Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 1 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
CCP Custom Combination Panels –
220–240 V~ (CE and non-CE)
Custom Combination Panels are pre-assembled and tested
power panels that are configurable to control multiple load
types. They are ideal for projects with many small loads.
Features
• Panels are prewired and tested prior to shipping.
• Feed-through panels and panels with breakers are
available.
• Supports various load types using remote power modules
(RPMs):
Dimming Module: Works directly with incandescent,
forward-phase electronic low-voltage (ELV), magnetic
low-voltage (MLV), LutronR 2-wire LED drivers,
switched lighting loads, switched LED drivers, switched
uorescent ballasts, and compatible forward-phase
dimmable LEDs.
Adaptive Module: Works directly with incandescent,
ELV (forward-and reverse-phase), MLV, LutronR 2-wire
LED drivers and compatible forward-and reverse-phase
dimmable LEDs.
XP Switching Module: Works with many switchable
load types including, but not limited to, resistive,
inductive, motor loads, switched LED drivers and
fluorescent ballasts.
ELV Dimming Module: Works with trailing-edge
electronic low-voltage, incandescent lighting and
compatible reverse-phase dimmable LEDs.
0–10 V- Dimming Module: Works with 010V-
dimming ballasts and drivers. Works in conjunction with
a LP dimming module or an XP switching module. Is
capable of DALI
® intensity broadcast to control DALIR
drivers and ballasts.
Panels are rated for 220–240 V~ input power.
Bypass jumpers included for load mis-wire protection.
Front cover provided to maximize thermal performance
without needing a fan.
1–9 Modules (Dimming, Adaptive, ELV, XP) for 4–36
controllable outputs.
Panels have a circuit selector that allows panels to be
compatible with:
GRAFIK Eye
® 4000 series control units and operate on
the same link as GP and XP panels.
— Quantum
® systems.
— DMX512 dimming systems via the 2LINK
TM option.
Each panel provides power and dimming for
4–36controllable outputs.
1
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 2 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Power
Input power: 220–240 V~. All voltages 50/60 Hz,
phase-to-neutral
Branch circuit breakers (AIC ratings):
220–240 V~ 6,000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Wiring
Internal: Pre-wired by Lutron.
System communications: PELV/SELV/NEC Class 2
wiring connects dimming panels to other components.
Line voltage: Feed and load wiring only. No other
wiring or assembly required.
Setup
Circuit selector digitally assigns controllable outputs to
zones and sources. Permits reassignment of zones
and sources without rewiring.
Physical Design
Enclosure: NEMA-Type 1, IP-20 protection; 16 U.S.
gauge steel. Indoor use only.
Maximum Weight:
Small panel 60 cm (24 in) = 12 kg (27 lbs)
Standard panel 150 cm (59 in) = 36 kg (80 lbs)
Mounting
Surface mount or recess mount between 40cm (16 in)
studs.
Allow clearance around panel for ventilation (see page
10 for details).
Non-CE Panel Specifications: 220–240 V~
Line Voltage (Mains) and Load Connections
Use copper wire only, supply conductors 60 °C to
75 °C (140 °F to 167 °F).
• Feed-through panels
DIN rail-mounted terminal blocks provided for
line-voltage (mains) power to RPMs and to circuit
selector power supply.
DIN rail-mounted terminal blocks provided for load
wiring.
• Breaker panels
Isolation switch provided for line-voltage (mains)
power. Power is distributed to branch circuit
breakers, modules, and control gear via internal
wiring installed by Lutron.
DIN rail-mounted terminal blocks provided for load
wiring.
Wire Sizing
• Refer to Wiring page for wire size details.
Environment
040 °C (32 104 °F). Relative humidity less than 90%,
non-condensing.
* For more information on load ratings, please refer to Application Note#201 at www.lutron.com/TechnicalDocumentLibrary/048-201.pdf
** Not all LED and CFL loads available today are dimmable. Visit www.lutron.com/LEDtool for a list of loads that have been tested by Luton to be compatible
with this product.
2
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 3 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
Complies with CE
Power
Input power: 220–240 V~. All voltages 50/60 Hz,
phase-to-neutral
Branch circuit breakers (AIC ratings):
220–240 V~ 6,000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Wiring
Internal: Prewired by Lutron.
System communications: PELV/SELV/NEC Class 2
wiring connects dimming panels to other components.
Line voltage: Feed and load wiring only. No other
wiring or assembly required.
Setup
Circuit selector digitally assigns controllable outputs to
zones and sources. Permits reassignment of zones
and sources without rewiring.
Physical Design
Enclosure: NEMA-Type 1, IP-20 protection; 16 U.S.
gauge steel. Indoor use only.
Maximum Weight:
Small panel 60 cm (24 in) = 12 kg (27 lbs)
Standard panel 150 cm (59 in) = 36 kg (80 lbs)
Mounting
Surface mount or recess mount between 40cm (16 in)
studs.
Allow clearance around panel for ventilation (see page
10 for details).
CE Panel Specifications: 220240 V~
Line Voltage (Mains) and Load Connections
Use copper wire only, supply conductors 60 °C to
75 °C (140 °F to 167 °F).
• Feed-through panels
DIN rail-mounted terminal blocks provided for
line-voltage (mains) power to RPMs and to circuit
selector power supply.
DIN rail-mounted terminal blocks provided for load
wiring.
• Breaker panels
Isolation switch provided for line-voltage (mains)
power. Power is distributed to branch circuit
breakers, modules, and control gear via internal
wiring installed by Lutron.
DIN rail-mounted terminal blocks provided for load
wiring.
Wire Sizing
• Refer to Wiring page for wire size details.
Environment
040 °C (32 104 °F). Relative humidity less than 90%,
non-condensing.
* For more information on load ratings, please refer to Application Note#201 at www.lutron.com/TechnicalDocumentLibrary/048-201.pdf
** Not all LED and CFL loads available today are dimmable. Visit www.lutron.com/LEDtool for a list of loads that have been tested by Luton to be compatible
with this product.
3
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 4 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sources/Load Types
Operate these sources with a smooth, continuous
Square Law dimming curve or in a full-conduction,
non-dim state:
LP Dimming Modules
80 BTU/hour maximum per module.
RTISS
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/10% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
CE model is rated to for a max load of 13 A per
module, with a maximum of 13 A on an output.
Non-CE model is rated for 16 A per module, with a
maximum of 16 A per on an output.
Can operate HID sources in a full conduction,
non-dim state.
When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
Adaptive Dimming Modules
115 BTU/hour maximum per module.
RTISS-TE
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/10% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
Rated to handle a fully loaded electrical circuit (16 A
max). 4 outputs per module. Maximum of 10 A on an
output.
When programmed to “auto” mode, the unit starts in
reverse-phase and if an incompatible load is detected,
it will convert to forward-phase.
When controlling Lutron 2-wire drivers, refer to driver
spec sheet for permitted driver quantities.
If mixing Lutron 2-wire drivers and other loads on the
same module, treat each driver as a 50 W load.
0–10 V- Dimming Modules (TVM)
Two 0 10 V- circuits per module.
Maximum of 12 modules, 24dimming legs total per
panel
Sink or source 50 mA per output (maximum 750 mA
total per twenty-four outputs).
5 BTU/hour maximum per module.
DIN rail mounted.
Able to control:
0 10 V-, IEC
® Standard 60929
10 0 V-
PWM (Pulse Width Modulation), IEC
® Standard
60929
DALI
® (Broadcast only), IEC® Standard 62386
Must be used in conjuction with a 4U dimming module
or XP switching module.
XP Switching Modules*
Switch legs rated at 16 A.
Four switch legs per module.
Patented Softswitch
® circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to a minimum of 1,000,000 cycles
at 16 A.
10 BTU / hour per module.
For additional information, see Lutron
® XP
Specication Submittal (P/N369345).
Motor Modules
Each module controls four 3-wire 220–240 V~ motors
for applications such as shades, draperies, and
hurricane shutters.
Individual control outputs use two mechanically
interlocked relays for directional control that prevents
simultaneous operation of both outputs.
ELV Dimming Modules
115 BTU/hour maximum per module.
Rated to handle 16 A
4 outputs per module. Maximum of 10 A on an output.
RTISS-TE
TM filter circuit technology compensates for
incoming line voltage variations: No visible icker with
+/10% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
Module Specifications
4
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 5 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Adaptive Module
LP-RPM-4A-230
Dimming Module
LP-RPM-4U-240
Dimming Module
LP-RPM-4U-230-CE
ELV Dimming Module
LP-RPM-4E-230-CE
Switching Module
XP2-SM-4S
Motor Module
HW-RPM-4M-230
0-10 V- Dimming Module + Dimming Module
GRX-TVM2 + LP-RPM-4U-240
0-10 V- Dimming Module + Dimming Module
GRX-TVM2 + LP-RPM-4U-230-CE
0-10 V- Dimming Module + Switching Module
GRX-TVM2 + XP2-SM-4S
Module Specifications (continued)
Ratings
Input Voltage
220–240 V~
Frequency 50/60 Hz
Maximum load per
module
13 A 16 A 13 A 16 A 64 A 16 A 16 A 13 A 64 A
Maximum load per
output
8 A 16 A 10 A 10 A 16 A 5 A 16 A 10 A 16 A
Number of outputs 4 4 4 4 4 4 4 4 4
Minimum load 10 W 40 W 40 W 10 W - - 40 W 40 W -
Technology
Forward-phase
dimming
Reverse-phase
dimming
Phase adaptive
Phase selective
RTISSR
RTISS TE
SoftswitchR
Mechanically
interlocked
switching relays
Load Interfaces
NGRX-PB
NGRX-ELVI
GRX-TVI
BCI-0-10
5
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 6 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Module Specifications (continued)
Load Types
Compatible dimmable
phase control LED
(forward-phase)
Compatible dimmable
phase control LED
(reverse-phase)
ELV (forward-phase)
ELV (reverse-phase)
MLV
Incandescent
Lutron 2-wire LED
drivers
Lutron tu-wire
fluorescent
Switched LED driver
Switched fluorescent
ballasts
Switched receptacle
0-10 V- LED driver
0-10 V- fluorescent
ballast
Other non-dim lighting
loads
Motor loads
Neon/cold-cathode
AC shade/ projection
screen motors
Ceiling paddle fan
Adaptive Module
LP-RPM-4A-230
Dimming Module
LP-RPM-4U-240
Dimming Module
LP-RPM-4U-230-CE
ELV Dimming Module
LP-RPM-4E-230-CE
Switching Module
XP2-SM-4S
Motor Module
HW-RPM-4M-230
0-10 V- Dimming Module + Dimming Module
GRX-TVM2 + LP-RPM-4U-240
0-10 V- Dimming Module + Dimming Module
GRX-TVM2 + LP-RPM-4U-230-CE
0-10 V- Dimming Module + Switching Module
GRX-TVM2 + XP2-SM-4S
6
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 7 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
CCP: Custom Combination Panel
Quantity and Type of Modules
_X _L _E _A _M _T
List modules in the order shown above. Insert the quantity before each module
code. Omit codes for modules not used in panel. See Note at right for limits on
numbers of modules per panel.
X = Four-Circuit Switching Module (XP2-SM-4S)
L = Four-Circuit Dimming Module (LP-RPM-4U)
E = Four-Circuit ELV Module (LP-RPM-4E)
A = Four-Circuit Adaptive Dimming Module (LP-RPM-4A)
M = Four-Circuit Motor Module (HW-RPM-4M-230)
T = 0-10 V- Control (GRX-TVM2)
Example: 2X3L indicates that two XP switching modules and three
4U dimming modules are desired.
Note: if any of the available module types is not desired, do not include it
in the model number.
Example: if two XP switching modules, three LP dimming modules, and
one motor module are desired, the correct model number would begin
CCP–2X3L1M, not CCP–2X3L0A1M
Voltage
230: 220–240 V~ (CE)
240: 220–240 V~ (non-CE)
Feed Type
F T: Feed-through
•4IS: Isolator switch for 3-phase 4-wire
Branch Circuit Breaker Rating
10: 10 A branch circuit breakers
13: 13 A branch circuit breakers
16: 16 A branch circuit breakers
Omit for feed-through
Custom Panel Sufx
CGP number indicates specic characteristics of the customized panel.
All CCP panels will have a corresponding CGP number.
How to Build a Model Number
Prefix Quantity
and
Type of
Modules
Voltage Feed
Type
Branch
Circuit
Breaker
Rating
Custom
Panel
Suffix
C C P _X_L_E_A_M_T 2 3 0 4 I S 1 0 C G P _ _ _
NOTE:
Module quantities are limited as
follows:
Standard-Size Branch Circuit
Breaker panels
Max. # in panel: 8
Max. # with TVM modules: 8
Max. # with XP modules: 6
Max. # with XP and TVM
modules: 6
Standard-Size Feed-Through
panels
Max. # in panel: 9
Max. # with TVM modules: 8
Mini-Size Branch Circuit Breaker
panels
(no XP modules):
Max. # in panel without TVMs: 3
Max. # in panel with TVMs: 2
Mini-Size Feed-Through panels
Max. # in panel (with dimming
modules and no TVMs): 3
Max. # in panel (with dimming
modules and TVMs): 2
Max. # in panel (all dimming
modules only): 4
Input Ratings
220–240 V~
7
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 8 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standard Size Panel Dimensions
All dimensions shown as: in (mm)
Top View
14.375
(3 6 5.13)
Bottom View
4.15
(105.41)
Front View
15.875
(403.23)
15.125
(3 9 4.18)
41.75
(1060.45)
59.50
(1511.30)
2.43 (61.85)
2.43 (61.85)
2.69 (68.25)
8.00
(203.2)
11.0 0
(279.4)
Right Side View
4.21 (106.93)
0.15 (3.81)
Left Side View
59.00
(1498.60)
Cover
8
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 9 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mini Panel Dimensions
Dimensions shown as: in (mm)
2.21
(56)
1.34
(34)
2.21
(56)
4.09
(104)
15.13
(384)
14.38 (365)
0.15
(4)
54.15
(105)
24.00
(610)
10.75
(273)
21.50
(546)
8.00
(203)
15.875
(403)
24.50
(622)
Bottom View
Top View
Right Side
Left Side
Front View
14.375
(365)
15.875
(403)
8.00
(203)
2.2
(56)
0.15
(4)
1.34
(34)
21.50
(546)
24.50
(622)
24.00
(610)
2.21
(56)
15.13
(384)
10.75
(273)
4.09
(104)
Cover
4.21
(107)
9
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 10 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Recess Mounting
Mount panel ush to 3 mm (1/8 in) below nished wall
surface.
If mounting panels next to each other, leave 38 mm
(1.5 in) clearance on each side of the panels for front
covers to be attached to the enclosure.
Mounting
Standard-size CCP Dimming Panels
Surface- or recess-mount indoors.
Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 0 40 °C (32 104 °F).
This equipment is air-cooled. Do not block vents or
warranty will be void.
Reinforce wall structure for weight and local codes.
Mount panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount panels so line (mains) voltage wiring is at least
1.8 m (6 ft) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Number of
Modules
Maximum Heat*
(BTUs [Kcal]/Hr)
1 125 (31.5)
2 240 (60.5)
3 355 (89.5)
4 470 (118.5)
5 585 (147.5)
6 700 (176.5)
7 815 (205.5)
8 930 (234.5)
Surface Mounting
Surface mounting keyholes accept 6 mm (1/4 in)
mounting bolts. This size is recommended.
If mounting panels next to each other, leave 38 mm
(1.5 in) clearance on each side of the panels for front
covers to be attached to the enclosure.
1
2
4
3
5
6
8
7
A
B
C
N
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring
and module
outputs to
loads
Preferred
feed wiring
PELV/SELV/NEC Class 2
wiring
Do not
block vents
31cm (12in)
minimum
clearance
Terminal blocks
for module
outputs to
loads
1
2
4
3
5
6
8
7
A
B
C
N
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring
and module
outputs to
loads
Feed wiring
and module
outputs to
loads
Preferred
feed wiring
PELV/SELV/NEC Class 2
wiring
Do not
block vents
31cm (12in)
minimum
clearance
Terminal blocks
for module
outputs to
loads
A
B
C
N
Isolator Switch
(220 –240 V~, 230 V~)
or
Minimum 38 mm
(1.5 in) apart
Minimum 1.5 in
apart
* Maximum heat is calculated using a panel with Adaptive Modules
and maximum loading. Heat will vary based on module configuration
and loading.
10
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 11 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Recess Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between ush and 1/8 in (3 mm) below
finished wall surface.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
Mounting
Mini Panels
Surface- or recess-mount indoors.
Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 32104 °F (0 40 °C).
This equipment is air-cooled. Do not block vents or
warranty will be void.
Mount Panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount Panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
Mount Panel within 7° of true vertical.
Surface Mounting
Surface mounting keyholes accept 1/4 in (6 mm)
mounting bolts. This size is recommended.
If mounting panels next to each other, leave 1.5 in
(38 mm) clearance on each side of the panels for front
covers to be attached to the enclosure.
N
N
Front View Side View
Feed wiring
and dimming
legs to loads
Branch
circuit
breakers
Feed wiring
and dimming
legs to loads
PELV/SELV/
NEC Class 2
wiring
Do not
block vents
31cm (12in)
minimum
clearance
Terminal blocks
for dimming
legs to loads
N
N
Front View Side View
Branch
circuit
breakers
Feed wiring
and dimming
legs to loads
Feed wiring
and dimming
legs to loads
PELV/SELV/
NEC Class 2
wiring
Do not
block vents
31cm (12in)
minimum
clearance
Terminal blocks
for dimming
legs to loads
Minimum 38 mm
(1.5 in) apart
Minimum 38 mm
(1.5 in) apart
Number of
Modules
Maximum Heat*
(BTUs [Kcal]/Hr)
1 125 (31.5)
2 240 (60.5)
3 355 (89.5)
* Maximum heat is calculated using a panel with Adaptive Modules
and maximum loading. Heat will vary based on module configuration
and loading.
11
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 12 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Panel Wiring
DL
N
CCP
(cover off)
Terminal blocks
Bypass jumpers
(Do not remove
until load wiring
is verified)
Branch circuit breakers
Wire Sizes for Load Wiring
Wire Sizes
Power Feed (panels with main ISO Switch):
Hot/Live - 2.5 mm
2
(14 AWG) to 35 mm
2
(2 AWG)
Neutral - 2.5 mm
2
(14 AWG) to 35 mm
2
(2 AWG)
•PowerFeed(feedthroughpanels):
Hot/Live - 2.5 mm
2
(14 AWG) to 4.0 mm
2
(10 AWG)
Neutral - 2.5 mm
2
(14 AWG) to 4.0 mm
2
(10 AWG)
Load Wiring (all panels):
Hot/Live - 2.5 mm
2
(14 AWG) to 4.0 mm
2
(10 AWG)
Neutral - 2.5 mm
2
(14 AWG) to 4.0 mm
2
(10 AWG)
Wiring Tips
Wire the panel similar to a Lighting Distribution
Panel:
Run feed and load wiring to appropriate terminal
blocks or Isolator switch installed in the panel.
For feed through panels run separate neutrals
for each module—no common neutrals across
phases.
The panel can provide temporary lighting:
Wire all loads.
Do not remove bypass jumpers that are pre-
installed for load controlling modules.
Use pre-installed Breakers to switch lights on
and off.
Main Isolation Switch
12
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 13 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
010 V- Dimming Module + LP Dimming
Module
For 010 V-, PWM, and DALI® (Intensity broadcast
only) loads.
Each TVM controls 2consecutive dimming legs of
lighting which are the first dimming legs in the panel.
Maximum low-voltage ballast control current: 50 mA
per zone, 750 mA per panel.
+ 1
+ 2
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
TVM
H
+
N
Load terminals
Switched Hot/Live
Neutral
Driver/Ballast
Adaptive Dimming Module
For incandescent and dimmable forward-or reverse
phase control loads.
ELV Dimming Module
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Load
Load terminals
Dimmed Hot/Live
Neutral
Typical Load Wiring
LP Dimming Module
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Dimmable load or non-dim load
Load terminals
Dimmed Hot/Live
Neutral
DH
DH
DH
DH
H
N
N
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Dimmable load or non-dim load
Load terminals
Dimmed Hot/Live
Neutral
XP Switching Module*
H
SH
H
SH
H
SH
H
SH
L
R
L
R
L
R
L
R
R
Hot
Switched Hot
Neutral
Distribution
panel
Load terminals
H
H
H
H
SH
SH
SH
SH
Load
010 V- Dimming Module + XP Switching
Module
+ 1
+ 2
H
SH
H
SH
H
SH
H
SH
R
Driver/Ballast
Hot
Switched Hot
Neutral
Distribution
panel
Load terminals
H
H
H
H
SH
SH
SH
SH
+
TVM
13
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 14 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Typical Load Wiring
Motor Module
R
L
R
L
R
L
R
L
H
N
N
N
N
N
N
N
L
H
R
N
L
R
N
N
L
R
L
R
3-wire
Motor
Raise
Lower
Neutral to motor
Load terminals
14
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 15 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Low-Voltage PELV/SELV/NEC Class 2 Wiring (All Models)
System communications use low-voltage PELV/SELV/NEC Class 2 wiring.
Wiring must be daisy-chained.
Wiring must run separately from line (mains) voltage.
GRAFIK Eye® 4000 System
PELV/SELV/NEC Class 2 wiring link requires:
Two 2.5 mm
2
(12 AWG) conductors for control power.
One twisted, shielded pair of 1.0 mm
2
(18 AWG) for data link.
One 1.0 mm
2
(18 AWG) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 610 m (2000 ft).
Approved low-voltage cable is available from Lutron
1
, Belden, and Liberty. These are approved with 0.625 mm
2
(22 AWG) data link wires.
Quantum® System
PELV/SELV/NEC Class 2 wiring link requires:
Two 2.5 mm
2
(12 AWG) conductors for control power.
One twisted, shielded pair of 0.5 mm
2
(22 AWG) for data link.
One 1.0 mm
2
(18 AWG) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 610 m (2000 ft).
Up to 3 MX-RPTR may be used to extend the panel link to a max. of 2438 m (8000 ft).
Maximum of 32 circuit selectors per link or 512 switch legs (controllable outputs) per link.
It is not necessary to position the Quantum
® panel at the end of the link; it may be in the middle.
1
GRX-CBL-46L PELV/SELV/NEC Class 2 wiring cable is available from Lutron and contains:
Two 2.5 mm
2
(12 AWG) conductors for control power.
One twisted, shielded pair of 0.625 mm
2
(22 AWG) for data link.
One 1.0 mm
2
(18 AWG) conductor for emergency (essential) sense line.
CCP Panel
Control Unit
Control
Interface
Wallstations
CCP Panel
LUTRON
LUTRON
Quantum
®
Hub
Refer to Quantum
®
Specication
Control Unit
Control
Interface
Wallstations
15
Custom Combination PanelsGRAFIK SystemsT Power Equipment
369999a 16 09.02.2016
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergency power: The additional 1.0 mm
2
(18 AWG) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency (essential)
lighting panel to “sense” when normal (non-essential) power is lost. If more than one emergency lighting panel needs to sense from a specic normal
panel, a dedicated wire between each pair of normal (non-essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit board of circuit selector. Connect the bare drain wires and cut off
the outside shield.
PELV/SELV/NEC Class 2
Terminal Connections
Each Low-Voltage PELV/SELV/NEC Class 2 terminal
can accept only two 1.0 mm
2
(18 AWG) wires.
Two2.5 mm
2
(12AWG) conductors won’t t. Connect
as shown, using appropriate wire connectors.
SELECT CIRCUIT
2
1
Circuit
Data A OK
Power
1234 5D
Common
24VF
W
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
PELV/SELV/NEC Class 2 Panel-to-Panel Wiring (All Models)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
Control Wiring
(2) 2.5 mm
2
(12 AWG)
1: Common
2: 24 VFW
To
additional
Power
Panels
CCP Panel 1 CCP Panel 2
To Lighting
Controls or
Processors
Shield/Drain
Shield/Drain
(1) 1.0 mm
2
(18 AWG)
5: Sense Line*
Data Link
(1) shielded, twisted pair 1.0 mm
2
(18 AWG)
3: MUX
4: MUX
1
2
3, 4
5
1
2
3, 4
(4) 2.5 mm
2
(12 AWG)
16