximum of 16 A on an
output.
Can operate HID sources in a full conduction,
non-dim state.
When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
Adaptive Dimming Modules
115 BTUs/hour maximum per module.
RTISS-TE
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/− 10% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
Rated to handle a fully loaded electrical circuit (16 A
max). 4 outputs per module. Maximum of 10 A on an
output.
When programmed to “auto” mode, the unit starts in
reverse-phase and if an incompatible load is detected,
it will convert to forward-phase.
When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
0-10 V Dimming Modules (TVM)
Two 0 10 V- circuits per module.
Sink or source 50 mA per output (~25 ballasts/drivers;
maximum 750 mA total per twenty-four outputs).
5 BTUs/hour maximum per module.
DIN rail mounted.
Able to control:
0 10 V-, IEC
® Standard 60929
10 0 V-
PWM (Pulse Width Modulation), IEC
® Standard
60929
DALI
® (Broadcast only), IEC® Standard 62386
Must be used in conjection with a dimming module or
XP switching module.
XP Switching Modules*
Able to control 20 A receptacles.
Switch legs rated at 20 A.
Four switch legs per module.
Patented Softswitch
® circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to 1,000,000 cycles
at 16 A.
10 BTUs / hour per module.
For additional information, see Lutron
® XP
Specication Submittal (P/N369345e).
Load
When controlling receptacles, the XP Switching
Module may be used with, but is not limited to, the
following:
Motors
Fans
Humidiers
Printers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
When controlling receptacles, the XP Switching
Module may NOT be suitable for use with devices that
require any of the following:
Shut-down process before power is interrupted (e.g.,
computers)
Cool-down process before power is interrupted (e.g.,
projectors)
Programming (e.g., clocks, DVRs)
Long warm-up cycle
The XP Switching Module is NOT for use with loads
that present a hazard if automatically energized (e.g.,
heaters).
Any receptacles that are controlled by an automatic
control device must be marked with “u” located on
the controlled receptacle outlet where visible after
installation as stated in 2014 NEC
® Article 406.3(E).
Module Specifications
3
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 4 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Module Specifications (continued)
Motor Modules*
For 20 A branch circuit, 1/4 HP per circuit. 5 A
maximum per circuit for motor loads, 3 A maximum
per circuit for tungsten loads.
Each module controls four 3-wire 120 V~ motors for
applications such as shades, draperies, and hurricane
shutters.
Individual control outputs use two mechanically
interlocked relays for directional control that prevents
simultaneous operation of both outputs. Air gap
provided when all four circuits are off.
Fan Speed Modules
Each of the four outputs of the fan module controls a
single ceiling fan.
There are ve available speeds: off, low, medium,
medium-high, and high.
Each output is rated to control a single ceiling fan load
up to 2 A at 120 V~.
4
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 5 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Adaptive Module
LP-RPM-4A-120
Dimming Module
LP-RPM-4U-120
Motor Module
LP-RPM-4M-120
Fan Speed Module
LP-RPM-4FSQ-120
Switching Module
XP2-SM-4S
0-10 V- Dimming Module +
Dimming Module
GRX-TVM2 + LP-RPM-4U-120
0-10 V- Dimming Module +
Switching Module
GRX-TVM2 + XP2-SM-4S
Module Specifications (continued)
Ratings
Input Voltage 120 V~ 120 V~ 120 V~ 120 V~ 120 V~ 120 V~ 120 V~
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Maximum load per module 16 A 16 A 16 A 8 A 80 A 16 A 64 A
Maximum load per output 10 A 16 A 5 A 2 A 20 A 16 A 16 A
Number of outputs 4 4 4 4 4 4 4
Minimum load 10 W 25 W - 0.25 W - 25 W -
Technology
Forward-phase dimming
Reverse-phase dimming
Phase adaptive
Phase selective
RTISSR
RTISS TER
SoftswitchR
Mechanically interlocked switching
relays
Switched capacitor quiet control
circuitry
Load Types
Dimmable phase control LED (forward
compatible dimming phase)
Dimmable phase control LED
(reverse-phase)
ELV (forward-phase)
ELV (reverse-phase)
MLV
Incandescent
LutronR 2-wire LED drivers
LutronR Tu-wireR fluorescent ballasts
Switched LED driver
Switched fluorescent ballasts
Switched general purpose receptacle
0-10 V- LED driver
0-10 V- fluorescent ballast
Other non-dim lighting loads
Motor loads
Neon/cold-cathode
AC shade/projection screen motors
Ceiling paddle fan
5
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 6 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Adaptive Module
LP-RPM-4A-120
Dimming Module
LP-RPM-4U-120
Motor Module
LP-RPM-4M-120
Fan Speed Module
LP-RPM-4FSQ-120
Switching Module
XP2-SM-4S
0-10 V- Dimming Module +
Dimming Module
GRX-TVM2 + LP-RPM-4U-120
0-10 V- Dimming Module +
Switching Module
GRX-TVM2 + XP2-SM-4S
Module Specifications (continued)
Load Interfaces
PHPM-PA
PHPM-3F
PHPM-SW-DV
PHPM-WBX
GRX-TVI
BCI-0-10
6
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 7 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
CCP: Custom Combination Panel
Quantity and Type of Modules
_X _L _A _M _F _T
List modules in the order shown above. Insert the quantity before each module
code. Omit codes for modules not used in panel. See Note at right for limits on
numbers of modules per panel.
X = Four-Circuit Switching Module (XP2-SM-4)
L = Four-Circuit Dimming Module (LP-RPM-4U-120)
A = Four-Circuit Adaptive Dimming Module (LP-RPM-4A-120)
M = Four-Circuit Motor Module (LP-RPM-4M-120)
F = Four-Circuit Quiet Fan Speed (LP-RPM-4FSQ-120)
T = 0-10 V - Control (GRX-TVM2)
Note: if any of the available module types is not desired, do not include it
in the model number.
Example: if two XP switching modules, three dimming modules, and one
motor module are desired, the correct model number would begin CCP–
2X3L1M, not CCP–2X3L0A1M…
Voltage
120: 120 V~
Feed Type
F T: Feed-through
2M*: 1 phase 2 wire feed in a mini panel.
•3M*:1 phase 3 wire feed (split phase) in a mini panel.
•4M*:3 phase 4 wire feed in a mini panel.
•2ML:Main lug for a 1 phase 2 wire feed.
•3ML:Main lug for a 1 phase 3 wire feed (split phase).
•4ML:Main lug for a 3 phase 4 wire feed.
Branch Circuit Breaker Rating
20: 20 A branch circuit breakers
15: 15 A branch circuit breakers
Omit for feed-through
Custom Panel Suffix
CGP number indicates specic characteristics of the customized panel.
All CCP panels will have a corresponding CGP number.
How to Build a Model Number
Prefix Quantity
and
Type of
Modules
Voltage Feed
Type
Branch
Circuit
Breaker
Rating
Custom
Panel
Suffix
C C P _X_L_A_M_F_T 1 2 0 4 M L 2 0 C G P _ _ _
NOTE:
Module quantities are limited as
follows:
Standard-Size Branch Circuit
Breaker panels
Max. # in panel: 9
Max. # with TVM modules: 8
Max. # with XP modules: 7
Max. # with XP and TVM
modules: 5
Standard-Size Feed-Through
panels
Max. # in panel: 9
Max. # with TVM modules: 8
Mini-Size Branch Circuit Breaker
panels
(no XP modules):
Max. # in panel: 3
Mini-Size Feed-Through panels
Max. # in panel (with dimming
modules and no TVMs): 3
Max. # in panel (with dimming
modules and TVMs): 2
Max. # in panel (all switching
modules): 4
Input Ratings
120 V~
120/240 V~
120/208 V~
* Branch circut breakers serve as a main input device. Incoming feeds lands directly to these branch circut breakers.
7
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 8 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standard Size Panel Dimensions
All dimensions shown as: in (mm)
Top View
14.375
(3 6 5.13)
Bottom View
4.15
(105.41)
Front View
15.875
(403.23)
15.125
(3 9 4.18 )
41.75
(1060.45)
59.50
(1511.3 0 )
2.43 (61.85)
2.43 (61.85)
2.69 (68.25)
8.00
(203.2)
11.0 0
(279.4)
Right Side View
4.21 (106.93)
0.15 (3 .81)
Left Side View
59.00
(1498.60)
Cover
2.69
(68)
8
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 9 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mini Panel Dimensions
Dimensions shown as: in (mm).
2.21
(56)
1.34
(34)
2.21
(56)
4.09
(104)
15.13
(384)
14.38 (365)
0.15
(4)
54.15
(105)
24.00
(610)
10.75
(273)
21.50
(546)
8.00
(203)
15.875
(403)
24.50
(622)
Bottom View
Top View
Right Side
Left Side
Front View
14.375
(365)
15.875
(403)
8.00
(203)
2.2
(56)
0.15
(4)
1.34
(34)
21.50
(546)
24.50
(622)
24.00
(610)
2.21
(56)
15.13
(384)
10.75
(273)
4.09
(104)
Cover
4.21
(107)
9
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 10 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Recess Mounting
Mount panel ush to 1/8 in (3 mm) below nished wall
surface.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
Mounting
Standard-size CCP Dimming Panels
Surface- or recess-mount indoors.
Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 32 104 °F (0 40 °C).
This equipment is air-cooled. Do not block vents or
warranty will be void.
Reinforce wall structure for weight and local codes.
Mount panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Number of
Modules
MaximumHeat*
(BTUs [Kcal]/Hr)
1 125 (31.5)
2 240 (60.5)
3 355 (89.5)
4 470 (118.5)
5 585 (147.5)
6 700 (176.5)
7 815 (205.5)
8 930 (234.5)
9 1045 (263.5)
Surface Mounting
Surface mounting keyholes accept 1/4 in (6 mm)
mounting bolts. This size is recommended.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
1
2
4
3
5
6
8
7
A
B
C
N
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring
and module
outputs to
loads
Preferred
feed wiring
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for module
outputs to
loads
1
2
4
3
5
6
8
7
A
B
C
N
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring
and module
outputs to
loads
Feed wiring
and module
outputs to
loads
Preferred
feed wiring
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for module
outputs to
loads
A
B
C
N
Main Lugs
(120 V~)
or
Minimum 1.5 in
apart
Minimum 1.5 in
apart
* Maximum heat is calculated using a panel with Adaptive Modules
and maximum loading. Heat will vary based on module configuration
and loading.
10
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 11 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Recess Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between ush and 1/8 in (3 mm) below
finished wall surface.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
Mounting
Mini Sized CCP Panels
Surface- or recess-mount indoors.
Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 32104 °F (0 40 °C).
This equipment is air-cooled. Do not block vents or
warranty will be void.
Mount Panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount Panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
Mount Panel within 7° of true vertical.
Surface Mounting
Surface mounting keyholes accept 1/4 in (6 mm)
mounting bolts. This size is recommended.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
Number of
Modules
MaximumHeat*
(BTUs [Kcal]/Hr)
1 125 (31.5)
2 240 (60.5)
3 355 (89.5)
N
N
Front View Side View
Feed wiring
and dimming
legs to loads
Branch
circuit
breakers
Feed wiring
and dimming
legs to loads
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for dimming
legs to loads
N
N
Front View Side View
Branch
circuit
breakers
Feed wiring
and dimming
legs to loads
Feed wiring
and dimming
legs to loads
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for dimming
legs to loads
Minimum 1.5 in apart
Minimum 1.5 in apart
* Maximum heat is calculated using a panel with Adaptive Modules
and maximum loading. Heat will vary based on module configuration
and loading.
11
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 12 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring
Wire the CCP similarly to a lighting distribution
panel:
Run feed and load wiring; no other wiring or
assembly is required.
Run separate neutrals for each module (no
common neutrals across phases).
The CCP can provide temporary lighting:
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Use branch circuit breakers to switch lights on and
off.
DL
DH
DH
DH
H
N
N
N
N
N
CCP
(cover off)
Terminal blocks
Branch circuit breakers
Main lug
Load
Bypass jumpers
(Do not remove
until load wiring
is verified)
Dimmed Hot/Live
(1) 1410 AWG (2.04.0 mm
2
)
Load Neutral
(1) 1410 AWG (2.04.0 mm
2
)
Panel
Type
Feed Wiring Feed Type Max Input Load Wiring
24 in or
59 in Feed
Through
Hot/Neutral:
14 AWG
(2.0 mm²) to
10 AWG
(6.0 mm²)
1P2W 20 A
Switched
Hot/Dimmed
Hot/Neutral:
14 AWG
(2.0 mm²)
to 10 AWG
(6.0 mm²)
24 in with
breakers
(1 module,
no XP)
Hot:
14 AWG
(2.0 mm²) to
8 AWG
(10 mm²)
Neutral:
14 AWG
(2.0 mm²) to
2/0 (67 mm²)
1P2W 20 A
24 in with
breakers (2
modules,
no XP)
1P2W,
1P3W
40 A
24 in with
breakers (3
modules,
no XP)
1P2W,
1P3W
3P4W
40 A
20 A
59 in with
breakers
(no XP)
Hot/Neutral:
14 AWG
(2.0 mm²) to
2/0 (67 mm²)
1P2W,
1P3W,
3P4W
175 A (CU
wire),
135 A (AL
wire)
59 in with
breakers
(3P4W,
with XP)
Hot/Neutral:
4 AWG
(25 mm²) to
250 kcmil
(mcm)
(120 mm²)
1P3W,
3P4W
200 A
12
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 13 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0-10 V Dimming Module + Dimming Module
For 010 V, PWM, and DALI® (Intensity broadcast only)
loads.
Each TVM controls 2consecutive dimming legs of
lighting which are the first dimming legs in the panel.
Maximum low-voltage ballast control current: 50 mA
per zone, 750 mA per panel.
+ 1
+ 2
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
TVM
H
+
N
Load terminals
Switched Hot/Live
Neutral
Driver/Ballast
Adaptive Dimming Module
0-10 V Dimming Module + XP Switching Module
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Load
Load terminals
Dimmed Hot/Live
Neutral
Typical Load Wiring
LP Dimming Module
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Dimmable load or non-dim load
Load terminals
Dimmed Hot/Live
Neutral
XPSwitchingModule*
* To avoid the risk of entrapment, serious injury, or death, these controls
must not be used to control equipment which is not visible from every
control location or which could create hazardous situations such as
entrapment if operated accidentally. Examples of such equipment which
must not be operated by these controls include (but are not limited to)
motorized gates, industrial doors, space heaters, etc. It is the installers
responsibility to ensure that the equipment being controlled is visible from
every control location and that only suitable equipment is connected to
these controls. Failure to do so could result in serious injury or death.
H
SH
H
SH
H
SH
H
SH
L
R
L
R
L
R
L
R
R
Hot
Switched Hot
Neutral
Distribution
panel
Load terminals
H
H
H
H
SH
SH
SH
SH
Load
+ 1
+ 2
H
SH
H
SH
H
SH
H
SH
R
Driver/Ballast
Hot
Switched Hot
Neutral
Distribution
panel
Load terminals
H
H
H
H
SH
SH
SH
SH
+
TVM
13
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 14 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Typical Load Wiring
Motor Module
R
L
R
L
R
L
R
L
H
N
N
N
N
N
N
N
L
H
R
N
L
R
N
N
L
R
L
R
3-wire
Motor
Raise
Lower
Neutral to motor
Fan Module
For ceiling fan control.
Each fan module output controls a single ceiling fan.
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Fan
Load terminals
Hot/Live Output
Neutral
Load terminals
14
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 15 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Low-Voltage IEC PELV / NEC® Class 2 Wiring (All Models)
System communications use low-voltage IEC PELV / NEC® Class 2 wiring.
Wiring must be daisy-chained.
Wiring must run separately from line (mains) voltage.
GRAFIK Eye®4000System
IEC PELV / NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
Approved low-voltage cable is available from Lutron
1
, Belden, and Liberty. These are approved with 22 AWG
(0.625 mm
2
) data link wires.
Quantum® System
IEC PELV/NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.5 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
If MUX-RPTR interface
2
and GRX-CBL-46L cable
1
is used, length may be up to 4000 ft (1219 m).
Maximum of 32 circuit selectors per link or 512 switch legs (controllable outputs) per link.
It is not necessary to position the Quantum
® panel at the end of the link; it may be in the middle.
CCP Panel
Control Unit
Control Interface
Wallstations
CCP Panel
LUTRON
LUTRON
Quantum®
Hub
Refer to Quantum
® Specication
Control Unit
Control Interface
Wallstations
1
GRX-CBL-46L IEC PELV / NEC® Class 2 wiring cable is available from Lutron and contains:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.625 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line.
15
Custom Combination PanelsGRAFIK Systems® Power Equipment
369644d 16 10.12.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergency power: The additional 18 AWG (1.0mm
2
) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency (essential)
lighting panel to “sense” when normal (non-essential) power is lost. If more than one emergency lighting panel needs to sense from a specic normal
panel, a dedicated wire between each pair of normal (non-essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit board of circuit selector. Connect the bare drain wires and cut off
the outside shield.
IEC PELV / NEC® Class 2
Terminal Connections
Each Low-Voltage IEC PELV / NEC® Class 2 terminal
can accept only two 18 AWG (1.0 mm
2
) wires.
Two12AWG (2.5 mm
2
) conductors won’t fit. Connect
as shown, using appropriate wire connectors.
SELECT CIRCUIT
2
1
Circuit
Data A OK
Power
1234 5D
Common
24VF
W
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
IEC PELV / NEC® Class 2 Panel-to-Panel Wiring (All Models)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
Control Wiring
(2) 12 AWG (2.5 mm
2
)
1: Common
2: 24 VFW
To
additional
Power
Panels
CCP Panel 1 CCP Panel 2
To Lighting
Controls or
Processors
Shield/Drain
Shield/Drain
(1) 18 AWG (1.0 mm
2
)
5: Sense Line*
Data Link
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
1
2
3, 4
5
1
2
3, 4
(4) 12 AWG (2.5 mm
2
)
16