PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 1 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module
The PowPak® CCO Module is a low-voltage radio frequency
(RF) control that provides a single dry contact closure
output based on input from Pico
® controls and Radio Powr
Savr
TM occupancy and daylight sensors. It can be powered
by to 24 V~ or 24 V- for easy connection and integration
into building management, HVAC, VAV, and other 3rd-party
systems.
Communication with RF input devices, such as Pico
®
controls and Radio Powr Savr
TM sensors, is accomplished
using Lutron
® Clear Connect® RF Technology.
Features
Single contact closure output including both normally open
(NO) and normally closed (NC) dry contacts
Maintained output type
Operates at 24 V~ or 24 V-
Receives wireless inputs from up to nine Pico
® controls, six
Radio Powr Savr
TM occupancy/vacancy sensors, and one
Radio Powr Savr
TM daylight sensor
• Utilizes Lutron
® Clear Connect® RF Technology – refer to
model number chart below for frequency band data
Screw tabs provided for surface mounting (recommended);
or mounts to a U.S style junction box through a standard
size knockout
Models Available
Model Number Region Operating Voltage Frequency Band
RMJ-CCO1-24-B U.S.A., Canada, Mexico 24 V~ or 24 V- 431.0437.0 MHz
URMJ-CCO1-24B U.S.A.
(BAA Compliant) 24 V~ or 24 V- 431.0437.0 MHz
RMQ-CCO1-24-B Hong Kong, Macau 24 V~ or 24 V- 433.05434.79 MHz
RMM-CCO1-24-B China, Singapore 24 V~ or 24 V- 868.125–868.475 MHz
RMK-CCO1-24-B Europe, U.A.E. 24 V~ or 24 V- 868.125–868.850 MHz
RMN-CCO1-24-B India 24 V~ or 24 V- 865.5866.5 MHz
RMP-CCO1-JA-B Japan 24 V~ or 24 V- 313.3314.8 MHz
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
RMJ-CCO1-24-B model shown
1
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 2 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Environment
Ambient operating temperature: 32 °F to 131 °F
(0 °C to 55 °C)
0 to 90% humidity, non-condensing
For indoor use only
Contact Closure Output
Accepts input voltages of 0–24 V ~ / 0–24 V-; see
chart below for load switching capacities
Provides both normally open (NO) and normally
closed (NC) dry contacts
Maintained output type
CCO terminals accept 20 AWG to 16 AWG
(0.5 mm
2
to 1.5mm
2
) solid or stranded wire
Output is latching
The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited
to, relays, solenoids, and motors. To control these
types of equipment, a flyback diode must be used
(DC voltages only). See diagram below. For more
information, please see Application Note #434
(P/N 048434).
Specifications
Regulatory Approvals
RMJ- & URMJ- models
• UL
® Listed (USA)
FCC approved. Complies with the limits for a Class B
device, pursuant to Part 15 of the FCC rules. (USA)
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Listed in accordance to CAN/ULC S102.2-2010 with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
CSA and IC (Canada) (RMJ- only)
COFETEL (Mexico) (RMJ- only)
NOM (Mexico) (RMJ- only)
RMN- Model
WPC Type Approved (India)
RMK- Model
CE (European Union)
TRA Type Approved (United Arab Emirates)
Power
• IEC PELV/NEC
® Class 2
Operating voltage: 24 V~ / 24 V-
Operating current, nominal: 45 mA (24 V~)
35 mA (24 V-)
Standby Power Consumption (all models): < 1.0 W
System Communication
Operates using Clear Connect
® RF Technology for reli-
able wireless communication; refer to model number
chart on page 1 for frequency band details
RF range is 30 ft (9 m) for RMJ-, URMJ-, RMQ-, RMM-,
RMK-, RMN- models
RF range is 23 ft (7 m) for RMP- models
Contact Lutron first for applications using foil-backed or
metallic ceiling tiles.
Switching
Voltage
0-24 V-
0-24 V~
Resistive
Load
1.0 A
0.5 A
R
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
+
-
2
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 3 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
Dimensions are shown as: in (mm)
Range Diagrams
RMJ-, URMJ-, RMQ-, RMM-, RMK-, RMN- models RMP- models
Contact Lutron first for applications using foil-backed or metallic ceiling tiles.
All Wireless Transmitters must be installed within
30 ft (9 m) of the PowPak® Module.
All Wireless Transmitters must be installed within
23 ft (7 m) of the PowPak® Module.
Test
Test
30 ft (9 m)
Maximum
23 ft (7 m)
Maximum
40 ft (12 m) 40 ft (12 m)
30 ft (9 m)
30 ft (9 m)
PowPak®
CCO Module
PowPak
®
CCO Module
Install in center of room to
maximize RF coverage.
Install in center of room to
maximize RF coverage.
Pico®
Wireless
Transmitter
Pico®
Wireless
Transmitter
Radio Powr Savr
TM
Occupancy Sensor
Radio Powr Savr
TM
Occupancy Sensor
1/2 in or 21 mm trade size
knockout opening
3.94
(100)
3.42
(87)
2.82
(72)
1.25
(32)
3
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 4 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Default Operation
Transmitting Device Transmitted Command CCO Default Action
Pico
® Wireless Control On NO = Close, NC = Open
Off NO = Open, NC = Close
Raise No Action
Lower No Action
Preset NO = Close, NC = Open
Radio Powr Savr
TM
Occupancy Sensor
Occupied NO = Close, NC = Open
Unoccupied NO = Open, NC = Close
Radio Powr Savr
TM
Vacancy Sensor
Occupied No Action
Unoccupied NO = Open, NC = Close
Radio Powr Savr
TM
Daylight Sensor
Ambient Light Below
Target Level
NO = Close, NC = Open
Ambient Light Above
Target Level
NO = Open, NC = Close
System Diagram
Radio Powr SavrTM Occupancy Sensor (up to 6)
Radio Powr Savr
TM Daylight Sensor (up to 1)
Pico
® Control (up to 9)
To 3rd-Party
Equipment
To power source
4
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 5 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring Diagram (Recommended)
NOTE: When wiring CCO output, use
20 AWG to 16 AWG (0.5 mm
2
to 1.5 mm
2
)
solid or stranded wire.
To CCO controlled device.
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
Supply Voltage
24 V~ /24 V-
NOTE: CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
Wire Nut
(2 Supplied)
NOTE: The CCO output may be wired using either the NO or NC terminal.
Refer to the Default Operation chart on page 6 for more information
regarding the behavior of the CCO output terminals.
NOTE: RMJ-, URMJ-, RMQ-, RMM- and RMN- models are
supplied with three twist-on wire connectors. RMK- and RMP-
models are supplied with Lever Operated Connectors. See
Installation sheets for RMP- and RMK- models for Lever Operated
Connector information.
5
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 6 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring Diagram (Junction Box Optional)
*
NOTE: Some applications (in USA) require the
PowPak® module to be installed inside an additional
junction box. For information about how to perform
this installation, please visit www.lutron.com,
Application Note #423 (P/N 048423). Please consult
all local and national electric codes for proper
installation methods.
Supply Voltage
24 V~ / 24 V-
Junction Box
*
To 3rd-Party
Equipment
NC
NO
COM
Switching
Voltage
0-24 V-
0-24 V~
Resistive
Load
1.0 A
0.5 A
R
6