SPECIFICATION SUBMITTAL
grx-av-1 06.14.04
Control Interfaces
GRX-AV
®
GRX-AV Control Interface
Description
• Integrates a GRAFIK Eye Lighting Control System
with equipment that has contact-closure I/O, including:
– Motion and occupant sensors.
– Timeclocks and push buttons.
– Motorized projection screens, skylights, window
shades, and movable walls.
– AV equipment.
– Security systems.
• May be programmed to control any combination of
one to eight GRAFIK Eye 3000 or 4000 Series Control
Units.
Inputs/Outputs
• Provides five inputs and five outputs.
• Using the inputs, contact closures in other equipment
can operate Control Units to:
– Select scenes.
– Run sequences (loop through scenes).
– Lock Control Units.
– Activate panic mode (lights go full on).
– Adjust scenes to reflect status of movable walls.
– Turn lights on or off based on room occupancy.
• Using the outputs, scene changes in Control Units can:
– Trigger outputs to control other equipment.
– Provide status feedback to other equipment.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-av-2 06.14.04
Control Interfaces
GRX-AV
®
Power
• Low-voltage Class 2 (PELV).
Operating Voltage: 12/24 V Direct Current.
• Provides 2-way interface between preset lighting controls and dry contact closure devices.
• Provides 5 inputs and 5 outputs. Outputs can control other manufacturers’ equipment.
Operating Modes
• Scene selection
• Special functions
Partitioning
• Occupant sensor
Five Input Terminals
• Accept maintained inputs and momentary inputs with 40msec minimum pulse times.
• Inputs must be dry contact closure or open collector (NPN).
• On-state saturation voltage must be less than 2.0VDC.
• Off-state leakage current must be less than 10µA.
• Open circuit voltage: 36V maximum.
• Short circuit current: 4.0µA maximum.
Five Output Terminals
• Provide solid-state maintained or momentary (1-second) outputs.
• Outputs require an external relay and power supply (30VDC max., Class 2/PELV)
by others for contact closure devices.
• Maximum voltage: 38V
• Maximum current: 200mA
• Open collector (NPN) output: On-state saturation voltage 1.0V maximum,
off state leakage current 0.1µA maximum.
Status LEDs
Five Status LEDs light when associated output is active (on).
System Communications and Capacity
Low-voltage type Class 2 (PELV) wiring connects GRX-AV Interface to Control Units and
other components. Counts toward system maximum of 16 Wallstations/Control Interfaces.
Environment
32-104°F (0-40°C). Relative humidity less than 90% non-condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-av-3 06.14.04
Control Interfaces
GRX-AV
®
Mode DIP Switches Contact closures invoke: Inputs: Outputs:
5 6 7 8 Input 1 Input 2 Input 3 Input 4 Input 5
Scene Scene 1 Scene 2 Scene 3 Scene 4 Off Maintained or Maintained
Selection
Scene 5 Scene 6 Scene 7 Scene 8 Off momentary
Scene 9 Scene 10 Scene 11 Scene 12 Off
Scene 13 Scene 14 Scene 15 Scene 16 Off
Scene 1 Scene 2 Scene 3 Scene 4 Off Maintained or Momentary
1
Scene 5 Scene 6 Scene 7 Scene 8 Off momentary
Scene 9 Scene 10 Scene 11 Scene 12 Off
Scene 13 Scene 14 Scene 15 Scene 16 Off
Special Sequence Zone lockout Scene
“Panic”mode
Not Maintained only Maintained
Functions scenes 1-4 allows lockout turns lights used
Sequence
temporary disables full on (to
scenes 5-16
adjustments. scene scene 16),
Sequence
No changes to buttons.
locks Control
Momentary only Maintained
scenes 1-4
preset scenes.
Units.
Sequence
scenes 5-16
Partitioning
2
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Momentary only Maintained
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Maintained only Maintained
Occupant Sensor input toggles Control Units between scene 1 and off. Maintained only
3
Maintained
Sensor
Sensor input turns Control Units off. Occupant must turn lights on. Maintained only
3
Maintained
• Operating mode can be selected by setting DIP
switches 5 through 8. Inputs and outputs may be
maintained or momentary as indicated.
• May be programmed to control any combination of
one to eight GRAFIK Eye 3000 or 4000 Series Control
Units.
• For scene selection and special function modes,
one Control Unit or a group of Control Units may
be assigned to be operated by the GRX-AV.
• With partitioning and occupant sensor modes, a
different Control Unit or group of Control Units
may be assigned for each I/O closure.
1
Scenes trigger the position of motorized window shades or projection screens.
2
Movable walls toggle Control Units between “in combination” and “independent” modes of operation. Each input is setup to
operate the Control Units associated with a movable wall (or walls).
• When a motorized wall opens, the wall’s switch contact closes. The Control Units now work “in combination.” Scene changes at
one Control Unit occur on all the associated Control Units.
• When a wall closes, the switch contact opens. The Control Units return to independent operation.
3
If an occupant sensor input provides momentary closure, use scene selection mode.
Operating Modes and DIP Switch Settings
3
R
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-av-4 06.14.04
Control Interfaces
GRX-AV
®
Job Name:
Job Number:
• Mount on a 4" (10.2mm) square junction box.
• May also mount directly to the wall.
• Ensure that the metal casing is grounded. Connect a
ground wire to the ground screw.
• Note that wires do not feed through the back of the unit.
GRX-AV
4”x4”
Junction
Box
Insert Wires
Through
Punch-Outs
Wall
GRX-AV
Wall
Dimensions
Front
Side
MUX LINK
INPUTS OUTPUTS
COM
+V
MUX
PROGRAM
SWITCH
COM
COM
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
MUX
MUX LINK
INPUTS OUTPUTS
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
1 2 3 4 5 6 7 8
0 = ON; 1 = OFF
1 2 3 4
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
1 2 3 4
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
1 2 3 4
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 2 3 4
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
ADDRESS
1
2
3
4
ADDRESS
5
6
7
8
ADDRESS
9
10
11
12
ADDRESS
13
14
15
16
DIP SWITCH SETTINGS (1-4)
GRX-AV
AUDIOVISUAL CONTROL
CLASS 2 DEVICE
COOPERSBURG, PA 18036
ADDRESS
CONFIG.
TYPE
1 2 3 4 5 6 7 8
ON
OFF
4S CONTROL SCENES 1-4 5 ON 6 ON
SCENES 5-8 5 OFF 6 ON
7 ON 8 ON SCENES 9-12 5 ON 6 OFF
SCENES 13-16 5 OFF 6 OFF
4PS CONTROL MAINTAIN INPUTS 5 OFF
MOMENTARY INPUTS 5 ON
7 OFF 8 ON SWITCH 6 UNUSED
SPECIAL 1 CHANNEL FINE TUNING STATION 5 ON 6 ON
CONTROL NeTwork/HOMEWORKS STYLE CONTROL 5 ON 6 OFF
OCCUPANCY SENSOR - SCENE 1 & OFF 5 OFF 6 ON
7 OFF 8 OFF OCCUPANCY SENSOR - OFF ONLY 5 OFF 6 OFF
4Q CONTROL MAINTAIN INPUTS 5 OFF
MOMENTARY INPUTS 5 ON
7 ON 8 OFF SEQUENCE 1-4 6 ON
SEQUENCE 5-16 6 OFF
DIP SWITCH SETTINGS (5-8)
TYPE DIP SETTINGCONFIGURATION
R
DIP
Switches
MUX Link to
GRAFIK Eye
Control Units
and
Wallstations
6”
(127mm)
7 3/4”
(197mm)
2 1/2”
(84mm)
Mounting
Class 2 (PELV)
Wiring
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-av-5 06.14.04
Control Interfaces
GRX-AV
®
• Make daisy-chain connections to the low-voltage Class 2 (PELV)
MUX Link terminals on front of GRX-AV Interface.
• Do not use T-taps. Run all wires in and out of the terminal block.
• Each terminal accepts up to two #18 AWG (1.0mm
2
) wires.
Low-Voltage Class 2 (PELV) Wiring
NEUTRAL
SSA
ZONE 3
ZONE 2
ZONE 1
HOT/LIVE
CU WIRE ONLY
1 2 3 4
Inputs Outputs
MUX Link
C 1 2 3 4 5 1 2 3 4 5 C
+
V
1
2
35
4
Input 1
Input 2
Input 3
Input 4
Input 5
Output 1
Output 2
Output 3
Output 4
Output 5
Power
Supply
COM
+V
MUX
MUX
Program
Switch
To additional Wallstations/Control Interfaces
(16 Maximum; three from one Control Unit
without external 12VDC power supply)
User-Supplied Equipment
Lutron Cable
GRX-CBL-346S
Rear View of GRAFIK Eye Control Unit
(GRX-3103 shown)
GRX-AV
Power Supply
(User-Supplied,
30 V DC max.)
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-av-6 06.14.04
Control Interfaces
GRX-AV
®
MUX LINK
INPUTS OUTPUTS
COM
+V
MUX
PROGRAM
SWITCH
COM
COM
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
MUX
MUX LINK
INPUTS OUTPUTS
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
1 2 3 4 5 6 7 8
When used with GRX-3000 Control Units
• Two #18 AWG (1.0mm
2
) conductors for common (terminal 1) and 12VDC (terminal 2).
Ensure that the terminal 2 connection is wired correctly. Refer to GRX-3000 Specification
Submittal for additional details.
• One shielded, twisted pair of #18 AWG (1.0mm
2
) for data link (terminals 3 and 4).
When used with GRX-4000 Control Units
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1) and 24VDC (terminal 2).
These will not fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground (Earth) or Wallstation/Control
Interfaces. Connect the bare drain wires and cut off the outside shield.
Data Link - (1) twisted,
shielded pair #18 AWG
(1.0mm
2
)
3: MUX
4: MUX
Class 2/PELV
Control wiring
1: Common
2: 24VDC
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(1) #18 AWG
(1.0mm
2
)
Class 2 (PELV) Terminal Connections
GRX-AV
6