Infrared Receiver
Scene
Selection
Buttons
ZoneBase
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-1 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
Description
• Provides pushbutton recall of four preset
lighting scenes, plus Off.
• Allows setup of lighting scenes using buttons
on the Control Unit.
• Controls many light source types directly, and
others using power interfaces.
• Provides lockout options to prevent
accidental changes.
• Includes built-in infrared receiver for
operation with an optional remote control.
Models available to:
• Accept 120V, 220-240V (non-CE), 230V (CE)
and 100V input power.
• Control two to six zones of lighting.
GRX-3100 Control Units
Provide setup using buttons on the Control
Unit.
GRX-3500 Control Units
Provide optional setup using a PC, including
setting lighting levels in 1% increments.
GRAFIK Eye 3000 Series Control Unit
Cover (shown open)
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-4 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electrostatic discharge without damage or
memory loss.
• Compensates in real time for incoming line voltage
variations: No visible flicker with +/-2% change in
RMS voltage/cycle and +/-2% Hz change in
frequency/second.
• 10-year power failure memory automatically
restores lighting to levels prior to power interruption.
• Faceplate snaps on with no visible means of
attachment.
System Communications and Capacities
• Low-voltage type Class 2 (PELV) wiring connects
Control Units, Wallstations, and Control Interfaces:
• Up to 8 Control Units may be linked to control up
to 48 zones.
• Up to 16 total Wallstations and Control Interfaces
may be added for a total of 24 control points.
Environment
• 32-104°F (0-40°C). Relative humidity less than
90% non-condensing.
Specifications
Input Power
• 120V, 220-240V (non-CE), 230V (CE) or 100V,
50/60Hz.
• Lightning Strike Protection: Meets ANSI/IEEE
standard 62.41-1980. Can withstand voltage surges
of up to 6000V and current surges of up to 3000A.
Lighting Sources/Load Types
Controls the following lighting sources with a
smooth, continuous Square Law dimming curve or
on a full conduction non-dim basis:
• Incandescent, Tungsten, Magnetic Low Voltage
Transformer
• Lutron Tu-Wire
® Electronic Fluorescent Dimming
Ballast
• Neon and Cold Cathode
Controls the following lighting sources with a smooth
continuous Square Law dimming curve through
separate power interfaces:
• Electronic Low Voltage Transformer
• Lutron Electronic Fluorescent Dimming Ballast
Preset Control
• 4 preset lighting scenes and off are accessible from
the Control Unit front panel.
• 12 additional scenes are stored in the Control Unit.
These scenes are accessible via Wallstations and/or
Control Interfaces.
• Light levels fade smoothly between scenes. Fade
time can be set differently for each scene, between
0-59 sec. or 1-60 min. Fade time from Off is
capped at 5 sec.
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-7 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
G R X - 3 5 0 6 - T - A U - W H
Prefix
Number
of Zones
Input
Voltage
Set-Up
Method
Cover
Option
Color
Option
Color Options
Architectural Matte Finishes
Standard – Ship in 48 hours
Cover Option: A or T
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Designer Gloss Finishes
Ship in 4 to 6 weeks
Cover Option: A only
White GWH
Light Almond GLA
Almond GAL
Ivory GIV
Satin Color Matte Finishes
Cover Option: A or T
Hot HT
Ochre OC
Terracotta TC
Desert Stone DS
Stone ST
Limestone LS
Blue Mist BT
Midnight MN
Taupe TP
Biscuit BI
Eggshell ES
Snow SW
Architectural Metal Finishes
Cover Option: T only
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Bright Nickel BN
Anodized Aluminum Finishes
Cover Option: T only
Clear CLA
Black BLA
Brass BRA
Bronze BZA
Prefix:
GRX for Grafik Eye 3000 Series
Control Units
Set-Up Method:
1 for standard via front panel
5 for PC setup
Number of Zones:
2, 3, 4, or 6
Cover Option:
A for Opaque
T for Translucent Black
Input Voltage
__ (no code) for 120V Single Feed
AU for 220-240V (non-CE)
CE for 230V (CE)
JA for 100V
Color Option:
See Color Options list
Cover Options
Opaque A
Cover and Base will match.
Translucent Black T
Black Cover and choice of
base color.
Also available:
- Custom controls
- Color matching
- Engraving
These options ship in 4 to 6
weeks
How to Build a Model Number
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-9 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
Model Numbers
120V Input Power
100V Input Power
230V (CE) Input Power
220–240V (non-CE) Input Power
Number
of Zones
2
3
4
6
Standard Setup
GRX-3102-_-__
GRX-3103-_-__
GRX-3104-_-__
GRX-3106-_-__
PC Setup
GRX-3502-_-__
GRX-3503-_-__
GRX-3504-_-__
GRX-3506-_-__
Unit Capacity
(Watts/VA)
1200
1500
2000
2000
Zone Capacity
(Watts/VA)
800
800
800
800
Number
of Zones
2
3
4
6
Standard Setup
GRX-3102-_-AU-__
GRX-3103-_-AU-__
GRX-3104-_-AU-__
GRX-3106-_-AU-__
PC Setup
GRX-3502-_-AU-__
GRX-3503-_-AU-__
GRX-3504-_-AU-__
GRX-3506-_-AU-__
Unit Capacity
(Watts/VA)
1600
2400
3000
3000
Zone Capacity
(Watts/VA)
1200
1200
1200
1200
Number
of Zones
2
3
4
6
Standard Setup
GRX-3102-_-CE-__
GRX-3103-_-CE-__
GRX-3104-_-CE-__
GRX-3106-_-CE-__
PC Setup
GRX-3502-_-CE-__
GRX-3503-_-CE-__
GRX-3504-_-CE-__
GRX-3506-_-CE-__
Unit Capacity
(Watts/VA)
1600
2300
2300
2300
Zone Capacity
(Watts/VA)
800
800
800
800
Number
of Zones
2
3
4
6
Standard Setup
GRX-3102-_-JA-__
GRX-3103-_-JA-__
GRX-3104-_-JA-__
GRX-3106-_-JA-__
PC Setup
GRX-3502-_-JA-__
GRX-3503-_-JA-__
GRX-3504-_-JA-__
GRX-3506-_-JA-__
Unit Capacity
(Watts/VA)
1000
1250
1600
1600
Zone Capacity
(Watts/VA)
600
600
600
600
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-11 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
B
3 5/16"
(85mm)
3 1/2" (89mm) wallbox
depth recommended
C
A
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 4 ZONE 1 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 4ZONE 1 ZONE 6ZONE 5
1
Can be ordered from Lutron.
Dimensions and Mounting - All Voltages Except 230V (CE)
5/16"
(8 mm)
1 15/16"
(49 mm)
4 9/16"
(116 mm)
Model
2-Zone:
GRX-3102
GRX-3502
3-Zone:
GRX-3103
GRX-3503
4-Zone:
GRX-3104
GRX-3504
6-Zone:
GRX-3106
GRX-3506
Side View
A
4 5/16"
(123mm)
6 11/16”
(168mm)
8 5/16”
(208mm)
8 5/16”
(208mm)
B
1 13/16”
(46mm)
3 5/8”
(92mm)
5 7/16”
(138mm)
5 7/16”
(138mm)
C
5.56”
(141mm)
7.25”
(184mm)
8.94”
(227mm)
8.94”
(227)
Wallbox
1
U.S. Size
2 Gang
3 Gang
4 Gang
4 Gang
Depth
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-13 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
• Pull power wiring from distribution panel and to light fixtures.
• Each line voltage terminal can accept up to two #12 AWG (2.5mm
2
) wires.
Consult Lutron for:
• Non-dim relay wiring.
• Load side emergency transfer wiring.
ZONE 6
ZONE 4
HOT/LIVE
SSA
CU WIRE ONLY
ZONE 2
ZONE 3
ZONE 5
NEUTRAL
ZONE 1
CLASS 2
1 2 3 4
USA
Class 2
IEC
PELV
• System communications use low-voltage Class 2 (PELV) wiring.
• Wiring must be daisy-chained.
• Wiring must run separately from line (mains) voltage.
External 12VDC Power Supply is
required to power more than three
Wallstations and/or Control Interfaces
from a single Control Unit.
Distribution Panel
Control Unit
Control Interface
Wallstations
Power
Supply
Earth/Ground from Distribution Panel
Rear View of GRX-3106 Control Unit
Hot/Live
Hot/Live
Load 1
Load 3
Load 5
Load 2
Load 4
Load 6
(2) #12 AWG
(2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
Neutral
Neutral
Line Voltage Wiring - 120V, 100V, 220-240V Models
Low-Voltage Class 2 (PELV) Wiring
Class 2 (PELV) wiring link requires:
Two #12 AWG (2.5mm
2
) conductors for control power.
One twisted, shielded pair of #18 AWG (0.625mm
2
) for data link.
Total length of Control Link may be up to 2,000 ft. (610m).
Approved low-voltage cable is available from Lutron
1
, Belden, and Liberty.
These are approved with #22 AWG data link wires.
GRX-CBL-346S Class 2 (PELV) wiring cable is available from Lutron and contains:
Two #12 AWG (2.5mm
2
) conductors for control power.
One twisted, shielded pair of #22 AWG (0.625mm
2)
for data link.
1
6
A1
1
2
3
4
5
6
7
A3
A2
A4
4
3
2
1
4
3
2
1
1234
4321
1234
4321
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-17 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
• Each Class 2 (PELV) terminal accepts up to two #18 AWG
(1.0mm
2
) wires.
• Daisy chain the terminal 1, 3, and 4 connections to all
Control Units, Wallstations, and Control Interfaces.
• Each Control Unit has its own power supply. Terminate the
terminal 2 connection (12VDC power) so that each Control
Unit supplies power to a maximum of three Wallstations.
Each Wallstation should receive power from only one
Control Unit.
• Total length of Class 2 (PELV) wiring may be up to 2,000 ft.
(600m).
• Make all connections in the Control Unit’s wallbox. Remote
connections (T-taps) must be in a switchbox or junction box
with a maximum wire length of 8 ft. (2.5m) from the link to
the connected unit.
• Do not allow Class 2 (PELV) wires to contact line/main wires.
Class 2 (PELV) Terminal Connections
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
A3 powers Wallstations
2, 3, and 4 – No terminal
No. 2 connection
between Wallstations
4 and 5
A1 powers 1 only –
terminal No. 2 connection
terminates at Wallstation 1
A2 and A3
have their own
power supplies –
no terminal No. 2
connection
Lutron Cable,
GRX-CBL-346S
Note:
Up to 8 GRAFIK Eye 3000 Series Control Units and 16 Wallstations/Control Interfaces
may be daisy-chained together in one system.
Class 2/PELV cable is available from Lutron - order GRX-CBL-346S.
A4 powers Wallstations
5, 6, and 7 – no terminal
No. 2 connection between
Wallstations 4 and 5
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
7
123456 123456123456123456
CLASS 2
1 2 3 4
USA
Class 2
IEC
PELV
ZONE 2
ZONE 4
ZONE 6
SSA
HOT/LIVE
NEUTRAL
ZONE 1
ZONE 3
ZONE 5
CU WIRE ONLY
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3000-18 06.11.04
Preset Dimming Controls
GRAFIK Eye 3000 Series
®
Rear View of GRAFIK Eye Control Unit
(GRX-3106 shown)
Lutron cable
GRX-CBL-346S
2 twisted pair
#18 AWG (1.0mm
2
)
(+) 12VDC
Wallstation
Wallstations/Control Interfaces
(16 Maximum)
Wallstation
Wallstation
Wallstation
1 #18 AWG
(1.0mm
2
)
Common
1 twisted pair
#18 AWG (1.0mm
2
)
To Power
Source
GRX-12VDC
Note:
Do not connect terminal No. 2 between GRAFIK Eye 3000
Series Control Unit and GRX-12VDC Power Supply
GRX-12VDC Power Supply Wiring
External 12VDC Power Supply is required to power
more than three Wallstations and/or Control Interfaces
from a single Control Unit.
8