Control Interfaces
GRX-PRG
®
GRX-PRG Programming Control Interface
Description
• Integrates a GRAFIK Eye Lighting Control System with a PC or
other digital equipment that supports RS232 communication.
• Provides a basic RS232 command set that allows a PC to
monitor and control lighting.
• Built-in Astronomic Timeclock provides ability to schedule
lighting events. Example: lobby lights turn on to scene 1 at
7:30 a.m. or 10 minutes after sunrise.
• Enables use of a PC to set up GRX-3500 and GRX-4500
Control Units.
• Comes with easy-to-use, “point-and-click” Windows
®-
compatible LIAISONTM software for scheduling the Astronomic
Timeclock and using the Programmer Interface.
• Functionality is selected using DIP switches.
• Operates with or without a PC connected.
• May be programmed to control any combination of
one to eight GRAFIK Eye 3000 or 4000 Series Control Units.
• GRX-3100 and GRX-4100 Control Units may utilize the
Astronomic Timeclock function of the GRX-PRG.
• GRX-3500 and GRX-4500 Control Units may utilize all
functions of the GRX-PRG.
Windows® is a registered trademark of Microsoft Corporation.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-prg-2 2.19.04
Control Interfaces
GRX-PRG
®
Power
Low-voltage Class 2 (PELV)
Operating Voltage: 12/24 V Direct Current.
Basic RS232 Command Set
• Monitoring: Scene selection and scene status updates.
• Control: Scene selection, scene lockout, sequencing, zone lockout, zone raise/lower.
Astronomic Timeclock
• Allows lighting changes to occur automatically based on time of day and/or day of week/month,
as well as relative to sunrise and sunset.
• Supports four schedules with 60 lighting events per schedule and one Super Sequence.
• Allows user to start, pause, and stop schedules from a PC, a Wallstation, or by a DIP switch on
the Interface.
• Provides commands to set and monitor the Timeclock’s time, date, and day of week, and report
sunrise and sunset.
Programmer Interface
Permits complete set up of the following on GRX-3500 or GRX-4500 Control Units via an
IBM
TM-compatible PC:
• Scenes, including light levels in 1% increments and fade times.
• Load type settings.
• Tamper-proof protection of scenes.
• Assignment of communication between Control Units and Wallstations.
• Dimmer Panel zone and load assignment
Allows an IBM-compatible PC to query GRX-3500 and GRX-4500 Control Units for their setup,
including type of Control Unit and number of zones.
LIAISONTM Software
• Allows use of a PC to create timeclock schedules for all GRX-3000 and GRX-4000 Control Units.
• Allows use of a PC to create setups for GRX-3500 and GRX-4500 Control Units.
• Provides downloading of schedules and setups to GRX-PRG Interface and Control Units.
• Works on any PC operating with Windows
® 3.1 or higher.
• Supplied by Lutron. Updates are available online at www
.lutron.com
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring connects GRX-PRG Interface to Control Units and other
components.
• One GRX-PRG Interface per GRAFIK Eye 3000 or 4000 system. Automatically occupies
wallstation address 16.
• 50 feet (15m) maximum from GRX-PRG Interface to PC or other RS232 source.
Environment
32-104°F (0-40°C). Relative humidity less than 90% non-condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-prg-3 2.19.04
Control Interfaces
GRX-PRG
®
Functions
DIP Switch
1
2
3
4
5
6
7
8
Function
Zone Lock Retain
Scene Lock Retain
Sequence Retain
Sequencing Scene Range
Not Used
Button Feedback
Scene Status
Astronomic Timeclock
Schedules
When set to ON
If power goes out, locked zones stay
locked when power returns.
If power goes out, locked scenes stay
locked when power returns.
If power goes out, sequencing resumes
when power returns.
Sequencing loops through scenes 5 to 16.
Interface reports Control Unit and
Wallstation button presses.
Interface reports scene changes.
Enables internal Timeclock.
When set to OFF
Power cycling unlocks locked
zones.
Power cycling unlocks locked
scenes.
Power cycling stops sequencing.
Sequencing loops through
scenes 1 to 4.
No reporting on button presses.
No reporting on scene changes.
Disables internal Timeclock.
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-prg-4 2.19.04
Control Interfaces
GRX-PRG
®
Dimensions
Front
Side
MUX LINK
1 2 3 4
1 2 3 4 5 6 7 8
LED1 LED2
1
PROGRAMMING INTERF ACE
AUXILIAR Y CONTROL
GRX-PRG
COOPERSBURG, PA 18036
R
1
2
3
4
5
6
7
8
ZONE LOCK
RETAIN
SCENE LOCK
RETAIN
SEQUENCE
RETAIN
SEQUENCE
TYPE
NOT USED
RAW FEEDBACK
SCENE ST ATUS
TIMECLOCK
ON/OFF
ZONE LOCKED UNITS WILL REMAIN IN
ZONE LOCK AFTER A POWER OUT AGE
SCENE LOCKED UNITS WILL REMAIN IN
SCENE LOCK AFTER A POWER OUT AGE
SEQUENCING UNITS WILL AGAIN
SEQUENCE AFTER A POWER OUT AGE
ON: SEQUENCE SCENES 5-16
OFF: SEQUENCE SCENES 1-4
INTERF ACE WILL REPOR T WHEN A BUTTON
HAS BEEN PUSHED OR RELEASED ON A
GRAFIK EYE MAIN UNIT OR ACCESSORY
INTERF ACE WILL RETURN THE CURRENT
SCENE OF ALL MAIN UNITS WHEN A NEW
SCENE IS SELECTED
WILL ENABLE INTERNAL TIMECLOCK
SWITCH FUNCTION DESCRIPTION
GRAFIK Eye 3000 Series
FOR WIRING OF 4000 SERIES, REFER
TO INST ALLATION INSTRUCTIONS
1 2 3 4
MUX LINK
1 2 3 4 5
RS232 LINK
PC OR A/V EQUIPMENT
RxD
TxD
COM
HOT/LIVE
SSA
Zone 3
Zone 2
Zone 1
CU WIRE ONL Y
Neutral
Class 2
4
3
2
1
For use with Lutron GRAFIK Eye
3500 and 4500 products only.
PELV (CLASS 2:USA)
R
2345
TO PC OR A/V
EQUIPMENT
TO GRAFIK
EYE
MUX LINK RS232 LINK
1 2 3 4 5
1 2 3 4
COM
+V
MUX
MUX
COM
DATA
IN
DATA
OUT
N/C
N/C
POWER INPUTS:
MUX LINK 2 (+V): 12 (3000 SERIES)
MUX LINK 2 (+V): 24 (4000 SERIES)
DIP Switches
MUX Link to
GRAFIK Eye
Control Units
and
Wallstations
6”
(127mm)
TX Data LED
(LED 3)
RS232 Link
(to PC or A/V
Equipment
Class 2 (PELV)
Wiring
7 3/4”
(197mm)
2 1/2”
(84mm)
Ground Screw
• Mount on a 4" (10.2mm) square junction box.
• May also mount directly to the wall.
• Ensure that the metal casing is properly grounded.
Connect a ground wire to the ground screw.
GRX-PRG
4”x4”
Junction
Box
Insert Wires
Through
Punch-Outs
Wall
GRX-PRG
Wall
Mounting
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-prg-5 2.19.04
Control Interfaces
GRX-PRG
®
• Make daisy-chain connections to the low-voltage Class 2 (PELV) MUX Link
terminals on the front of GRX-PRG Interface.
• Do not use T-taps. Run all wires in and out of terminal block.
• Each terminal accepts up to two #18 AWG (1.0mm
2
) wires.
• LED 1 lights when the Class 2 (PELV) MUX link is installed correctly.
RS232 Link Wiring
• Use cable provided.
• Standard 9-pin serial connector plugs into RS232 equipment,
other end connects to RS232 Link terminals.
• Must be 50 feet (15m) or less.
RS232 Signals
Low-Voltage Class 2 (PELV) Wiring
GRX-PRG RS232
Link Terminal
1
2
3
4
5
Signal
Common
Data In
Data Out
No Connect
No Connect
Typical PC or
A/V Equipment
Com
TxD
RxD
Pin on 9-pin Cable
5
3
2
NEUTRAL
SSA
ZONE 3
ZONE 2
ZONE 1
HOT/LIVE
CU WIRE ONLY
1 2 3 4
RS232 Link
1 2 3 4 5
MUX Link
To additional Wallstations/Control Interfaces
(16 Maximum; three from one Control Unit
without external 12VDC power supply)
50 ft. (15m)
Maximum
GRX-RS232 Wiring Terminals
COM
TxD
RxD
PC or AV
Equipment
Rear View of GRAFIK Eye Control Unit
(GRX-3103 shown)
Lutron Cable
GRX-CBL-346S
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grx-prg-6 2.19.04
Control Interfaces
GRX-PRG
®
When used with GRX-3000 Control Units
• Two #18 AWG (1.0mm
2
) conductors for common (terminal 1) and 12VDC (terminal 2).
Ensure that the terminal 2 connection is wired correctly. Refer to GRX-3000
Specification Submittal for more details.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link (terminals 3 and 4).
When used with GRX-4000 Control Units
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1) and 24VDC (terminal 2).
These will not fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground (Earth) or
Wallstation/Control Interfaces. Connect the bare drain wires and cut off the
outside shield.
Class 2 (PELV) Terminal Connections
MUX LINK
1 2 3 4
1 2 3 4 5 6 7 8
LED1 LED2
1 2345
TO PC OR A/V
EQUIPMENT
TO GRAFIK
EYE
MUX LINK RS232 LINK
1 2 3 4 5
1 2 3 4
COM
+V
MUX
MUX
COM
DATA
IN
DATA
OUT
N/C
N/C
POWER INPUTS:
MUX LINK 2 (+V): 12 (3000 SERIES)
MUX LINK 2 (+V): 24 (4000 SERIES)
Data Link - (1) twisted,
shielded pair #18 AWG
(1.0mm
2
)
3: MUX
4: MUX
Class 2/PELV
Control wiring
1: Common
2: 24VDC
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(1) #18 AWG
(1.0mm
2
)
GRX-PRG
6