SPECIFICATION SUBMITTAL
GP Dimming Panels 6 11.13.08
Power Equipment
GP Dimming Panels
GRAFIK Systems
Wiring
• Internal: Prewired by Lutron.
• System communications: Low-
voltage Class 2 (PELV) wiring
connects Dimming Panels to
other components.
• Line (mains) voltage: Feed, load,
and control circuit wiring only.
No other wiring or assembly
required.
Filter Chokes
• Load current rise time is
measured at a 90 degree
conduction angle, with 120 V
input power.
• 10-90% of load current
waveform:
- 350μSec rise time at 50%
dimmer capacity.
- 400μSec rise time at 100%
dimmer capacity.
• 0-100% of load current
waveform:
- 525μSec rise time at 50%
dimmer capacity.
- 600μSec rise time at 100%
dimmer capacity.
• At no point in the waveform can
the rate of current change
exceed 300 mA per μSec.
• Consult Lutron for higher rise
time options.
Standards
• Complies with CE.
• California Energy Commission Listed
Power
• Input power: 230 V, 50/60 Hz,
phase-to-neutral.
• Branch Circuit Capacity: 10 A
• Number of Circuits: 3-24
• Branch Circuit Breakers: IEC-rated
thermal magnetic.
AIC rating (other ratings available):
6000 A
• Lightning strike protection: Meets
ANSI/IEEE standard 62.41-1980.
Can withstand voltage surges of up
to 6000 V and current surges of up
to 3000 A.
• 10-year power failure memory:
Automatically restores lighting to
scene selected prior to power
interruption.
Sources/Load Types
Operates these sources with a
smooth continuous Square Law
dimming curve or on a full
conduction non-dim basis:
• Incandescent (Tungsten)/Halogen
• Magnetic Low Voltage Transformer
• Electronic Low Voltage Transformer
1
• Lutron Electronic Fluorescent
Dimming Ballasts
• Magnetic Fluorescent Lamp Ballasts
• Optional modules allow for control of
0-10 V, DSI, and PWM load types.
• Operates HID sources on a full
conduction non-dim basis.
Dimming Cards
• Panel current ratings are listed
for continuous operation.
• RTISS
® filter circuit technology
compensates for incoming line
voltage variations: No visible
flicker with +/-2% change in
RMS voltage/cycle and +/-2%
Hz change in frequency/second.
• Arcless-relay air gap-off
switches (one per load circuit)
ensure open load circuits when
off function selected. Eliminate
arcing at mechanical contacts
when loads are switched.
Physical Design
• Enclosure: NEMA-Type 1 (Type
2 available upon request), IP-20
protection; #16 U.S. Gauge
Steel. Indoors only.
• Weight: 30-175 pounds
(14-80 kg).
• Mounting: Surface mount only.
Allow space for ventilating.
Environment/Heat Dissipation
• Patented, ribbed aluminum heat
sink base cools Panel by
convection. No fans.
• 32-104 °F (0-40 °C). Relative
humidity less than 90%
non-condensing.
Specifications - 230 Volt (CE)
1
Reverse-phase control transformers require an ELVI Power Interface. Check phase with transformer manufacturer.