S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 1 09.30.09
Daylight Control Package
The CES daylight sensor package allows Lutron
lighting control systems to respond to ambient light
levels based on the settings of the controller. The
package includes a power pack, CES daylight
sensor, and LC8 controller. It can be integrated via
contact closure into a variety of Lutron lighting
systems.
Features
Allows management of Lutron lighting control
systems through dry contact closure outputs from
the LC8 controller.
The controller features adjustable On and Off
setpoints.
The package can be integrated into any Lutron
system that accepts dry contact closure inputs.
A variety of sensor types are available to fit any
application.
Models Available:
GRX-CESO-120 PKG: Outdoor, 120 V
GRX-CESO-277 PKG: Outdoor, 277 V
GRX-CESI-120 PKG: Indoor, 120 V
GRX-CESI-277 PKG: Indoor, 277 V
GRX-CESA-120 PKG: Atrium, 120 V
GRX-CESA-277 PKG: Atrium, 277 V
GRX-CESS-120 PKG: Skylight, 120 V
GRX-CESS-277 PKG: Skylight, 277 V
Dimensions
Dimensions are in inches (mm)
1.15 (29)
1.28
(32.5)
GRX-CESI
1.85 (47)
GRX-CESO
2.25 (57)
GRX-CESA or GRX-CESS
2.33 (59)
3.69 (94)
1.36 (35)
PP
1.35
(34 mm)
1.28
(32.5)
1
R
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 2 09.30.09
Specifications
LC8 Controller
Each Controller shall be powered by 24 V , and
have separate high and low fully adjustable
setpoints. Signal/setpoint and relay status indication
shall be provided along with calibration input for
adjustment. The controller shall be enclosed in a
plastic enclosure for surface mounting installation.
The controller shall provide a 10 A low voltage Form
C relay output.
Dead Band: Adjustable - 5-95%
Input Delay: Standard - 30 second Sensor
(removable for adjustment)
Output: Standard - Form C SPDT Relay
10 A resistive
Circuit Board: 3.75” H x 2.25” W x 1” D
Plastic Box Dim.: 4.75” H x 2.25” W x 1.5” D
CES Sensors
The photoelectric device shall be a Class 2, low-
voltage, ambient light sensor designed to interface
directly with the analog input of the Lighting Control
System. The sensor shall supply an analog signal to
the EMS system proportional to the light measured.
The sensor output shall provide for zero or offset
based signal. The sensor shall be capable of a fully
adjustable response in the range between 0 and
10,000 foot candles with a +/-1% accuracy at 70 °F
(21 °C).
The sensitivity adjustment shall be at the sensor
body, and outside of the sensor’s viewing angle. The
sensor housing shall be constructed from GE
Cycolac (R) ABS, shall be flame retardant and meet
UL 94 HB standards.
Indoor
Indoor sensors shall have a Fresnel lens, with a 60
degree cone of response. Indoor sensors shall only
require a penetration hole in the ceiling of 3/8 inch
dia., and the sensor shall mount to the ceiling using
adhesive tape. The indoor sensor range shall be
between 0 and 750 FC.
Outdoor
Outdoor models shall have a hood over the aperture
to shield the sensor from direct sunlight. The
outdoor sensor circuitry shall be completely
encased in an optically clear epoxy resin. Outdoor
sensors shall mount to a standard threaded 1/2 inch
conduit or fit a 1/2 inch knockout. The Outdoor
sensor range shall be between 0 and 750 FC.
Atrium or Skylight
The Atrium or Skylight sensors shall have a
translucent dome with a 180 degree field of view.
Atrium or Skylight sensors shall mount to standard
threaded 1/2 inch conduit or fit a 1/2 inch knockout.
Atrium sensor range shall be from 2 to 2,500 FC.
Skylight sensor range shall be between 10 and
7,500 FC.
Environment
Operating temperature: 13 – 140 °F (-11 – 60 °C).
All CES sensors are water-resistant and designed to
withstand UV radiation.
LC8 Controller and PP Power Packs for indoor use
only.
2
R
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 3 09.30.09
Wiring
6 7 8
1 2 3 4 5
SENSOR DELAY
OFF
ON
On LED
Off LED
On Setting Knob
Off Setting Knob
Sensor (typical)
Power pack
PP-120H,
PP-277H, or
PP-UNVH*
LC8 Controller
Yellow (0-10 V signal)
Black
(common)
Red (24 V )
Red (24 V )
Black
Blue (cap off)
Red
(cap off
both)
N.O. contact
Common
N.C. contact
To Lutron lighting control system
PELV (Class 2: USA) only
No line voltage
Notes
When interfacing to a Lutron system,
the N.C. contact will turn lights on
(contact closure close) when daylight
levels are low, and turn lights off
(contact closure open) when daylight
levels are high.
When the Off or On LED is lit, the
light level is above the setting of its
respective knob.
*Check with Lutron for
availability
Black (120 V )
White (neutral)
3
R
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 4 09.30.09
Mounting
LC8: Mount the controller using the adhesive strips
provided. Choose a location where the PP series
power pack can be provided with power.
GRX-CESI: Mount in 3/8 in (9.5 mm) hole using the
adhesive backing (included).
Ceiling mount: 6 to 8 feet from window, centrally
located.
Reflected wall mount: Facing the reflecting wall, not
in line with any indoor lighting.
Wall mount with sconces: Mount at same height as
sconce, but not directly in line.
GRX-CESO: Mount in standard 1/2 in (13 mm)
conduit or knockout. Mount horizontally, facing
north, with the hooded portion on top.
GRX-CESA: Mount in standard 1/2 in (13 mm)
conduit or knockout, opposite the atrium window.
GRX-CESS: Mount in standard 1/2 in (13 mm)
conduit or knockout, near the center of the skylight
well, at least 12 in (305 mm) from the sides. Mount
vertically, facing up, with top of sensor level with top
of skylight curb.
PP: Power pack fits inside junction box. Mount
with 6/32 x 1.25 in (5 x 32 mm) pan head screws.
Or mount to standard 4 x 4 in (102 x 102 mm)
junction box through knockout with 1/2 in (13 mm)
EMT threaded nipple.
Note: Always turn power off and lock out during unit
installation. Always install unit in accordance with
applicable national and local electrical codes.
6 – 8 ft
1.8 – 2.4 m
Light fixture
Light fixture
Sensor
Window
GRX-CESI: Ceiling Mount
18 in
(457 mm)
Sensor
GRX-CESI: Reflecting Wall Mount
60˚
Sensor
GRX-CESI: Sconce Wall Mount
Sconce
Sensor
Window
GRX-CESA
Sensor
GRX-CESS
1/2 in (13 mm)
conduit
Sensor
GRX-CESO
Snow line
1/2 in (13 mm)
conduit
North
4
R
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 5 09.30.09
Power
Power Pack
Input or Operating Voltage:
120 V , 277 V , or universal (call for availability)
transformer 60 Hz
24 V nominal output; 100 mA nominal, full wave
rectified and filtered
CES Sensors
Operating Voltage: 24 V PELV (Class 2: USA).
Operating Current: 40 mA nominal from 24 V
supply.
Control Output: 0 – 10 V signal representative of
ambient light present (input to LC8 controller).
5
R
S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRAFIKTM Systems Daylight Control Package Daylight Sensor System
ces system 6 09.30.09
CALIBRATION
Each GRX-CES sensor is calibrated during manufacturing to the light levels in its intended environment (indoor,
outdoor, etc.). Below is a chart of the settings for each model. The first column corresponds to the settings on
the adjustment knobs in the GRX-LC8 controller.
Adjustment Knob
Setting
Corresponding Foot-Candle Thresholds
GRX-CESI GRX-CESA GRX-CESS GRX-CESO
Below 1 0 2 10 0
1 10 100 200 25
2 20 200 400 50
3 30 300 600 75
4 40 400 800 100
5 50 500 1000 125
6 60 600 1200 150
7 70 700 1400 175
8 80 800 1600 200
9 90 900 1800 225
10 100 1000 2000 250
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
SIMULATOR
JACK
INPUT
TIME
DELAY
RELAY
STATUS
ON
ON
ON
OFF
OFF
OFF
FOR FURTHER
CALIBRATION
INFORMATION,
SEE IMM
(INSTALLATION
MAINTENANCE
MANUAL).
OCC
SENSOR
FOOTCANDLE
SETTINGS
1 10
10 100
25 250
100 1000
200 2000
I
O
A
S
OFF
setting
ON
setting
Daylighting Level (foot-candles)
Dead
band
Time of day
Time of day
Lights ON
Lights ON
Lights OFF
GRX-LC8
Calibration
Using the chart above, set the On adjustment knob: This is the low light level that will trigger your lights to go on.
Set the Off adjustment knob: This is the high light level that will trigger your lights to turn off. For proper
operation, set the On knob at least 10% (1 tick mark on the knob) lower than the Off knob to create the dead
band.
6