PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 1 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® Dimming Module
with EcoSystem
® for Japan
The PowPak® Dimming Module with EcoSystem® is a
radio frequency (RF) control that operates up to
32EcoSystem
® LED drivers based on input from Pico®
controls and Radio Powr Savr
sensors. Configurable
for multiple zones in a single area, the Dimming Module
with EcoSystem
® is ideal for small areas such as
classrooms, conference rooms, and private offices.
Communication with RF input devices, such as Pico
®
controls and Radio Powr Savr
sensors, is accomplished
using Lutron Clear Connect
® RF Technology.
Features
•Controlsupto32EcoSystem
® LED drivers
•ReceivesinputfromuptoninePico
® controls, six
Radio Powr Savr
occupancy/vacancy sensors, and
one Radio Powr Savr
daylight sensor
•UtilizesLutronClearConnect
® RF Technology – refer to
model number chart below for frequency band data
•Mountstoajunctionboxthroughastandard21.7mm
knockout
Model Number Operating Voltage Frequency Band Region
RMP-ECO32-JA-B 100 V ~ 50/60 Hz 312.3 – 314.8 MHz Japan
RMP-ECO32-200-JA 200 V~ 50/60 Hz 312.3 – 314.8 MHz Japan
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
1
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 2 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Power
•Operatingvoltage:
100 V ~ 50 / 60 Hz 40mA
System Communication
•OperatesusingClearConnect® RF Technology for
reliable wireless communication; refer to model
number chart on page 1 for frequency band details
•RFrangeis7m
Environment
•Ambientoperatingtemperature:0°Cto40°C
•0%to90%humidity,non-condensing
•Forindooruseonly
EcoSystem
® Link
•Communicateswithupto32EcoSystem
® enabled
LED drivers
•EcoSystem
® Digital Link can be wired Class1 or
Class2 for maximum wiring flexibility
•Terminalsaccept0.75 to 1.5 mm
2
(18 to 16 AWG)
solid wire
NOTE: The PowPak
® Dimming Module with EcoSystem®
does NOT support the C5-XPJ-16A switching module.
NOTE: Wired sensors connected to EcoSystem
®
devices are NOT supported.
Default Operation
•Associatedwirelessinputdevicescontrolall
connected EcoSystem
® LED drivers
•OccupancySensors:
–Occupied:100%;Unoccupied:0%(OFF)
•Pico
®Controls:
–On:100%;FavoriteLevel:50%;Off:0%(OFF)
•DaylightSensor:Decreaseselectriclightinresponse
to additional available daylight
Key Design Features
•LEDstatusindicatorsshowcommunicationstatusand
provide programming feedback
•Powerfailurememory:Ifpowerisinterrupted,
connected loads will return to the previous level prior
to interruption
•EcoSystem
® link miswire protection up to 347 V ~
•Daylightoverride:Pressingtheraisebuttononan
associated Pico
® will temporarily override daylighting
for the fixtures in that Pico
® group
Daylighting will be re-enabled for that Pico
® group
whenoneofthefollowingoccurs:
•Twohourshavepassedsincetheoverride.*
•ON,OFForPresetbuttonhasbeenpressedona
Pico
® controlling that group.
•AllassociatedOccupancySensorshavereported
unoccupied.
* Eachtimeadaylightingoverrideoccursforany
Pico
® group, the two hour timer is reset.
2
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 3 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
System Diagram
Test
Lutron® LED
Drivers
Lutron® LED
Drivers
Upto32
EcoSystem®
LED drivers
Radio Powr Savr
Occupancy Sensor (up to 6)
Radio Powr Savr
Daylight Sensor (up to 1)
Pico
® Control (up to 9)
EcoSystem
® digital link
Wiring Diagram
100 V~ 200 V~
HOT
NEUTRAL
GROUND
E1
E2
To LED Drivers
Junction Box
Green
White
Black
LIVE 1
LIVE 2
GROUND
E1
E2
To LED Drivers
Junction Box
Green
Red
Black
From
2-pole
circuit
breaker
[
3
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 4 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring Diagram
Input Voltage
To LED drivers
Conduit
Nut
White
(Neutral)
Black
(Hot)
Green
(Ground)
E2
E1
NOTE: Use0.75to1.5mm
2
(18 to 16AWG)
solid wire.
Please use 1.6 mm
2
or 2.0 mm
2
diameter copper wire.
Strip off 10 mm of the insulated coating on the wire and
straighten the wire if it bends.
Shown,
actual size
1
2
3
10 mm
1
2
3
4
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 5 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak®InstallationInsideJunctionBox
(Dimming Module RMP-ECO32-JA-B shown)
Antenna
BOX ABOX B
Insomeapplications,aPowPak®modulecanbeinstalledinsideajunctionbox.
A) Remove the label tab by tearing at the perforation.
B) Lift the flexible antenna on the PowPak® module from the cutout on the right side of the antenna trough.
C) Extend the antenna out from the left side of the PowPak® as indicated.
+
-
+
-
+
-
+
-
Remove label tab
at perforations
Lift out
antenna
here
A
B
C
Extend
antenna
here
Mounting within a Junction Box
5
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 6 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
Dimensionsareshownas:mm
Range Diagram
100.1
71.6 31.8
86.9
All Wireless Transmitters must be installed within
7 m of the PowPak® Dimming Module.
Test
7 m
Maximum
12 m
10 m
PowPak®
Dimming Module
Installincenterofroomto
maximize RF coverage.
Pico®
Wireless
Transmitter
•ContactLutronrstforapplicationsusingfoil-backedormetallicceilingtiles.
21.7 mm
diameter
Radio Powr Savr
Occupancy Sensor
6
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369-675b 7 09.05.12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Advanced Configurations
Pico® Wireless Controls
•UptoninePico
® devices, each with their own control
group
•Eachgroupcanincludeanyoftheconnecteddrivers
•FavoritelevelscanbesetforeachPico
® wireless control
Radio Powr Savr
Daylight Sensor
•Uptotwodaylightingrowscanbecongured
•TheRadioPowrSavr
daylight sensor group can
include up to 32 drivers
Minimum Light Level Setting (optional)
•Certainapplications,suchashallways,mayrequire
that the lights never turn off. For these areas, select
the10%minimumlightleveloption.
Window
Pico® group 1
Pico®
group 1
Pico®
group 2
Pico
®
group 3
Occupied
Unoccupied
Pico® group 2
Pico
® group 3
Window
Window
Off or at 10% Off or at 10%
On Unaffected
Window
Daylighting Row 1
Daylighting Row 2
Test
Test
Window
Pico® group 1
Pico®
group 1
Pico®
group 2
Pico
®
group 3
Occupied
Unoccupied
Pico® group 2
Pico
® group 3
Window
Window
Off or at 10% Off or at 10%
On Unaffected
Window
Daylighting Row 1
Daylighting Row 2
Test
Test
High-End Trim
•Themaximumlightoutputofconnecteddriverscan
bedecreasedbyupto50%forenergysavingsin
over-lit spaces
•High-EndTrimaffectsallconnecteddriversequally,
and can be configured from the dimming module or
from any associated Pico
®
Radio Powr Savr
Occupancy Sensors
•RadioPowrSavr
occupancy and vacancy sensors
control all connected drivers
•GroupedPico
®controlscanbeusedtoadjustthe
Occupied levels of drivers that they control from
1%to100%orcanmakethemunaffectedby
Occupancy events
•Vacancyevents(areabecomesunoccupied)turnall
driversofforto10%,ifminimumlightlevelisset
Window
Pico® group 1
Pico®
group 1
Pico
®
group 2
Pico
®
group 3
Occupied
Unoccupied
Pico® group 2
Pico
® group 3
Window
Window
Off or at 10% Off or at 10%
On Unaffected
Window
Daylighting Row 1
Daylighting Row 2
Test
Test
Window
Pico® group 1
Pico®
group 1
Pico
®
group 2
Pico
®
group 3
Occupied
Unoccupied
Pico® group 2
Pico
® group 3
Window
Window
Off or at 10% Off or at 10%
On Unaffected
Window
Daylighting Row 1
Daylighting Row 2
Test
Test
7