PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369433g 2 07.21.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Environment
• Ambient operating temperature: 32 °F to 131 °F
(0 °C to 55 °C)
• 0 to 90% humidity, non-condensing
• For indoor use only
Contact Closure Output
• Accepts input voltages of 0–24 V ~ / 0–24 V-; see
chart below for load switching capacities
• Provides both normally open (NO) and normally
closed (NC) dry contacts
• Maintained output type
• CCO terminals accept 20 AWG to 16 AWG
(0.5 mm
2
to 1.5mm
2
) solid or stranded wire
• Output is latching
• The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited
to, relays, solenoids, and motors. To control these
types of equipment, a flyback diode must be used
(DC voltages only). See diagram below. For more
information, please see Application Note #434
(P/N 048434).
Specifications
Regulatory Approvals
RMJ- & URMJ- models
• UL
® Listed (USA)
• FCC approved. Complies with the limits for a Class B
device, pursuant to Part 15 of the FCC rules. (USA)
• Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
• Listed in accordance to CAN/ULC S102.2-2010 with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
• CSA and IC (Canada) (RMJ- only)
• COFETEL (Mexico) (RMJ- only)
• NOM (Mexico) (RMJ- only)
RMN- Model
• WPC Type Approved (India)
RMK- Model
• CE (European Union)
• TRA Type Approved (United Arab Emirates)
Power
• IEC PELV/NEC
® Class 2
• Operating voltage: 24 V~ / 24 V-
• Operating current, nominal: 45 mA (24 V~)
35 mA (24 V-)
• Standby Power Consumption (all models): < 1.0 W
System Communication
• Operates using Clear Connect
® RF Technology for reli-
able wireless communication; refer to model number
chart on page 1 for frequency band details
• RF range is 30 ft (9 m) for RMJ-, URMJ-, RMQ-, RMM-,
RMK-, RMN- models
• RF range is 23 ft (7 m) for RMP- models
• Contact Lutron first for applications using foil-backed or
metallic ceiling tiles.
Switching
Voltage
0-24 V-
0-24 V~
Resistive
Load
1.0 A
0.5 A
R
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
+
-