SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron Plenum QS Cable Accessories
369596d 1 01.22.18
GRX-PCBL346S Cable
Plenum rated cable for use with the following
Lutron systems:
- GRAFIK Eye
- Energi Savr Node
- Quantum
- myRoom
- HomeWorks QS
• Plenum rated for use in ceilings and enclosures
that are also used by the building air distribution
system to transport environmental air.
Specifications
Model number:
GRX-PCBL-346S-500 – 500 ft (150 m) spool
Listed as type CL3P (Class 3 Plenum Cable) or
CMP cULus.
• Five conductors:
Common – 18 AWG (0.75 mm
2
)
Power – 18 AWG (0.75 mm
2
)
MUX Data – 22 AWG (0.25 mm
2
)
_ Data – 22 AWG (0.25 mm
2
)
Drain Wire – 24 AWG (0.2 mm
2
)
• Total Outer Jacket Diameter: 0.17 in (4.37 mm).
• 300 V Rated.
• Plenum sheath, 75 °C rated.
• UL Listed.
• Rated FT6.
cULus or CSA Listed.
• CPR Classification: E
CA
• Capacitance of 22 AWG (0.25 mm
2
) Twisted
Wire Pair:
-Conductor to shield: 48 pf/ft max
-Conductor to Conductor: 25 pf/ft max
22 AWG (0.25 mm
2
)
22 AWG (0.25 mm
2
)
18 AWG (0.75 mm
2
)
18 AWG (0.75 mm
2
)
12 AWG (4.0 mm
2
)
18 AWG (0.75 mm
2
)
12 AWG (4.0 mm
2
)
22 AWG (0.25 mm
2
)
22 AWG (0.25 mm
2
)
24 AWG (0.2 mm
2
) Drain
0.17 in (4.37 mm)
TWP
24 AWG (0.2 mm
2
) Drain
0.30 in (7.75 mm)
TWP
Note: Control link wiring distance maximums and other limitations for GRX-PCBL-346S cable are the same as those for GRX-CBL-346S cable.
Please refer to the Product Specification Submittal Sheets or Product Installation Guides at www.lutron.com for details.
}Twisted wire pair
Lutron, )Lutron, GRAFIK Eye, GRAFIK 6000, Softswitch128, HomeWorks, and Quantum are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
Energi Savr Node, GRAFIK 5000, GRAFIK 7000, HomeWorks Interactive, myRoom, and LCP128 are trademarks of Lutron Electronics Co., Inc.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron Plenum QS Cable Accessories
369596d 2 01.22.18
GRX-PCBL-46L Cable
Plenum rated cable for use with the following Lutron systems:
- GRAFIK Eye 4000
- LCP128
- Softswitch128
- GRAFIK 5000
- GRAFIK 6000
- GRAFIK 7000
- Quantum
- HomeWorks Interactive
- HomeWorks QS
- Energi Savr Node
• Plenum rated for use in ceilings and enclosures that are
also used by the building air distribution system to
transport environmental air.
Specifications
Model numbers:
GRX-PCBL-46L-250 – 250 ft (75 m) spool
GRX-PCBL-46L-500 – 500 ft (150 m) spool
Listed as type CL3P (Class 3 Plenum Cable) or CMP cULus.
• Six conductors:
Common – 12 AWG (4.0 mm
2
)
Power – 12 AWG (4.0 mm
2
)
MUX Data – 22 AWG (0.25 mm
2
)
_ Data – 22 AWG (0.25 mm
2
)
Sense Line – 18 AWG (0.75 mm
2
)
Drain Wire – 24 AWG (0.2 mm
2
)
• Total Outer Jacket Diameter: 0.30 in (7.75 mm).
• 300 V Rated.
• Plenum sheath, 75 °C rated.
• UL Listed.
• Rated FT6.
cULus or CSA Listed.
• CPR Classification: E
CA
• Capacitance of 22 AWG (0.25 mm
2
) Twisted
Wire Pair:
-Conductor to shield: 48 pf/ft max
-Conductor to Conductor: 25 pf/ft max
22 AWG (0.25 mm
2
)
22 AWG (0.25 mm
2
)
18 AWG (0.75 mm
2
)
18 AWG (0.75 mm
2
)
12 AWG (4.0 mm
2
)
18 AWG (0.75 mm
2
)
12 AWG (4.0 mm
2
)
22 AWG (0.25 mm
2
)
22 AWG (0.25 mm
2
)
24 AWG (0.2 mm
2
) Drain
0.17 in (4.37 mm)
TWP
24 AWG (0.2 mm
2
) Drain
0.30 in (7.75 mm)
TWP
Note: Control link wiring distance maximums and other limitations for GRX-PCBL-46L cable are the same as those for GRX-CBL-46L cable.
Please refer to the Product Specification Submittal Sheets or Product Installation Guides at www.lutron.com for details.
}Twisted wire pair
2