Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369362c 1 04.07.17
Control Interfaces
GRX-CI-NWK-EGRAFIK Eye
GRX-CI-NWK-E Control Interface
Description
•IntegratesaGRAFIKEyeLightingandShadeControl
Systemwithatouchscreen,PC,orotherdigital
equipmentthatsupportsTCP/IPcommunication
overEthernet.
•TCP/IPprovidesfastreliabletwo-way
communication.
•Providesmonitoringcommandsthatallowa
touchscreenorPCtoqueryGRAFIKEyeControl
Unitsto:
-Determinewhichsceneisselected.
-Readindividualzone’sintensity.
-Keeptrackofbuttonspressed.
•Providescontrolcommandsthatallowatouchscreen
orPCtooperateGRAFIKEyeControlUnitsto:
-Selectorsequencelightingscenes.
-RaiseorLoweroneormorezones.
-LockGRAFIKEyeControlUnits.
-SetZoneIntensityonGRAFIKEye3500or4500
SeriesControlUnits,whichallowsuserstoset
intensitiesonzonesoflightandtoraiseandlower
anindividualshadezone(SivoiaQEDshades
alsoallowtheselectionofindividualshadezone
presets).
•FunctionalityissetusingDIPswitches.
•Maybeprogrammedtocontrolanycombination
ofonetoeightGRAFIKEye3000or4000Series
ControlUnits.
1
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369362c 2 04.07.17
Control Interfaces
GRX-CI-NWK-EGRAFIK Eye
DIPSwitch
1
2
3
4
5
6
7
8
Function
ZoneLockRetain
SceneLockRetain
SequenceRetain
SequencingSceneRange
MultipleAddresses
1
ButtonFeedback
SceneStatus
NotUsed
WhensettoON
Ifpowergoesout,lockedzonesstay
lockedwhenpowerreturns.
Ifpowergoesout,lockedscenesstay
lockedwhenpowerreturns.
Ifpowergoesout,sequencingresumes
whenpowerreturns.
Sequencingloopsthroughscenes5to16.
DIPSwitches1-4usedtosetaddress,
notfunction.
InterfacereportsControlUnitand
Wallstationbuttonpresses.
Interfacereportsscenechanges.
WhensettoOFF
Powercyclingunlockslocked
zones.
Powercyclingunlockslocked
scenes.
Powercyclingstopssequencing.
Sequencingloopsthrough
scenes1to4.
DIPSwitches1-4operateas
specifiedabove.
Noreportingofbuttonpresses.
Noreportingofscenechanges.
Functions
1
OnlyforprojectswithmorethanoneControlInterfacethatuseRS232orEthernetcommunications(GRX-CI-PRG,
GRX-CI-RS232,orGRX-CI-NWK-E).OneInterfaceintheprojectautomaticallyassumesaddress16–DIPswitchesdonotneedto
besettogiveitanaddress.(IfaGRX-CI-PRGispresent,itmustassumeaddress16.)EveryotherRS232orEthernetInterfacein
theprojectmusthaveauniqueaddress:SetDIPswitch5toonandthenuseDIPswitches1-4toassignauniqueaddress.
Regulatory Approvals
•Forcommercialuse,ClassAonly
•cULusListed
Power
•IECPELV/NEC®Class2
•OperatingVoltage:12V-125mA
24V-65mA
Uses RS232 Command Set for GRAFIK Eye 3000/4000
•Monitoring:Sceneselection,scenestatusupdates,readzoneintensity.
•Control:Sceneselection,scenelockout,sequencing,zonelockout,zoneraise/lower.
•AdditionalcontrolwithGRAFIKEye3500or4500SeriesControlUnits:Setzoneintensity.
System Communications and Capacity
•Low-voltageIECPELV/NEC®Class2wiringconnectstheControlInterfacetoGRAFIKEyeControlUnits.
•StandardCAT5cable,328ft(100m)maximum,connectsGRX-CI-NWK-EInterfacetoPCorotherEthernet
source.
•SupportsMDI/MDIXauto-crossover(nocrossovercableneeded).
•Auto-negotiationof10or100Mbpsspeedandfull-orhalf-duplexoperation.
•MultipleControlInterfacesmaybeusedinasinglesystem.
Environment
•32to104°F(0to40°C).Relativehumiditylessthan90%non-condensing.
Specifications
2
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369362c 3 04.07.17
Control Interfaces
GRX-CI-NWK-EGRAFIK Eye
Dimensions
DIPSwitches
MUXLinkto
GRAFIKEye
ControlUnitsand
Wallstations
MUXLinkTX
(LED6)
EthernetLink
(toPCorAV
Equipment)
IECPELV/
NEC®Class2Wiring
2.47in
(62.7mm)
3.75in
(95.3mm)
4.26in
(108.2mm)
5.26in
(133.6mm)
1.06in
(26.9mm)
Power(LED1)
EthernetLink
(LED2)
MUXLinkRX
(LED7)
12or24V
Mounting
Holes
Mounting
1.Mountthecontrolinterfacedirectlyonawall,as
shownintheMountingDiagram,usingscrews(not
included).Whenmounting,providesufcientspace
forconnectingcables.
TheunitcanalsobeplacedintheLUT-19AV-1UAV
rackusingthescrewsprovidedwiththeunit.The
LUT-19AV-1Uwillholduptofourunits.
Ifconduitisdesiredforwiring,theLUT-5x10-ENC
canbeusedtomountoneunit.
2.Strip4in(10mm)ofinsulationfromwires.Eachdata
linkterminalwillacceptuptotwo18AWG
(1.0mm
2
)wires.
3.ConnectwiringasshownintheWiringDiagram
(nextpage).LED1lightscontinuously(Power)and
LED7blinksrapidly(DataLinkRX)whentheIEC
PELV/NEC®Class2DataLinkisinstalledcorrectly.
LU T-19AV-1U
WireStripLength
4in
(10mm)
5.26
4.263.75
2.50
1.06
ControlInterface
Wall
Mounting Diagram
LUT-5x10-ENC
0.25
(6.4)
0.34(8.6)
dia.
0.18(4.6)
dia.
0.18(4.6)
dia.
#6or#8(M3orM4)
screwrecommended
(notincluded)
Mounting Hole Detail
Dimensions:in(mm)
3
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369362c 4 04.07.17
Control Interfaces
GRX-CI-NWK-EGRAFIK Eye
ZONE 6
ZONE 4
HOT/LIVE
SSA
CU WIRE ONLY
ZONE 2
ZONE 3
ZONE 5
NEUTRAL
ZONE 1
CLASS 2
1 2 3 4
USA
Class 2
IEC
PELV
4 3 2 1
ToadditionalWallstations/ControlInterfaces
16maximum,threepoweredfromoneGRAFIKEyeControlUnit
(GRX-CI-NWK-Ecountsastwodevicestowardthemaximumof
threeconnectedtoonecontrolunitwhennotusingoptional
transformer).
CAT5Cable
328ft(100m)
Maximum
ToPCorAV
Equipment
RearViewofGRAFIKEyeControlUnit
(GRX-3106shown)
Ethernet Link Wiring
•StandardCAT5cableconnectsGRX-CI-NWK-EInterfacetoPC,router,orother
Ethernetsource.
•Nocrossovercableneeded.
•Mustbe328ft(100m)orless.
•Ethernetnetworkandcableprovidedbyothers.
•Makedaisy-chainconnectionstotheIECPELV/NEC®Class2
MUXLinkterminalsonthebackoftheControlInterface.
•DonotuseT-taps.Runallwiresinandoutofterminalblock.
•Eachterminalacceptsuptotwo18AWG(1.0mm
2
)wires.
•LED1lights(power)andLED7blinksrapidly(MUXLinkRX)whenthe
IECPELV/NEC®Class2MUXLinkisinstalledcorrectlyandGRAFIK
Eye ControlUnit(s)areaddressed.
IEC PELV/NEC® Class 2 Wiring
LutronCable
GRX-CBL-346S
Power Options
•PowerforoneGRX-CI-NWK-Ecountsastwodevicestowardthemaximumof
threedevicesperGRAFIKEyeControlUnitwhenpoweredoffofPin2ofthe
MUXLink.
•ToPowerseparatelyfromtheMUXLinkorderthefollowingtransformermodel
numbers.
120V~ T120-15DC-9-BL
240V~ TE240-15DC-9-BL
240V~(UK) TU240-15DC-9-BL
•DonotconnectPin2oftheMUXLinktotheGRX-CI-NWK-Ewhenusing
optionaltransformer.
ToOutlet
(withoptional
transformer).
Donotwire
Pin2when
using
transformer.
ControlInterface
Wiring
DataLink-4:MUX
3:MUX
IECPELV/NEC®Class2
Controlwiring
2:12V- Power
1:Common
4
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369362c504.07.17
Control Interfaces
GRX-CI-NWK-EGRAFIK Eye
4 3 2 1
DataLink-(1)twisted,shieldedpair
18AWG(1.0mm
2
)
3:MUX
4:MUX
IECPELV/NEC®Class2
Controlwiring
1:Common
2:24V- Power
D:Drain/Shield
(2)12AWG
(2.5mm
2
)
(2)12AWG
(2.5mm
2
)
(1)18AWG
(1.0mm
2
)
(1)18AWG
(1.0mm
2
)
When used with GRX-3000 Control Units
•Two18AWG(1.0mm
2
)conductorsforCommon(terminal1)and12V-(terminal2).
RefertoGRX-3000SpecificationSubmittalformoredetails.Ensurethattheterminal2connectioniswiredwhen
notusingoptionaltransformer.
•Oneshielded,twistedpair18AWG(1.0mm
2
)fordatalink(terminals3and4).
When used with GRX-4000 Control Units (See Wiring Diagram Below)
•Two12AWG(2.5mm
2
)conductorsforCommon(terminal1)and24V-(terminal2).Thesewillnotfit
interminals.Connectasshown.Ensurethattheterminal2connectioniswiredwhennotusingoptional
transformer.
•Oneshielded,twistedpair18AWG(1.0mm
2
)fordatalink(terminals3and4).
•ConnectDrain/Shieldasshown.DonotconnecttoGround(Earth)orWallstation/ControlInterfaces.Connectthe
baredrainwiresandcutofftheoutsideshield.
IEC PELV/NEC® Class 2 Terminal Connections
GRX-CI-NWK-E
)Lutron,Lutron,GRAFIKEyeandSivoiaaretrademarksof
LutronElectronicsCo.,Inc.registeredintheU.S.andother
countries.
5