SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
™
Relay Module Energi TriPak
™
Series Wireless Lighting Control
369-549b 2 01.23.12
Specifications
Regulatory Approvals
RMJ- models only
•ULListed
•UL2043PlenumRated
•FCCapproved.ComplieswiththelimitsforaClassB
device, pursuant to Part 15 of the FCC rules.
•CSAandIC
•COFETEL
•NOM
Power
•Operatingvoltage:
RMJ- models 120 / 277 V ~
50 / 60Hz
RMQ- models 220-240 V ~
50 / 60Hz
RMM- models 220-240 V ~
50 / 60Hz
System Communication
•OperatesusingClearConnect
™
RF Technology
for reliable wireless communication; refer to model
number chart on page 1 for frequency band details
•RFrangeis30ft(10m)
Environment
•Ambientoperatingtemperature:32°Fto131°F
(0°Cto55°C)
•0%to90%humidity,non-condensing
•Forindooruseonly
Load
•Maximumload:5Ageneralpurpose.Nominimum
load requirements.
•Loadtypesinclude(butarenotlimitedto):
–Incandescent
– MLV
– ELV
– Resistive
–Inductive
– Magnetic fluorescent
– Electronic fluorescent
•Motorrating:
RMJ- models 1/6 HP (120V~), 1/3 HP (277V~)
RMQ- models 1/2 HP (220-240V~)
RMM- models 1/2 HP (220-240V~)
•Loadrelayisnon-latching
Key Design Features
•LEDstatusindicatorshowscurrentloadstatusand
provides programming feedback
•Powerfailurememory:Ifpowerisinterrupted,
connected loads will return to the previous level prior
to interruption
•DaylightingcanbeoverriddenbypressingtheON
button on any associated Pico®
– Daylighting will be re-enabled after 2 hours or after
the area becomes unoccupied
Contact Closure Output (CCO version only)
•Providesoccupancystatusto3rd-partyequipment
such as building management systems, HVAC, and
VAV controllers
•Providesbothnormallyopen(NO)andnormally
closed (NC) dry contacts
•Maintainedoutputtype
•CCOterminalsaccept20to16AWG(0.5 to 1.5 mm
2
)
solid or stranded wire
•Outputislatching
•Notforvoltagesgreaterthan24V
•TheCCOisnotratedtocontrolunclamped,
inductiveloads.Inductiveloadsinclude,butarenot
limited to, relays, solenoids, and motors. To control
these types of equipment, a flyback diode must be
used (DC voltages only). See diagram below. For
more information, please see Application Note #434
(p/n 048434).
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-