GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 1 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for
up to 144 load circuits and control any light source,
including full-conduction, non-dimming.
Models available with:
• 120 V~ and 277 V~ input power.
3 to 144 circuits.
Different feed types and breakers.
GP Dimming Panels work with:
• GRAFIK Eye
® 4000 Control Units.
• GRAFIK 5000
TM, GRAFIK 6000®, GRAFIK 7000TM
Systems and Quantum® Systems.
LP Dimming Panels.
• XP Softswitch
® Panels.
DMX512 dimming systems via the 2LINK
TM option.
GP Dimming Panels: 120/277 V~
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP36
Large-Size
Panels
GP48-144
Large-Size
Panels
1
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 2 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for up to
24 load circuits and control any light source, including
full-conduction, non-dimming.
Models available with:
• 230 V~ input power.
3 to 24 circuits.
Different feed types and breakers.
GP Dimming Panels work with:
• GRAFIK Eye
® 4000 Control Units.
• GRAFIK 5000
TM, GRAFIK 6000®, GRAFIK 7000TM Systems
and Quantum® Systems.
LP Dimming Panels.
• XP Softswitch
® Panels.
DMX512 dimming systems via the 2LINK
TM option.
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP Dimming Panels: 230 V~ (CE)
2
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 3 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for up to
24 load circuits and control any light source, including
full-conduction, non-dimming.
Models available with:
220 – 240 V~ input power.
3 to 24 circuits.
Different feed types and breakers.
GP Dimming Panels work with:
• GRAFIK Eye
® 4000 Control Units.
• GRAFIK 5000
TM, GRAFIK 6000®, GRAFIK 7000TM Systems
and Quantum® Systems.
LP Dimming Panels.
• XP Softswitch
® Panels.
DMX512 dimming systems via the 2LINK
TM option.
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP Dimming Panels: 220240 V~ (non-CE)
3
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 4 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standards
ULR Listed (Reference: UL File E42071).
Complies with CSA or NOM (where appropriate).
California Energy Commission Listed
Seismic Certified (Test Method AC156. Reference
OSHPD Preapproval OSP-0215-10).
Power
Input power: 120 V~ and 277 V~, 50/60 Hz, phase-
to-neutral.
Branch Circuit Capacity:
– 120 V~ (up to 2000 W / VA)
– 277 V~ (4500 W / VA)
Minimum load: 25 W
Number of Circuits: 3 144
Branch Circuit Breakers: ULR rated thermal magnetic.
AIC ratings (other ratings available):
– 120 V~ (10,000 A)
– 277 V~ (14,000 A)
Lightning strike protection: Meets ANSI / IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operates these sources with a smooth continuous
Square Law dimming curve or on a full-conduction,
non-dimming basis:
• Incandescent (Tungsten)/Halogen
Magnetic Low-Voltage Transformer
LED drivers specified by the manufacturer to work
with forward-phase dimming controls. *
Electronic low-voltage transformers specified by the
manufacturer to work with forward-phase dimming
controls.
• Lutron
® Electronic Fluorescent Dimming Ballasts
Magnetic Fluorescent Lamp Ballasts
Optional modules allow for control of 0 10 V-, DSI,
and PWM load types.
Operates HID sources on a full-conduction,
non-dimming basis.
Wiring
Internal: Pre-wired by Lutron.
System communications: Low-voltage IEC PELV/NEC
®
Class 2 wiring connects dimming panels to other
components.
Line (mains) voltage: Feed, load, and control circuit
wiring only; no other wiring or assembly required.
Filter Chokes
Load current rise time is measured at a 90-degree
conduction angle.
10 90% of load-current waveform:
350 μSec rise time at 50% dimmer capacity.
400 μSec rise time at 100% dimmer capacity.
0 100% of load-current waveform:
525 μSec rise time at 50% dimmer capacity.
600 μSec rise time at 100% dimmer capacity.
At no point in the waveform can the rate of current
change exceed 300 mA per μSec.
Consult Lutron for higher rise time options.
Dimming Cards
Panel current ratings are listed for continuous
operation; UL® listed specifically for each light source.
• RTISS
® filter circuit technology compensates for
incoming line voltage variations; no visible flicker with
+ / 2% change in RMS voltage/cycle and + / 2%Hz
change in frequency/second.
Arcless relay air-gap OFF switches (one per load
circuit) ensure open load circuits when OFF function
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
Enclosure: NEMA-Type 1 (Type 2 available on request);
IP-20 protection; 16 U.S. Gauge Steel; indoor use only.
Weight: 30 to 1300 lb (14 to 590 kg).
Mounting: Surface-mount only. Allow space for
ventilating.
Seismic Certification Limits: SDS = 2.5g, z/h = 1.0,
IP = 1.5 for wall or wall/floor mounted panels.
SDS = 1.5g for floor-mount panels only. Contact
Lutron for details.
Environment / Heat Dissipation
Patented, ribbed aluminum heat sink base cools panel
by convection; no fans.
32 °F 104 °F (0 °C 40 °C); relative humidity less than
90%, non-condensing.
Specifications: 120/277 V~
continued on next page
* Lutron cannot guarantee compatibility with untested LED drivers. Refer to the LED Product Selection tool at www.lutron.com/ledtool for a list of
compatible products.
4
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 5 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Short Circuit Current Ratings (other ratings available)
Panel Type Voltage Std. Min. SCCR Rating
GP Main Lug (standard- and large-size) 120 V~; 277 V~ 25,000 A
GP Main Breaker (standard-size)
120 V~ 10,000 A
277 V~ 18,000 A
GP Main Breaker (large-size)
120 V~ 25,000 A
277 V~ 25,000 A
GP Mini-Size
120 V~ 10,000 A
277 V~ 14,000 A
GP Mini-Size (feed-through)
120 V~ 10,000 A
277 V~ 14,000 A
Specifications: 120/277 V~ (continued)
5
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 6 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring
Internal: Pre-wired by Lutron.
System communications: Low-voltage IEC PELV/NEC
®
Class 2 wiring connects dimming panels to other
components.
Line (mains) voltage: Feed, load, and control circuit
wiring only; no other wiring or assembly required.
Filter Chokes
Load current rise time is measured at a 90-degree
conduction angle, with 120 V~ input power.
10-90% of load current waveform:
350 μSec rise time at 50% dimmer capacity.
400 μSec rise time at 100% dimmer capacity.
0 100% of load current waveform:
525 μSec rise time at 50% dimmer capacity.
600 μSec rise time at 100% dimmer capacity.
At no point in the waveform can the rate of current
change exceed 300 mA per μSec.
Consult Lutron for higher rise time options.
Dimming Cards
Panel current ratings are listed for continuous
operation.
• RTISS
® filter circuit technology compensates for
incoming line voltage variations; no visible flicker with
+ / 2% change in RMS voltage/cycle and + / 2% Hz
change in frequency/second.
Arcless relay air-gap OFF switches (one per load
circuit) ensure open load circuits when OFF function
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
Enclosure: NEMA-Type 1 (Type2 available on request),
IP-20 protection; 16 U.S. Gauge Steel; indoor use only.
Weight: 30 to 175 lb (14 to 80 kg).
Mounting: Surface-mount only; allow space for
ventilating.
Environment/Heat Dissipation
Patented, ribbed aluminum heat sink base cools panel
by convection; no fans.
32 °F 104 °F (0 °C 40 °C); relative humidity less than
90%, non-condensing.
Standards
Complies with CE.
Power
Input power: 230 V~ 50/60 Hz, phase-to-neutral.
Branch Circuit Capacity: 10 A
Minimum load: 25 W
Number of Circuits: 3 24
Branch Circuit Breakers: IEC-rated thermal magnetic.
AIC rating (other ratings available): 6000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operates these sources with a smooth continuous
Square Law dimming curve or on a full conduction,
non-dimming basis:
• Incandescent (Tungsten)/Halogen
Magnetic Low-Voltage Transformer
LED drivers specified by the manufacturer to work
with forward-phase dimming controls. *
Electronic low-voltage transformers specified by the
manufacturer to work with forward-phase dimming
controls.
• Lutron
® Electronic Fluorescent Dimming Ballasts
Magnetic Fluorescent Lamp Ballasts
Optional modules allow for control of 0 10 V-, DSI,
and PWM load types.
Operates HID sources on a full-conduction,
non-dimming basis.
Specifications: 230 V~ (CE)
* Lutron cannot guarantee compatibility with untested LED drivers. Refer to the LED Product Selection tool at www.lutron.com/ledtool for a list of
compatible products.
6
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 7 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring
Internal: Prewired by Lutron.
System communications: Low-voltage IEC PELV/NEC
®
Class 2 wiring connects dimming panels to other
components.
Line (mains) voltage: Feed, load, and control circuit
wiring only; no other wiring or assembly required.
Filter Chokes
Load current rise time is measured at a 90-degree
conduction angle, with 120 V~ input power.
10 90% of load current waveform:
350 μSec rise time at 50% dimmer capacity.
400 μSec rise time at 100% dimmer capacity.
0 100% of load current waveform:
525 μSec rise time at 50% dimmer capacity.
600 μSec rise time at 100% dimmer capacity.
At no point in the waveform can the rate of current
change exceed 300 mA per μSec.
Consult Lutron for higher rise time options.
Dimming Cards
Panel current ratings are listed for continuous
operation.
• RTISS
® filter circuit technology compensates for
incoming line voltage variations: No visible flicker with
+ / 2% change in RMS voltage/cycle and + / 2% Hz
change in frequency/second.
Arcless relay air-gap OFF switches (one per load
circuit) ensure open load circuits when OFF function
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
Enclosure: NEMA-Type 1 (Type2 available on request),
IP-20 protection; 16 U.S. Gauge Steel; indoor use only.
Weight: 30 to 175 lb (14 to 80 kg).
Mounting: Surface-mount only; allow space for
ventilating.
Environment/Heat Dissipation
Patented, ribbed aluminum heat sink base cools panel
by convection; no fans.
32 °F 104 °F (0 °C 40 °C); relative humidity less than
90%, non-condensing.
Power
Input power: 220 240 V~ 50/60 Hz,
phase-to-neutral.
Branch Circuit Capacity: 16 A or 10 A
Minimum load: 25 W
Number of Circuits: 3 24
Branch Circuit Breakers: IEC-rated thermal magnetic.
AIC rating (other ratings available): 6000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operates these sources with a smooth continuous
Square Law dimming curve or on a full-conduction,
non-dimming basis:
• Incandescent (Tungsten)/Halogen
Magnetic Low-Voltage Transformer
LED drivers specified by the manufacturer to work
with forward-phase dimming controls. *
Electronic low-voltage transformers specified by the
manufacturer to work with forward-phase dimming
controls.
• Lutron
® Electronic Fluorescent Dimming Ballasts
Magnetic Fluorescent Lamp Ballasts
Optional modules allow for control of 0 10 V-, DSI,
and PWM load types.
Operates HID sources on a full-conduction,
non-dimming basis.
Specifications: 220 – 240 V~ (non-CE)
* Lutron cannot guarantee compatibility with untested LED drivers. Refer to the LED Product Selection tool at www.lutron.com/ledtool for a list of
compatible products.
7
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 8 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
GP: GP Dimming Panel
Number of Load Circuits
Indicates number of load circuits in the panel
Voltage
120: 120 V~
277: 277 V~
Feed Type
2: 1-phase, 2-wire
3: 1-phase, 3-wire (split phase)
4: 3-phase, 4-wire
Panel Feed
ML: Main Lugs only
Mxx: Main Breaker with xx = breaker size in Amps
Branch Circuit Breakers
20: 20 A branch circuit breakers
15: 15 A branch circuit breakers
Custom Panel Suffix
Indicates panel with special options
How to Build a GP Model Number: 120/277 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 1 2 – 1 2 0 4 M L – 2 0 – C G P – X X X
8
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 9 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
GP: GP Dimming Panel
Number of Load Circuits
Indicates number of load circuits in the panel
Voltage
230: CE
Feed Type
2: 1-phase, 2-wire
4: 3-phase, 4-wire
Panel Feed
IS: Isolator Switch
Branch Circuit Breakers
10: 10 A branch circuit breakers
Region Suffix
CE: 230 V~
Custom Panel Suffix
Indicates panel with special options
How to Build a GP Model Number: 230 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 1 2 – 2 3 0 4 I S – 1 0 C E – C G P – X X X
Region
Suffix
9
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 10 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
GP: GP Dimming Panel
Number of Load Circuits
Indicates number of load circuits in the panel
Voltage
240: 220 – 240 V~
Feed Type
2: 1-phase, 2-wire
4: 3-phase, 4-wire
Panel Feed
IS: Isolator Switch
Branch Circuit Breakers
16: 16 A branch circuit breakers
10: 10 A branch circuit breakers
Region Suffix
AU: 220 – 240 V~
Custom Panel Suffix
Indicates panel with special options
How to Build a GP Model Number: 220 240 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 1 2 – 2 4 0 4 I S – 1 6 A U – C G P – X X X
Region
Suffix
10
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 11 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~
GP3/4 Mini-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP3
1-phase, 2-wire
40 A 15 A 1500 W / VA
40 A 20 A 2000 W / VA
1-phase, 3-wire
30 A 15 A 1500 W / VA
40 A 20 A 2000 W / VA
3-phase, 4-wire
15 A 15 A 1500 W / VA
20 A 20 A 2000 W / VA
GP4 Feed-through
20 A 15 A
4
1500 W / VA
20 A 20 A
4
2000 W / VA
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP3
1-phase, 2-wire 40 A 20 A 4500 W / VA
3-phase, 4-wire 20 A 20 A 4500 W / VA
GP4 Feed-through 20 A 20 A
4
4500 W / VA
1
Only standard panels listed. Consult Lutron for further options.
2
20/16 A, 15/12 A continuous load rating.
3
Measured current will not exceed continuous load rating due to voltage drop in the dimmer.
4
Breakers located in distribution panel supplied by others.
continued on next page
11
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 12 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~ (continued)
GP8 – 24 Standard-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP8
1-phase, 2-wire Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
1-phase, 3-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
60 A Main Breaker 60 A 15 A 1500 W / VA
80 A Main Breaker 80 A 20 A 2000 W / VA
3-phase, 4-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
50 A Main Breaker 50 A 15 A 1500 W / VA
60 A Main Breaker 60 A 20 A 2000 W / VA
GP12
1-phase, 3-wire Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
3-phase, 4-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
60 A Main Breaker 60 A 15 A 1500 W / VA
80 A Main Breaker 80 A 20 A 2000 W / VA
GP16
1-phase, 3-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
125 A Main Breaker 125 A 15 A 1500 W / VA
175 A Main Breaker 175 A 20 A 2000 W / VA
3-phase, 4-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
100 A Main Breaker 100 A 15 A 1500 W / VA
125 A Main Breaker 125 A 20 A 2000 W / VA
GP20 3-phase, 3-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
110 A Main Breaker 110 A 15 A 1500 W / VA
150 A Main Breaker 150 A 20 A 2000 W / VA
GP24 3-phase, 4-wire
Main Lugs Only
175 A 15 A 1500 W / VA
175 A 20 A 2000 W / VA
125 A Main Breaker 125 A 15 A 1500 W / VA
175 A Main Breaker 175 A 20 A 2000 W / VA
1
Only standard panels listed. Consult Lutron for further options.
2
20/16 A, 15/12 A continuous load rating.
3
Measured current will not exceed continuous load rating due to voltage drop in the dimmer.
continued on next page
12
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 13 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~ (continued)
GP8 – 24 Standard-Size Models
1
(continued)
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
Maximum Dimmed
Hot Load
2
GP8
1-phase, 2-wire Main Lugs Only 175 A 20 A 4500 W / VA
3-phase, 4-wire
Main Lugs Only 175 A 20 A 2000 W / VA
60 A Main Breaker 60 A 20 A 2000 W / VA
GP12 3-phase, 4-wire
Main Lugs Only 175 A 20 A 2000 W / VA
80 A Main Breaker 80 A 20 A 2000 W / VA
GP16 3-phase, 4-wire
Main Lugs Only 175 A 20 A 2000 W / VA
125 A Main Breaker 125 A 20 A 2000 W / VA
1
Only standard panels listed. Consult Lutron for further options.
2
Measured current will not exceed continuous load rating due to voltage drop in the dimmer.
continued on next page
13
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 14 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~ (continued)
GP36 – 144 Large-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP36 3-phase, 4-wire
Main Lugs Only
750 A 15 A 1500 W / VA
750 A 20 A 2000 W / VA
200 A Main Breaker 200 A 15 A 1500 W / VA
250 A Main Breaker 250 A 20 A 2000 W / VA
GP48 3-phase, 4-wire
Main Lugs Only
750 A 15 A 1500 W / VA
750 A 20 A 2000 W / VA
250 A Main Breaker 250 A 15 A 1500 W / VA
350 A Main Breaker 350 A 20 A 2000 W / VA
GP60 3-phase, 4-wire
Main Lugs Only
750 A 15 A 1500 W / VA
750 A 20 A 2000 W / VA
300 A Main Breaker 300 A 15 A 1500 W / VA
400 A Main Breaker 400 A 20 A 2000 W / VA
GP72 3-phase, 4-wire
Main Lugs Only
750 A 15 A 1500 W / VA
750 A 20 A 2000 W / VA
350 A Main Breaker 350 A 15 A 1500 W / VA
400 A Main Breaker 400 A 20 A 2000 W / VA
GP96-144 3-phase, 4-wire Main Lugs Only
750 A 15 A 1500 W / VA
750 A 20 A 2000 W / VA
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP36 3-phase, 4-wire
Main Lugs Only 750 A 20 A 4500 W / VA
250 A Main Breaker 250 A 20 A 4500 W / VA
GP48 3-phase, 4-wire
Main Lugs Only 750 A 20 A 4500 W / VA
350 A Main Breaker 350 A 20 A 4500 W / VA
GP60 3-phase, 4-wire
Main Lugs Only 750 A 20 A 4500 W / VA
400 A Main Breaker 400 A 20 A 4500 W / VA
GP72 3-phase, 4-wire
Main Lugs Only 750 A 20 A 4500 W / VA
400 A Main Breaker 400 A 20 A 4500 W / VA
GP96-144 3-phase, 4-wire Main Lugs Only 750 A 20 A 4500 W / VA
1
Only standard panels listed. Consult Lutron for further options.
2
20/16 A, 15/12 A continuous load rating.
3
Measured current will not exceed continuous load rating due to voltage drop in the dimmer.
14
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 15 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 230 V~
GP3/4 Mini-Size Models
1
230 V~ (CE) Power
Number
of Circuits
Feed Type
Maximum
Feed
Panel Feed /
Branch Circuit Breakers
GP36
1-phase, 2-wire 30 A 10 A
3-phase, 4-wire 10 A 10 A
GP48 Feed-through 10 A 10 A
2
1
Only standard panels listed. Consult Lutron for further options.
2
Breakers located in distribution panel supplied by others.
GP8 – 24 Standard-Size Models
1
230 V~ (CE) Power
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Branch Circuit Breakers
GP8
1-phase, 2-wire Isolator Switch 125 A 10 A
3-phase, 4-wire Isolator Switch 125 A 10 A
GP12 3-phase, 4-wire Isolator Switch 125 A 10 A
GP16 3-phase, 4-wire Isolator Switch 125 A 10 A
GP20 3-phase, 4-wire Isolator Switch 125 A 10 A
GP24 3-phase, 4-wire Isolator Switch 125 A 10 A
1
Only standard panels listed. Consult Lutron for further options.
15
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 16 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 220 – 240 V~
GP3/4 Mini-Size Models
1
220 – 240 V~ Power
Number
of Circuits
Feed Type
Maximum
Feed
Panel Feed /
Branch Circuit Breakers
GP3
1-phase, 2-wire
48 A 16 A
30 A 10 A
3-phase, 4-wire
16 A 16 A
10 A 10 A
GP4 Feed-through
16 A 16 A
10 A 10 A
GP8 – 24 Standard-Size Models
1
220 – 240 V~ Power
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Branch Circuit Breakers
GP8
1-phase, 2-wire Isolator Switch 125 A
16 A
10 A
3-phase, 4-wire Isolator Switch 125 A
16 A
10 A
GP12 3-phase, 4-wire Isolator Switch 125 A
16 A
10 A
GP16 3-phase, 4-wire Isolator Switch 125 A
16 A
10 A
GP20 3-phase, 4-wire Isolator Switch 125 A
16 A
10 A
GP24 3-phase, 4-wire Isolator Switch 125 A
16 A
10 A
1
Only standard panels listed. Consult Lutron for further options.
16
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 17 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP3/4 Mini-Size Panels
All dimensions shown as: in (mm)
Top V iew
11
(279)
6
1
4
(160)
3
5
8 (92)
5
1
8
(130)
1
5
8 (41)
7/8 in (22 mm) diameter
IEC PELV/NEC® Class2
wiring only.
Left-Side View
18
(457)
19
1
2
(495)
21
1
8
(537)
11
(279)
9
5
8
(244)
Front View
Keyholes accept 1/4 in
(6mm) mounting bolts,
maximum. #10 M6
recommended.
Right-Side View
2
3
4 (70)
5
1
4 (133)
1
1
8 (29)
1
3
16 (30)
Bottom View
Load circuit wiring Feed wiring
2
3
4 (70)
1
1
2 (38)
5
1
2 (140)
1
1
2 (38)
11
(279)
17
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 18 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP8 24 Standard-Size Panels
All dimensions shown as: in (mm)
Bottom View
Top V iew
28 (711)
12
(304)
4 (100)
Suggested load
wiring entries.
Suggested feed
wiring entry.
2 (50)2 (50)
13
(330)
12
(304)
Right-Side View
Removable
top cover
7/8 in (22 mm)
diameter IEC
PELV/NEC®
Class2 wiring
only.
2 (50)
Left-Side View
33
(838)
35
(889)
Front View
28 (711)
12 (304)
37
(940)
Keyholes accept 5/16 in
(8mm) mounting bolts,
maximum. 1/4 in (M8)
recommended.
18
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 19 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP36 Large-Size Panels
All dimensions shown as: in (mm)
* Available to punch for alternate feed wiring.
** Available to punch for alternate load circuit wiring.
Top V iew
26
1
8 (653)
23 (580)
14
1
8
(360)
6 (150)
5
1
2 (140)
Suggested load and
feed wiring entry.
Back View
26
1
8 (653)
25
1
16 (627)
1
7
8 (47)
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6 in (150 mm)
diameter*
3/4 in (20 mm)
diameter IEC
PELV/NEC®
Class2 wiring
only.
Left-Side View
10
1
2
(263)
14
1
8
(353)
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
4 in (100 mm)
diameter**
Bottom View
24
1
14 (633)
23
5
16 (583)
26
1
8 (653)
2
3
16 (55)2 (50)
1
7
8 (47)1
1
8 (28)
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
3 in (75 mm) square area*
8 (200)
1
5
16 (33)
11
(275)
11
15
16
(298)
14
1
8
(353)
19
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 20 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP48/60/72 Large-Size Panels
All dimensions shown as: in (mm)
* Available to punch for alternate feed wiring.
** Available to punch for alternate load circuit wiring.
52
5
16 (1308)
23 (580) 23 (580)
14
1
8
(360)
6 (150)
5
1
2 (140)
Top V iew
Suggested load and
feed wiring entry.
51
1
8 (1278)
27
1
4 (681)
25
1
16 (627) 1
7
8 (48)
50 (1250)
Back View
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6 in (150 mm)
diameter*
3/4 in (20 mm)
diameter IEC
PELV/NEC®
Class2 wiring
only.
10
1
2
(263)
14
1
8
(353)
Left-Side View
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
4 in (100 mm)
diameter**
Bottom View
50
7
16 (1261)
49
7
16 (1236)
24
5
16 (633)
28
15
16 (723)
23
5
16 (583)
28 (700)
2
3
16 (55)
1
7
8 (48)
8 (200)
1
5
16 (33)
11
(275)
11
15
16
(298)
14
1
8
(353)
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
3 in (75 mm) square area*
20
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 21 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP96 144 Large-Size Panels (two units installed back-to-back)
All dimensions shown as: in (mm)
* Available to punch for alternate feed wiring.
** Available to punch for alternate load circuit wiring.
52
5
16 (1308)
23 (580) 23 (580)
28
1
4
(720)
14
1
8
(360)
6 (150)
5
1
2 (140)
Top V iew
Suggested load and
feed wiring entry.
51
1
8 (1278)
27
1
4 (681)
25
1
16 (627) 1
7
8 (48)
50 (1250)
Back View of One Unit
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
10
1
2
(263)
14
1
8
(353)
Left-Side View
4 in (100 mm)
diameter**
3/4 in (20 mm)
diameter IEC
PELV/NEC®
Class2 wiring
only.
Bottom View
50
7
16 (1261)
49
7
16 (1236)
24
5
16 (633)
28
15
16 (723)
23
5
16 (583)
28 (700)
2
3
16 (55)
1
7
8 (47)
3 in (75 mm)
square area*
8 (200)
1
5
16 (33)
11
(275)
11
5
16
(298)
14
1
8
(353)
9/16 in (14 mm) diameter
mounting hole. Use 1/2 in
(13 mm) hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6 in (150 mm)
diameter*
3/4 in (20 mm)
diameter IEC
PELV/NEC®
Class2 wiring
only.
21
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 22 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Surface mount indoors.
Panel generates heat. Mount only where ambient
temperature will be 0 40 °C (32 104 °F).
This equipment is air cooled. Do not block vents or
warranty will be void. Leave 12 in (310 mm) clearances
above, below, and in front of panel. No clearance
necessary on sides.
Reinforce wall structure for weight and local codes.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP3 / 4 685 30 lb (14 kg)
Dimming panels will hum slightly and internal relays will
click while in op er a tion. Mount where audible noise is
ac cept able.
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
GP panels must be mounted within 7° of true vertical.
For maximum feed and wire sizes, consult Wiring
Overview page.
Note: Water damages panels. Install where they will
not get wet.
Mounting: GP3/4 Mini-Size Panels
Front View
IEC PELV/NEC®
Class 2 wiring
Terminal blocks
for load circuits
Branch circuit
breakers
Feed wiring
Load circuit
wiring
Raceway
Side View
12 in (310 mm)
minimum
12 in (310 mm)
minimum
IEC PELV/NEC
®
Class 2 wiring
12 in (310 mm)
minimum
Wall
22
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 23 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Surface mount indoors.
Panel generates heat. Mount only where ambient
temperature will be 32 104 °F (0 40 °C).
This equipment is air cooled. Do not block vents or
warranty will be void. Leave 12 in (310 mm) clearances
above, below, and in front of panel. Leave clearance
on sides for IEC PELV/NEC
® Class 2 wiring.
Reinforce wall structure for weight and local codes.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP8 1365 115 lb (52 kg)
GP12 2045 130 lb (59 kg)
GP16 2725 145 lb (66 kg)
GP20 3405 160 lb (73 kg)
GP24 4085 175 lb (80 kg)
Dimming panels will hum slightly and internal relays will
click while in op er a tion. Mount where audible noise is
ac cept able.
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
GP panels must be mounted within 7° of true vertical.
For maximum feed and wire sizes, consult Wiring
Overview page.
Note: Water damages panels. Install where they will
not get wet.
Mounting: GP8 24 Standard-Size Panels
Front View
Ceiling
Raceway
Feed wiring
Load circuit
wiring
Terminal blocks
for load circuits
IEC PELV/NEC
®
Class 2 wiring
Main lugs or
main breaker
Side View
12 in (310 mm)
minimum
12 in (310 mm)
minimum
IEC PELV/NEC
®
Class 2 wiring
Air flow
12 in (310 mm)
minimum
Wall
23
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 24 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
At least 8.67 ft (2650 mm) between the floor and the
suspended ceiling is required for this layout.
Note: Water damages panels. Install where they will
not get wet.
Mounting One Panel Above Another
* 6 in (160 mm) minimum approved for this layout only.
Side View (GP8 – 24)
Suspended
ceiling depth
Mounting holes
IEC PELV/NEC
®
Class 2 wiring
Air flow
Mounting holes
Wall
Front View (GP8 – 24)
Ceiling
Raceway
Load circuit
wiring
Feed wiring
Main lugs or
main breaker
IEC PELV/NEC
®
Class 2 wiring
12in
(310mm)
minimum
8.67ft
(2650mm)
minimum
7.5ft
(2280mm)
6.5ft
(1950mm)
3 ft 4
5
8in
(1030mm)
6in (160mm)
minimum*
12in
(310mm)
minimum
24
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 25 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Surface mount indoors.
Panel generates heat. Mount only where ambient
temperature will be 32 104 °F (0 40 °C).
This equipment is air cooled. Do not block vents or
warranty will be void. Leave 12 in (310 mm) clearances
above and in front of panel. Leave clearance on sides
for IEC PELV/NEC
® Class2 wiring.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP36 4350 325 lb (147 kg)
GP48 5800 550 lb (250 kg)
GP60 7250 600 lb (273 kg)
GP72 8700 650 lb (295 kg)
Mount panel on floor and against a wall. Use 1/2 in
(13mm) mounting bolts.
Dimming panels will hum slightly and internal relays will
click while in op er a tion. Mount where audible noise is
ac cept able.
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
GP panels must be mounted within 7° of true vertical.
GP36-72 Mounting
GP36 consists of the right side module only. Mount as
shown.
Alternate Conduit Locations
Run feed wiring in from bottom.
Run load circuit wiring in from left side.
Note: Water damages panels. Install where they will
not get wet.
Mounting: GP36 72 Large-Size Panel
Side View
12 in (310 mm)
minimum
3 ft (930 mm)
minimum
IEC PELV/NEC
®
Class 2 wiring
Air flow
Wall
Front View
Ceiling
Raceway
Feed and load
circuit wiring
Main lugs or
main breaker
IEC PELV/NEC
®
Class 2 wiring
Terminal blocks
for load circuits
GP36
GP48 – 72
25
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 26 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Surface mount indoors.
Panel generates heat. Mount only where ambient
temperature will be 32 104 °F (0 40 °C).
This equipment is air cooled. Do not block vents or
warranty will be void. Leave 12 in (310 mm) clearances
above and in front of panel. Leave clearance on sides
for IEC PELV/NEC
® Class2 wiring.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP96-144 17400 1300 lb (590 kg)
Mount panel on floor and against a wall. Use 1/2 in
(13mm) mounting bolts.
Dimming panels will hum slightly and internal relays will
click while in op er a tion. Mount where audible noise is
ac cept able.
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
GP panels must be mounted within 7° of true vertical.
GP96-144 Mounting
Allow airflow and 3 ft (92 cm) clearance from fronts/
sides of panel as shown.
Note the extra IEC PELV/NEC
® Class2 wiring.
Alternate Conduit Locations
Run feed wiring in from bottom.
Run load circuit wiring in from left side.
Note: Water damages panels. Install where they will
not get wet.
Mounting: GP96 144 Large-Size Panel
Front View
Ceiling
Raceway
Feed and load
circuit wiring
Main lugs or
main breaker
IEC PELV/NEC
®
Class 2 wiring
Terminal blocks
for load circuits
Side View
12 in (310 mm)
minimum
3 ft (930 mm)
minimum
IEC PELV/NEC
®
Class 2 wiring
Air flow
Wall
26
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 27 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
120/277 V~
Power Feed: 14AWG (2.0mm
2
) to 8AWG (6.0mm
2
)
Neutral Feed: 14AWG (2.0mm
2
) to 6AWG (10.0mm
2
)
Dimmed Line/Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 6AWG (10.0mm
2
)
230 V~ (CE), 220 240 V~
Power Feed: 18AWG (1.0mm
2
) to 4AWG (25.0mm
2
)
Neutral Feed: 14AWG (2.0mm
2
) to 6AWG (10.0mm
2
)
Dimmed Line/Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 6AWG (10.0mm
2
)
Wiring Tips
Wire GP3 Mini-Size panels similarly to a lighting
distribution panel:
Run feed and load wiring; no other wiring or assembly
required.
Common neutrals are not permitted. Run separate
neutrals for each load circuit.
GP3 panels can provide temporary lighting.
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Use branch circuit breakers to switch lights on and off.
Wiring Overview: GP3 Mini-Size Panels (120/277 V~, 230 V~ [CE], 220 240 V~)
IEC PELV/NEC®
Class 2 wiring
Terminal block
Ground
Panel Feed Wiring
Power Feed
(Line/Hot)
Neutral
Feed
SH
1
H
1
DH
2
SH
2
DH
3
SH
3
DH
1
H
2
H
3
Load
Bypass jumpers
(Do not remove)
Typical Load Circuit
Dimmed
Line/Hot
Load
Neutral
120/277 V~
SL
1
L
1
DL
2
SL
2
DL
3
SL
3
DL
1
L
2
L
3
Load
Bypass jumpers
(Do not remove)
Typical Load Circuit
Dimmed
Line/Hot
Load
Neutral
230 V~ (CE),
220 – 240 V~
OR
27
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 28 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
Power Feed: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Neutral Feed: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Dimmed Line / Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Wiring Tips
Wire GP4 Mini-Size panels similarly to a lighting
distribution panel:
Run feed and load wiring; no other wiring or assembly
required.
Common neutrals are not permitted. Run separate
neutrals for each load circuit.
GP4 panels can provide temporary lighting.
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Wiring Overview: GP4 Mini-Size Panels (120/277 V~, 230 V~ [CE], 220 240 V~)
Panel Feed Wiring
Power Feed
(Line/Hot)
Neutral
Feed
IEC PELV/NEC®
Class 2 wiring
Terminal block
Ground
DH
1
SH
1
H
1
N
1
N
1
DH
2
SH
2
H
2
N
2
N
2
Load
Bypass jumpers
(Do not remove)
Typical Dimming Leg
Dimmed
Line/Hot
Load
Neutral
28
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 29 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
Power Feed Standard Main Lugs: 14AWG (2.0mm
2
) to 2/0AWG (70.0mm
2
)
Power Feed Dual-Tap Main Lugs: 6AWG (10.0mm
2
) to 4/0AWG (120mm
2
)
Neutral Feed: 6AWG (10.0mm
2
) to 350mcm (177.0mm
2
)
Dimmed Line/Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 6AWG (10.0mm
2
)
Wiring Tips
Wire GP8 – 24 Standard-Size
panels similarly to a lighting
distribution panel:
Run feed and load wiring; no other
wiring or assembly required.
Common neutrals are not permitted.
Run separate neutrals for each load
circuit.
GP8 24 panels can provide
temporary lighting.
Wire all loads.
Do not remove the bypass jumpers
that protect the dimming modules.
Use branch circuit breakers to switch
lights on and off.
Wiring Overview: GP8 24 Standard-Size Panels (120/277 V~)
Panel Feed Wiring
Power Feed
(Line/Hot)
Neutral
Feed
DH
1
SH
1
H
1
DH
1
SH
1
Typical Load Circuit
Load
Bypass jumpers
(Do not remove)
Load
Neutral
Dimmed
Line/Hot
Terminal block
Branch circuit
breakers
IEC PELV/NEC
®
Class 2 wiring
29
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 30 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
Power Feed: 14AWG (2.0mm
2
) to 2AWG (35.0mm
2
)
Neutral Feed: 14AWG (2.0mm
2
) to 2AWG (35.0mm
2
)
Dimmed Line / Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Wiring Tips
Wire GP8 – 24 Standard-Size
panels similarly to a lighting
distribution panel.
Run feed and load wiring; no other
wiring or assembly required.
Common neutrals are not
permitted. Run separate neutrals
for each load circuit.
GP8 24 panels can provide
temporary lighting.
Wire all loads.
Do not remove the bypass jumpers
that protect the dimming modules.
Use branch circuit breakers to
switch lights on and off.
Wiring Overview: GP8 24 Standard-Size Panels (230 V~ [CE], 220 240 V~)
Panel Feed Wiring
Power Feed
(Line/Hot)
Neutral
Feed
DL
1
SL
1
L
1
DL
2
SL
2
L
2
N
1
N
1
Typical Load Circuit
Load
Bypass jumpers
(Do not remove)
Dimmed
Live
Load
Neutral
Terminal block
Branch circuit
breakers
IEC PELV/NEC
®
Class 2 wiring
30
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 31 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
Panel Feed Wiring:
Main lugs only: Parallel 4AWG to 500kcmil (mcm)
200A to 400A main breakers: 1/0AWG (50mm
2
) to 600kcmil (mcm)
Dimmed Line/Hot: 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
)
Load Neutral: 14AWG (2.0mm
2
) to 6AWG (10.0 mm
2
)
Wiring Tips
Wire GP36 144 Large-Size panels similarly to a
lighting distribution panel:
Run feed and load wiring; no other wiring or assembly
required.
Common neutrals are not permitted. Run separate
neutrals for each load circuit.
GP36 144 panels can provide temporary lighting.
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Use branch circuit breakers to switch lights on and off.
Wiring Overview: GP36 144 Large-Size Panels (120/277 V~)
* Varies depending on MB or MLO. See model numbers page.
Panel Feed Wiring
Power Feed
(Line/Hot)*
Neutral
Feed*
DH SH H DH SH
Typical Load Circuit
Load
Bypass jumpers
(Do not remove)
Load
Neutral
Dimmed
Line/Hot
Branch circuit breakers
IEC PELV/NEC® Class 2 wiring
Terminal block
31
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 32 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
All load circuit wiring is 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
).
Switched Hot (SH) must be used for 3-wire controlled loads only; use the Dimmed Hot (DH) for all non-dim load
types.
• Consult Wiring Overview page for appropriate neutral location.
Load Circuits: 120/277 V~ (GP3 – 144)
Wiring for Lutron® Hi-lume® A-Series L3D drivers, and Lutron® Hi-lume® fluorescent dimming ballasts
SH
1
H
1
DH
1
N
GP Dimming Panel
Load Terminals
Lutron® 3-Wire
Ballast or LED
Driver
Load
Neutral (White)
Red
Red
Blue
Blue
Ground
Dimmed Hot (Orange)
Switched Hot (Black)
Bypass jumpers
(Do not remove)
Wiring for 2-Wire Load Types
N
SH
1
H
1
DH
1
GP Dimming Panel
Load Terminals
Load
Neutral (White)
Dimmed Hot (Orange)
Bypass jumpers
(Do not remove)
Lutron® Hi-lume® 120 V~
dimming ballast shown.
Wiring for Lutron® GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GP Dimming Panel
H
+
N
GRX-TVMTerminal Block
Load
Neutral (White)
Dimmed Live (Orange)
Bypass jumpers
(Do not remove)
32
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 33 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
All load circuit wiring is 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
).
Use the Dimmed Live (DL) for all non-dim load types.
• Consult Wiring Overview page for appropriate neutral location.
Load Circuits: 230 V~ (CE) (GP3 – 24)
Wiring for Lutron® GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GP Dimming Panel
H
+
N
GRX-TVMTerminal Block
Load
Neutral (White)
Dimmed Live (Orange)
Bypass jumpers
(Do not remove)
Wiring for 2-Wire Load Types
SL
1
L
1
N
1
DL
1
GP Dimming Panel
Load Terminals
Load
Neutral (White)
Dimmed Live (Orange)
Bypass jumpers
(Do not remove)
33
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 34 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
All load circuit wiring is 14AWG (2.0mm
2
) to 10AWG (4.0mm
2
).
Switched Live (SL) must be used for Hi-lume
® FDB or Eco-10® loads only; use the Dimmed Live (DL) for all
non-dim load types.
• Consult Wiring Overview page for appropriate neutral location.
Load Circuits: 220 240 V~ (GP3 – 24)
Wiring for Lutron® Hi-lume® or Eco-10® (ECO-Series) Fluorescent Dimming Ballasts
SL
1
L
1
N
1
DL
1
GP Dimming Panel
Load Terminals
Lutron® 3-Wire
Ballast or LED
Driver
Load
Neutral (White)
Red
Red
Blue
Blue
Ground
Dimmed Live (Orange)
Switched Live (Black)
Bypass jumpers
(Do not remove)
Wiring for 2-Wire Load Types
SL
1
L
1
N
1
DL
1
GP Dimming Panel
Load Terminals
Load
Neutral (White)
Dimmed Live (Orange)
Bypass jumpers
(Do not remove)
Lutron® Hi-lume®
220–240 V~ dimming
ballast shown.
Wiring for Lutron® GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GP Dimming Panel
H
+
N
GRX-TVMTerminal Block
Load
Neutral (White)
Dimmed Live (Orange)
Bypass jumpers
(Do not remove)
34
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 35 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Low-Voltage IEC PELV/NEC® Class 2 Wiring (All Models)
System communications uses low-voltage IEC PELV/NEC® Class 2 wiring.
Wiring must be daisy-chained.
Wiring must run separately from line (mains) voltage.
GRAFIK Eye® 4000 System
• IEC PELV/NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
Approved low-voltage cable is available from Lutron
1
and Belden. These are approved with 22 AWG (0.5 mm
2
)
data link wires.
Quantum® System
• IEC PELV/NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.5 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
If MUX-RPTR interface
2
and GRX-CBL-46L cable
1
is used, length may be up to 4000 ft (1219 m).
Maximum of 32 circuit selectors per link or 512 switch legs (controllable outputs) per link.
It is not necessary to position the Quantum
® panel at the end of the link; it may be in the middle.
1
GRX-CBL-46L IEC PELV/NEC® Class 2 wiring cable is available from Lutron and contains:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.5 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line.
2
Only the MUX-RPTR interface can only be used to extend the length of a power panel link in Quantum. To extend a QS wallstation link, a QSPS-P1-10-60
must be used.
3
Link terminators (LT-1) are required at the beginning and END of every power panel link.
Dimming Panel
Control Unit
Control Interface
Wallstations
Dimming Panel
Quantum®
Processor
Refer to Quantum
® Specification
Control Unit
Control Interface
Wallstations
Power Panel Link
3
35
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 36 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergency power: The additional 18 AWG (1.0mm
2
) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency (essential)
lighting panel to “sense” when normal (non-essential) power is lost. If more than one emergency lighting panel needs to sense from a specific normal
panel, a dedicated wire between each pair of normal (non-essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit board of circuit selector. Connect the bare drain wires and cut off
the outside shield.
IEC PELV/NEC® Class 2 Terminal
Connections: GRAFIK SystemsTM
Each Low-Voltage IEC PELV/NEC® Class 2 terminal can
accept only two 18 AWG (1.0 mm
2
) wires. Two12AWG
(2.5 mm
2
) conductors will not fit. Connect as shown,
using appropriate wire connectors.
IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: GRAFIK SystemsTM (All Models)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
Control Wiring
(2) 12 AWG (2.5 mm
2
)
1: Common
2: 24 VFW
To
additional
power
panels
Dimming Panel 1 Dimming Panel 2
To lighting
controls or
processors
Shield/Drain
Shield/Drain
(1) 18 AWG (1.0 mm
2
)
5: Sense Line*
Data Link
(1) shielded, twisted pair 22 AWG (0.5 mm
2
)
3: MUX
4: MUX
1
2
3, 4
5
1
2
3, 4
Data A OK
Power
1234 5D
m
mon
FW
n
se
Data B OK
m
n
(4) 12 AWG (2.5 mm
2
)
36
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 37 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergency power: The additional 18 AWG (1.0mm
2
) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency (essential)
lighting panel to “sense” when normal (non-essential) power is lost. If more than one emergency lighting panel needs to sense from a specific normal
panel, a dedicated wire between each pair of normal (non-essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit board of circuit selector. Connect the bare drain wires and cut off
the outside shield.
** 24 V-: Only connect Pin 2 (24 V-) between power panels and LUT-ELI-3PH units. Pin 2 should not be connected to the Quantum
® processor on the link.
IEC PELV/NEC® Class 2 Terminal
Connections: Quantum®
Each Low-Voltage IEC PELV/NEC® Class 2 terminal can
accept only two 18 AWG (1.0 mm
2
) wires or one12AWG
to 22 AWG (2.5 mm
2
to 0.5 mm
2
) wire. Connect as
shown, using appropriate wire connectors.
IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: Quantum®
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
Control Wiring
(2) 12 AWG (2.5 mm
2
)
1: Common
2: 24 VFW
To
additional
power
panels
Dimming Panel 1 Dimming Panel 2
To lighting
controls or
processors
Shield/Drain
Shield/Drain
(1) 18 AWG (1.0 mm
2
)
5: Sense Line *
Data Link
(1) shielded, twisted pair 22 AWG (0.5 mm
2
)
3: MUX
4: MUX
1
2 **
3, 4
5
1
2
3, 4
Data A OK
Power
1234 5D
m
mon
FW
n
se
Data B OK
m
n
(4) 12 AWG (2.5 mm
2
)
37
GP Dimming PanelsGRAFIK Systems® Power Equipment
369401d 38 01.07.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Custom Options
Option Description Application
Custom Main Breaker Panel features a custom main breaker size Jobs with special load requirements.
Dual Tap Lug Set Panel accepts up to 225 A feed A single feed with multiple GP Dimming
Panels is required.
Branch Circuit
Protection
Branch Circuit Breakers with higher AIC ratings or special
breaker types such as GFI (Ground Fault Interrupt)
Lutron
® Ten-Volt
Module (TVM)
Allows panel to operate fluorescent ballasts that meet IEC 929
standards for 0 10 V- control including:
• Lutron TVE ballasts
0 – 10 V- neon
• PWM fluorescent
• Tridonic
® DSI (Digital Serial Interface).
The TVM can sink or source 50 mA (typically 25 50 ballasts)
on each circuit
Jobs with fluorescent ballasts that
require 0 – 10 V-, PWM, or DSI control
MRI Panel dims DC (Direct Current) lighting in Magnetic Resonance
Imaging (MRI) facilities.
MRI facilities or sound studios where
standard lighting-control equipment
won't work because of RFI and EMI.
Locking Cover Prevents accidental switching of circuit breakers.
Adds an additional 2.25 in (57.2 mm) to the front of the panel.
Available for GP8 GP24 only.
Service corridors and public areas.
2Link
TM Allows a DMX512 theatrical console to operate the load
circuits in the dimming panel.
Allows a GRAFIK Eye
® 4000 System to handle 128 zones
(two links of 64 zones)
Allows two GRAFIK Eye® 4000 Systems to share the same
dimming panel.
Control of architectural lighting from
DMX512 theatrical console is required.
A mix of architectural and theatrical
lighting exists on the job.
Multiple systems where space for
panels is limited.
Tridonic is a registered trademark of Zumtobel AG.
38