S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
GRX-CI-PRG Control Interfaces
369363 Rev. B 2 06.02.11
Specifications
Standards
•CaliforniaEnergyCommission(CEC)Listed
Power
•IECPELV/NEC®Class2
•OperatingVoltage:12V
125mA
24V
65mA
Environment
•32to104°F(0to40°C).
•Relativehumiditylessthan90%non-condensing.
Basic Command Set
•Monitoring:Sceneselectionandscenestatus
updates.
•Control:Sceneselection,scenelockout,
sequencing,zonelockout,zoneraise/lower.
Astronomic Timeclock
•Allowslightingchangestooccurautomaticallybased
ontimeofdayand/ordayofweek/month,
aswellasrelativetosunriseandsunset.
•Supportsfourscheduleswith60lightingeventsper
scheduleandoneSuperSequence.
•Allowsusertostart,pause,andstopschedulesfrom
aPCoraWallstation.
•Providescommandstosetandmonitorthe
timeclock’stime,date,anddayofweek,andreport
sunriseandsunset.
•Ifalossofpoweroccurs,theprogrammedschedules
andthetimeofdaywillberetainedforaminimumof
10years.
Programmer Interface
Permitscompletesetupofthefollowingon
GRX-3500,GRX-4500,orGXI-3500controlunits
viaanIBM®-compatiblePC:
•Scenes,includinglightlevelsin1%incrementsand
fadetimes.
•Loadtypesettings.
•Tamper-proofprotectionofscenes.
•Assignmentofcommunicationbetweencontrol
unitsandwallstations.
•Dimmerpanelzoneandloadassignment
AllowsaWindows®-compatiblePCtoquery
GRX-3500,GRX-4500,andGXI-3500controlunits
fortheirsetup,includingtypeofcontrolunitand
numberofzones.
LIAISONTM Software
•ControloverTCP/IPrequiresLIAISONTMversion4.0
orlater.
•AllowsuseofaPCtocreatetimeclockschedules
forallGRX-3000,GRX-4000,andGXI-3000series
controlunits.
•AllowsuseofaPCtocreatesetupsforGRX-3500,
GRX-4500,andGXI-3500controlunits.
•Providesdownloadingofschedulesandsetupsto
GRX-CI-PRGinterfaceandcontrolunits.
•WorksonanyPCoperatingwithWindows®95
Windows®NT4.0,XP,orlater(excludingWindows®
VistaandWindows®7).
•SuppliedbyLutron.Updatesareavailableonlineat
www.lutron.com
System Communications and Capacity
•IECPELV/NEC®Class2wiringconnects
GRX-CI-PRGinterfacetocontrolunitsandother
components.
•OneGRX-CI-PRGInterfaceperGRAFIKEye®3000
or4000orGXI-3000system.Automatically
occupieswallstationaddress16.
•50ft(15m)maximumfromGRX-CI-PRGInterface
toPCorotherRS232source.
•328ft(100m)maximumfromGRX-CI-PRG
InterfacetoPCorotherEthernetsource.