SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 1 06.04.12
GRAFIKT 5000P / 6000P / 7000P
Processor Panel
Processor panels store and/or process all of the
information needed to run a GRAFIK 5000
TM,
GRAFIK 6000
®, or GRAFIK 7000TM centralized
lighting control system, including the following:
•Scenes,spaces,zones,andgroups
•Timeclocks,sequences,partitioning,andspecial
functions
•Powerpanelcommunication
•Controlstationdevice(CSD)communication
•Lightingzonecontroller(LZC)communication
*
The processor panel may be wired to the following:
•OneeLumenTManager(EM-x-CMP)oracomputer
networkwithWindows
®compatibleeLumenT
software(G7-x-SFT)foreasysystemsetup,control,
and operation
•Congurablelinkswithamaximumof32CSDsor
63LZCsperlink
•OnepowerpanellinktoconnectGP,LP,andXP
power panels
•Oneinterprocessorlinkwithamaximumof
32GRAFIKT 7000P processor panels
GRAFIK 7000P
*GRAFIKT 7000P only
WindowsisaregisteredtrademarkofMicrosoftCorporation
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 2 06.04.12
Specifications
Standards
•ULRListed(Reference:ULFileE42071)
•CSACertied
•CaliforniaEnergyCommissionListed
•SeismicCertied(TestMethodAC156.Reference
OSHPDPreapprovalOSP-0215-10)
•NOMcertiedmodelsavailable
•CEmodelsavailable
•Othercerticatesmayapply
Power
•Dedicatedinputfeed(seeModelNumberssection
fordetails):
-15A@100V
50/60Hz
-15A@120V
50/60Hz
-10A@220-240V
50/60Hz
•Batterybackup:Fullinternalbatterybackupcan
storeallsystemmemoryforveyearswithoutpower.
Systemautomaticallyreturnstostatein
effectpriortopowerinterruption.
•ModelscarryUL,CSA,NOM,and/orCEcertications
•CaliforniaEnergyCommission(CEC)Listed
•SeismicCertied(TestMethodAC156.Reference
OSHPDPreapprovalOSP-0215-10)
Scene Control
•Congureanynumberoflightingscenesforeach
group and space
•Powerpanelzones:
 -GRAFIKT5000P:128zones
 -GRAFIKT6000P:512zones
 -GRAFIKT7000P:512zonesperprocessor
•
GRAFIKEyeR3600,lightingzonecontrollers,and
LutronRSivoiaQED
® window treatments can be included
in a scene and do not count against the zone limit
•Fadeanddelaytimesperzoneareprogrammable
from instantaneous to 90 minutes
Timeclock Control
•Multipletimeclockschedulesavailable
•Triggerscommandsbasedontimeofday,orrelative
tosunriseorsunset(upto+/-2hours)
•Schedulescanbeindividuallyenabled/disabled
fromcontrolstationdevicesorEthernet/RS232
commands
•AutomaticcorrectionforleapyearandDaylight
SavingsTime,whereapplicable
•Timeclockisaccuratetowithin2minutesperyear
Advanced Functions Supported
•ProgrammableSequencing:Automaticlighting
sequencesavailableforeachspace;sequencescan
contain hundreds of steps and each step can be
programmedfrom0.2secondsto90minutesin
0.1secondincrements
•Partitioning:Allowsadaptivecontroloflightingin
partitionable spaces
•Daylightcompensation:Automaticallyselectpreset
scenes comprised of lighting presets and/or window
treatment presets
•Integrationtothird-partyequipmentwith:
-DMX512inputinterfaceonaCSDlink
-DMX512outputinterfaceonapowerpanellink
-Contactclosureinputs/outputsonaCSDlink
-RS232input/outputinterfaceonaCSDlink
-Ethernetinput/outputinterfaceonaCSDlink
Physical Design
•Enclosure:NEMA-Type1,IP-20protection;16U.S.
GaugeSteel
•Weight:50lb(22kg)
•Dimensions:14.38inx34.75inx3.5in(365mmx
883mmx88mm)
•Surfacemountorrecess(ush)mount
•SeismicCertificationLimits:S
DS
=2.5g,z/h=1.0,
I
P
=1.5.ContactLutronfordetails
Compatibility
•CanbeusedtoupgradeOrion
®, or legacy GRAFIK
5000
TM and GRAFIK 6000® processors
•Interfaceswiththird-partyequipment(seeAdvanced
FunctionsSupported)
•CompatiblewithLutronR window treatments
(ACmotorizedandSivoiaQED
®)
Environment
•32to104°F(0to40°C);relativehumiditylessthan
90%non-condensing
•Forindooruseonly
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 3 06.04.12
Model Numbers
G7-AR-0000-0-120
System Capabilities
GRAFIKT 5000P GRAFIKT 6000P GRAFIKT 7000P
# of Processors 1 1 32
#ofCongurableLinks 1CSDonly 3CSDonly 6 per processor
1
# of Power Panels on the
PowerPanelLink
64 125 125perprocessor
#ofZones
2
128 512 512perprocessor
1
Eachcongurablelinkcanhaveupto32CSDsor63LZCs.
2
ZonesconnectedtoGRX-3600,OMX-CCO-8,orSO-SVCcontrolsorlightingzonecontrollersareinadditiontothe
numberofzonesavailableintheprocessor;theyarenotcountedinthisnumber.
100: 100V 50/60Hz,15A
120: 120V
50/60Hz,15A
230: 220—240V
50/60Hz,10A
0: Future use
0000: Withoutcongurablelinks(GRAFIKT 7000Ponly)
W000: 3congurablelinks(GRAFIKT 5000Phasonly1CSDlink;
GRAFIKT 6000Phas3CSDlinks)
WW00: 6congurablelinks(GRAFIKT 7000Ponly)
R: Retrottablepanel(includessubplate)
?: Otheroptionsavailable:contactLutron
A: U.S.Englishversion
?: Multiplelanguagesavailable:contactLutron
7: GRAFIKT 7000P processor panel
6: GRAFIKT 6000P processor panel
5: GRAFIKT 5000P processor panel
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 4 06.04.12
System Overview
Power Panels Processor Panel Control Station Devices (CSDs)
1
IfEthernetisusedtoconnectboththeinterprocessorlinkanduserinterfacelink,theymustbothentertheprocessorpanel
onthesameEthernetwiring.ThereisonlyoneEthernetconnectorperprocessorpanel.AsingleEthernetsegmentcanbe
upto300ft(90m)long.ThismustbeadedicatednetworkforLutronRlightingcontrolonly.
2
RS485Linkscanbeupto2000ft(610m)longwhenusingthecorrectwire.SeetheRS485WiringOverviewformore
details.
Power Panels Control Station Devices (CSDs)
Lighting Zone Controllers (LZCs)
GRAFIKTM
5000P,
6000P,
or
7000P
Feed
Processor Panel
Control unitControl interface Wallstations
Feed LoadsLoads
Standard LZC panel
Small LZC
panel
LZC
LZC
Powerpanellink(RS4852)
125panelsmaximumfor
GRAFIK 6000
® and GRAFIK
7000
TMsystems;64panels
maximumforaGRAFIK5000
TM
system
Controlstationdevice(CSD)andlightingzonecontroller(LZC)
linkwiring(RS4852)withupto32CSDsor63LZCsperlink
GRAFIKT5000Pprocessorhas1CSDlink
GRAFIKT6000Pprocessorhas3CSDlinks
GRAFIKT7000Pprocessorshave0to6CSDorLZClinks
Interprocessorlinkwiring(RS4852or10/100BaseT-Ethernet
1
)
withupto32GRAFIKT7000Pprocessors(GRAFIK7000T
systemonly)
Userinterfacelink(10/100BaseTEthernet
1
orRS485
2
)toa
computerornetworkinterface
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 5 06.04.12
Mounting Processor Panels
Dimensions and Recommended Conduit Entry
Dimensionsshownas:in(mm)
Notes
•Subplatemustberemovedbeforemountingprocessorpanelenclosure.
•Wallstructuremustbereinforced,ifnecessary.Aprocessorpanelweighsupto50lb(22kg)
•Minimumclearancerequired:
3in(76mm)minimumaboveR
3in(76mm)minimumbelow
3in(76mm)minimuminfront
•Operatingenvironment:32to104°F(0to40°C);relativehumiditylessthan90%non-condensing
•Forindooruseonly
14.38
(365)
3.875
(98)
2
(51)
RS232put
Front View Right Side
View
Power panel link
1.5
(38)
6.475
(164)
8.63
(219)
2.875
(73)
0.5 (13) conduit knockouts
Surface mounting
holes (4)
Dedicated Feed Wiring
Control station device
(CSD) or lighting zone
controller (LZC) links
Userterface link
Bottom View
(IEC PELV/NECR Class 2 entry only)
Flush
mounting
holes (4)
34.75
(883)
Interprocessor link
Screws (4) for
hanging
subplate
21.27
(540)
Top View
(No IEC PELV/NECR Class 2 entry)
3.25
(95)
6.0
(152)
6
(152)
1.75
(44)
22
(559)
0.5 (13) and 0.75 (19)
conduit knockouts (18)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 6 06.04.12
Mounting Processor Panels (continued)
Surface mounting notes
•Spacersmustbeusedtoensurethatbacksurface
is1/8in(3.2mm)awayfromthewall.Subplate
mountingscrewswillprotrude1/8in(3.2mm)
behind the panel
gnitnuoM ecafruSgnitnuoM sseceR
Dedicated
feed
Space off
of the wall
as noted
Side ViewFront View Side ViewFront View
Wall shown cut away
16 in
(410 mm)
IEC PELV/
NECR Class 2
IEC PELV/
NECR Class 2
wiring
USA) wiring
Dedicated feed
Ceiling
Ceiling
Warning:ShockHazard.Toavoidtheriskof
electricshock,installpanelswheretheywill
notgetwet.Waterdamagespanels.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 7 06.04.12
Linevoltageinput
Receptacle-forLutronuseonly(120V
versionshown)
Panel power switch
IECPELV/NECRClass2transformers(6maximum)
Normal/Emergencypanelselectorswitch
Powersupplyboard(2maximum)
Mainboardassembly*(seenextpage)
Processor panel address switch*
Ethernetport*
*Note: Labelisshownonfrontsurfaceofunit.
Connectorsandswitchareonbottomsurface.
0
I
Processor Panel Overview
GRAFIKT7000Pprocessorwithsixlinksshown
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 8 06.04.12
Notes
Abbreviationsareasfollows:
 UI= UserInterface
 AUX= Auxiliary
IP = Interprocessor
PP = Power Panel
 EMG= Emergency
 PWR= Power
 COM= Common
 ADDR= Address
Notice: ThisproducthasbeentestedtomeetFCCPart15ClassArequirements.Inadomesticenvironment
thisproductmaycauseradiointerference,inwhichcasetheusermayberequiredtotakeappropriatemeasures.
Main Board Assembly
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link A
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link D
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link B
PWR
TX
RX
COM
PWR
MUX
MUX
DRAIN
1234D
UI Link
TX
RX
COM
PWR
MUX
MUX
DRAIN
1234D
AUX Link
TX
RX
COM
PWR
MUX
MUX
DRAIN
1234D
IP Link
TX
RX
COM
SENSE
MUX
MUX
DRAIN
1234D
PP Link
Ethernet
ACT LINK
ADDR
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link E
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link C
PWR/EMG
STAT
ACT
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link F
GRAFIKT7000Pwithsixlinksshown
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 9 06.04.12
Notice:Iflinkterminators(LT-1)arenotusedwhen
needed, or improper wiring topology is employed, the
systemmaynotcommunicate.
RS485 Wiring Overview
RS485wiringistheIECPELV/NECRClass2wiring
usedforthefollowinglinks:
•Controlstationdevice(CSD)link(s)
•Localzonecontroller(LZC)link(s)
•Powerpanel(PP)link
•Interprocessor(IP)link(ifnotusingtheEthernet
connectionoption)
•Userinterface(UI)link(ifnotusingtheEthernet
connectionoption)
Specifications and Notes
•DonotrunIECPELV/NECRClass2RS485wiringin
sameconduitasline(mains)voltagewiring;followall
applicable local and national electrical codes
•Eachlinkmustbedaisy-chained;donothome-run
wiringtoindividualdevices
•Theprocessorpaneldoesnotneedtobeattheendof
anyRS485link
•Usealinkterminator(LT-1)ateachendofeachRS485
link,withtheexceptionoftheLZClinks,whichdonot
requirelinkterminators
•Connectionstonumberedterminalsarewired
1to1,2to2,3to3,etc.throughouttheCSD,PP,
andIPlinks
•TotallengthofanyRS485linkmaynotbemore
than2000ft(610m).Thisdistanceisbasedon
propershieldingofthetwistedshieldedpair,12AWG
(2.5mm
2
)wiretoterminal1andterminal2oftheCSD
link,andtheuseofalinkterminator(LT-1)ateachend
ofeachnon-LZClink.
•If12AWG(2.5mm()wireisnotusedonterminals
1and2oftheCSDlink,themaximumCSDlinklength
mustbede-rated;seechart.LengthofLZC,PP,IP,
andUIlinksdonotneedtobede-ratedifsmallerwire
sizesareusedonterminals1and2.
•Alinkbooster(MX-RPTR)canbeusedtoincreasethe
CSDorPPlinklengthbyanother2000ft(610m),toa
maximumof3linkboostersand8000ft(2440m);link
boosterscannotbeusedonLZClinks
•RS485communicationisastreamoflow-voltage
data.Suggestionslistedonthispagehelptokeepthat
communication reliable:
 -Propershieldingblocksnoise
 -LT-1terminationstops“datareection”from
corruptingdataonthelink
 -Daisy-chainingeliminatesmultiple”datareection”
paths
 -12AWG(2.5mm
2
)wireonterminals1and2ofthe
CSDlinkminimizespowerlosstotheCSDs
Terminals 1 & 2
Wire Sizes
Maximum CSD
Link Length
12AWG(2.5mm
2
) 2000ft(610m)
14AWG(2.5mm
2
) 1400ft(425m)
16AWG(1.5mm
2
) 900ft(275m)
18AWG(1.0mm
2
) 600ft(180m)
2000 ft (610 m) max.
LT-1 CSD
CSD
CSD
CSD
G7000P
CSD
LT-1
Exampleofdaisychainwiring.
Donothome-runindividualdevicewiring.
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 10 06.04.12
ExampleofCSDlinkconnections
RS485 Wiring Overview (continued)
Additional RS485 Wiring Notes
•Two12AWG(2.5mm
2
)wirescannottintomost
deviceconnectorsontheRS485link.Usea
screw-onconnector(orotherapprovedconnector)
to“T-tap”a18AWG(1.0mm
2
)wiretoeach
connectorterminal,asneeded.Makethis“T-tap”
inthewallboxinordertokeepthelengthofthenew
18AWG(1.0mm
2
)wire(s)asshortaspossible
•Connecttheuninsulateddrain/shieldwire(s)to
terminalD/Shieldwheneverpresent.Ifthereisno
terminalD/Shield,connectthetwodrain/shieldwires
together,makingacontinuousshieldthroughoutthe
link.Ifthedeviceattheendofthelinkdoesnothave
aDrain/Shieldterminal,terminatethewireandleave
itdisconnected.
•Donotallowanypartofthedrain/shieldwireto
touchground(earth)oranyelectricalcircuitry
•CSDsshouldbemountedinmetalwallboxesthat
areconnectedtogroundedconduit.Groundingthe
metalmountingplatekeepselectrostaticdischarge
fromaffectingthedevicesontheRS485link.
Approved sources of wire include:
Twisted-shieldedpair(datalink)only:
•Belden#9461
•Alpha#2211
 One-cablesolutions(datalink,controlpowerwiring,
andsenselineinonecable):
•LutronRGRX-CBL-46L-500(non-plenum)
•LutronRGRX-PCBL-46L-500(plenum)
•Belden,Alpha,Liberty,andSignaturehave
approvedcables;askforGRAFIKEyeR cable
Note:SenselineisusedonlyonPPlink.
Control station
device (CSD)
connector
Drain/shield
One 18 AWGOne 18 AWG
(1.0 mm
2
)
(1.0 mm
2
)
Two 12 AWG
Two 12 AWG
(2.5 mm
2
)
(2.5 mm
2
)
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 11 06.04.12
Line Voltage Wiring of
Processor Panel
Notes
•Makesurelinevoltagefeedwiringenterstheprocessorfromthetopright
•Runadedicatedfeedcircuit(seeModelNumberssectionforfeedrating)
•Runwiringsothatline(mains)voltageisseparatefromIECPELV/NECRClass2wiring
I
N N N H H
N
T6
T1
N N
T2
N
T3
N
T4
N
T5
H
T1
T2
H
T4
H
H
T3
H
T5
0
I
N N N H H
T6
H
GROUND/EARTH
(green)
Receptacle
for Lutron
use only
shown)
(120 V~
HOT/LIVE
(black - 100 V~ , 120 V~ )
(brown - 230 V~ )
NEUTRAL
(white - 100 V~ , 120 V~ )
(blue - 230 V~ )
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 12 06.04.12
Control Station Device (CSD)
Link Wiring
Notes
•Followthejobdrawingstoconnectcontrolstationdevicestotheproperlinkontheprocessor(linkA-F)
•ItisnotnecessarytohavetheprocessorpanelattheendofanyRS485link
•SeeRS485WiringOverviewforapprovedcableoptions
•LinksAthroughFcanbeusedaseitherCSDorLZClinksinaGRAFIK7000Tsystem;functionisdenedusing
eLumenT software
N
T6
T1
N N
T2
N
T3
N
T4
N
T5
H
T1 T2
H
T4
H
H
T3
H
T5
0
I
N N N H H
T6
H
Control Wiring
(2) 12 AWG (2.5 mm
2
)
1: Common
2: PWR
Last Control Station Device on Link
Data Link
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
D: Drain wire in shield - Connect together to make one continuous link
shield. Keep away from ground and control electronics.
Link
Terminator
(LT-1)
Link
Terminator
(LT-1)
Control Station Devices
IR Ceiling
Receiver
COM
PWR/EMG
MUX
MUX
DRAIN
Processor Panel
(GRAFIKT 7000P
with 6 links shown)
1234D
1 2 3 4 5 6
4
3
2
1
1
2
3
4
Link A
(typical)
34 34
Note: Label shown is on top of processor assembly.
Connectors are located on bottom surface of processor
assembly.
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 13 06.04.12
Power Panel (PP) Link Wiring
Notes
•ItisnotnecessarytohavetheprocessorpanelattheendofthePPlink
•Thepowerpanellink’ssensewireisusedwheneverthereisapanelbeingsuppliedbyanemergency/essential
feed;seepowerpanelinstructionsformoredetails
•SeeRS485WiringOverviewforapprovedcableoptions
N
T6
T1
N N
T2
N
T3
N
T4
N
T5
H
T1
T2
H
T4
H
H
T3
H
T5
0
I
N N N H H
T6
H
Data Link
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
D: Drain wire in shield - Keep away from ground and all
electronics
Control Wiring
(2) 18 AWG (1.0 mm
2
)
1: Common
2: Sense
Link
Terminator
(LT-1)
Link
Terminator
(LT-1)
Power Panel
Power Panel
Last Power
Panel on Link
Emergency /
Essential Sense
Line
(1) 18 AWG (1.0 mm
2
)
5: Sense Line
Processor Panel
(GRAFIKT 7000P
with 6 links shown)
COM
SENSE
MUX
MUX
DRAIN
1234D
1 Common
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense Line
1 Common
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense Line
1 Common
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense Line
PP Link
34
34
Note: Label shown is on top of processor assembly.
Connectors are located on bottom surface of processor
assembly.
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 14 06.04.12
Ethernet Wiring Options
Notes
•WiringdistanceforanysingleEthernetdatalinksegmentis300ft(90m)max;useswitches,hubs,ortheRS485
WiringOptionforlongerdistances
0
I
I. Ethernet User Interface Only Wiring Option (Direct to Computer)
GRAFIKT
7000P
GRAFIKT
7000P
eLumenT
manager
Network switch or
hub (provided by
others)
eLumenT
manager
Ethernet data link from eLumenT manager to network interface to processor(s):
(1) Category 5 UTP (unshielded, twisted pair) cable
The wall jack shown is an NT-6PS-WH with an RJ45 connector.
Ethernet data link from one eLumenT manager to one processor:
(1) Category 5 UTP (unshielded, twisted pair) crossover cable
II
. Ethernet Wiring Option for User Interface and Interprocessor
(with Network Switch or Hub)
Processor panel
(GRAFIKT 7000P
with 6 links shown)
14
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 15 06.04.12
User Interface (UI) RS485 Link Wiring
Notes
•LeavethePWRconnectionoftheprocessor’sUIlinkunconnected
•OneUIlinkconnectionisrequiredforeachprocessor;multipleprocessorscannotbeconnectedtothesameUI
link
•WiringtheUIlinkviaRS485isnotnecessaryiftheprocessorisconnectedviaEthernet(SeeEthernetWiring
Optionsfordetails)
•SeeRS485WiringOverviewforapprovedcableoptionsandadditionalinformationwhenusingtheRS485wiring
method
N
T6
T1
N N
T2
N
T3
N
T4
N
T5
H
T1
T2
H
T4
H
H
T3
H
T5
0
I
N N N H H
T6
H
1 3 4
UI Link
RS485 data link from network interface to (each)
processor:
(1) 18 AWG (1.0 mm
2
)
1: Common
2: No connection
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
D: Drain wire in shield - Keep away from ground or
circuitry.
Ethernet data link from computer to
network interface:
(1) Category 5 UTP (unshielded,
twisted pair) cable
Network Interface shown is an Ethernet to RS485 converter
(G7-A-NWK-E-D-x).
The wall jack shown is an NTOMX-485J-WH.
eLumenT
manager
Network
interface
Link
terminator
(LT-1)
Link
terminator
(LT-1)
Processor panel
(GRAFIKT 7000P
with 6 links shown)
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
34
34
Note: Label shown
is on top of
processor assembly.
Connectors are
located on bottom
surface of
processor assembly.
To UI link on other
GRAFIKT 7000P
processors
15
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 16 06.04.12
Interprocessor (IP) RS485 Link Wiring
(GRAFIKT 7000P processor only)
Notes
•LeavethePWRconnectionoftheprocessor’sIPlinkunconnected
•WiringtheinterprocessorlinkviaRS485isnotnecessaryiftheGRAFIKT7000Pprocessorsareconnectedvia
Ethernet(seeEthernetWiringOptionsfordetails)
•SeeRS485WiringOverviewforapprovedcableoptionsandadditionalinformationwhenusingtheRS485wiring
method
0
I
Processor Panel
(GRAFIKT 7000P only)
Link
terminator
(LT-1)
GRAFIKT 7000P GRAFIKT 7000P
Data Link
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
D: Drain wire in shield
Control wiring
(1) 18 AWG (1.0 mm
2
)
1: Common
2: No connection
Link
terminator
(LT-1)
IP Link
COM
PWR
MUX
MUX
DRAIN
1234D
COM
PWR
MUX
MUX
DRAIN
1234D
IP Link
COM
PWR
MUX
MUX
DRAIN
1234D
IP Link
Last GRAFIKT 7000P on link
COM
PWR
MUX
MUX
DRAIN
1234D
IP Link
34 34
Note: Label shown is on top of processor assembly.
Connectors are located on bottom surface of processor
assembly.
16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 17 06.04.12
Notes
•LinkterminatorsarenotneededonLZClinks
•SeeRS485WiringOverviewforapprovedcableoptions
•LinksAthroughFcanbeusedaseitherCSDorLZClinksina
GRAFIKT7000Pprocessor;functionisdenedusingeLumenT manager
•ItisnotnecessarytohavetheprocessorpanelattheendoftheCSDor
LZClink
PS SIGNAL
PS CO M
CIR COM
WC COM
WC SIGNAL
+24V
+15V
OCC SI G
OCC CO M
MU X
MU X
LINK CO M
EMER G
PS SIGNAL
PS CO M
CIR COM
WC COM
WC SIGNAL
+24V
+15V
OCC SI G
OCC CO M
MU X
MU X
LINK CO M
EMER G
N
T6
T1
N N
T2
N
T3
N
T4
N
T5
H
T1
T2
H
T4
H
H
T3
H
T5
0
I
N N N H H
T6
H
Processor panel
(GRAFIKT 7000P
with 6 links shown)
COM
PWR/EMG
MUX
MUX
DRAIN
1234D
Link A
(typical)
MUX
MUX
COM
EMERG
DRAIN
LZC
MUX
MUX
COM
EMERG
DRAIN
LZC
MUX
MUX
COM
EMERG
DRAIN
LZC
LZC panel
Last LZC panel on link
LZC
Data Link
(1) shielded, twisted pair
18 AWG (1.0 mm
2
)
3: MUX
4: MUX
D: Drain wire in shield
Control wiring
(2) 18 AWG (1.0 mm
2
)
1: Common
2: EMERG
Note: Label shown is on top
of processor assembly.
Connectors are located on
bottom surface of processor
assembly.
Lighting Zone Controller (LZC) Link Wiring
(GRAFIKT 7000P processor only)
17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK SystemsT GRAFIKT 5000P / 6000P / 7000P Centralized Lighting Control Systems
369-643a 18 06.04.12
Set Normal/Emergency Panel Selector Switch (GRAFIKT 7000P only)
Thenormal(non-essential)/emergency(essential)switchlocatedonthepowersupplyboardintheprocessorpanel
determines the operation of lighting zone controller and power panel zones on the processor in the case of a
powerlossoremergencycondition.SeetheProcessorPanelOverviewforswitchlocation.Functionalityofpower
panelzonesisdeterminedbytheNormal/Emergencypanelselectorswitchlocatedineachpowerpanel.Seethe
installationmanualforeachpowerpanelforhelplocatingtheNormal/Emergencyswitch.
Switch Position Description Operation of LZCs Operation of Power Panels
Left Normal(non-essential) Lightingzonecontrollersconnected
toanLZClinkonthisprocessor
panel will enter emergency mode
when power is lost to this
processor panel and all power
panelsonthepowerpanellink
thataresettoNormal.
Power panels connected to
thepowerpanellinkonthis
processorwillenteroverride
mode when power is lost to this
processor panel and all power
panelsonthepowerpanellink
thataresettoNormal.
Center Ignored Lightingzonecontrollersconnected
toanLZClinkonthisprocessor
panel will enter emergency mode
when power is lost to this
processor panel and all power
panelsonthepowerpanellink
thataresettoNormal.
This processor panel has no
effect on power panels
connected to the power panel
linkofthisprocessor.
Right Emergency(essential) Lightingzonecontrollersconnected
toanLZClinkonthisprocessor
panel will enter emergency mode
when power is lost to all power
panelsonthepowerpanellink
thataresettoNormal.
This processor panel has no
effect on power panels
connected to the power panel
linkofthisprocessor.
Notes
•Ifnopowerpanelsareinstalled,theNormal/Emergencypanelselectorswitchmustbesettothe“Ignored”
position
•LZCsinemergencymodewillbeforcedtotheiruser-conguredemergencylevel.Powerpanelsinoverridemode
willbeforcedtotheiruser-conguredoverridelevel.LevelsaresetusingtheeLumenTsoftware.
•ContactLutronforapplicationswhereonlyasubsetofLZCsshouldenteremergencymodeduringapowerloss
or emergency condition
•ALUT-ELI-3PHisneededforeachprocessorpaneltomakethelightingcontrolsystemUL-924compliant.Seethe
installationguideprovidedwiththeLUT-ELI-3PHforcompletedetails.
•ALUT-ELI-3PHinitiatinganemergencyconditionwillcausealllightingzonecontrollerzonestoenteremergency
modeandallpowerpanelzonestogototheiroverrideleveliftheircorrespondingpanelselectorswitchissetto
Emergency(essential).ThiswilloccurregardlessofthestatusofallNormalpanels.
18