C-R-M1-WH
EcoSystem
TM
Mounting
Determine the proper location of the Infrared
Receiver using the adjacent diagram.
• The IR receiver responds to IR signals from up to 8'
away when mounted on a 10' ceiling.
• The cone of reception is entered upon the IR Receiver
as shown.
• The cone of reception is diminished when the receiver
is mounted less than 10' from the floor.
• The receiver requires a clear line of sight between
itself and the remote control for proper operation.
Mounting the IR Receiver
• Drill a 3/8 in. (10mm) diameter hole in the ceiling tile or
pendant fixture
• Thread the wires through the hole
• Install the IR Receiver into the hole
• Secure the IR Receiver with the mounting hardware
provided (hand tighten only).
Note - If the stem of the IR Receiver must be
shortened due to its location (for instance, in a
pendant fixture) this should be done prior to wiring.
3'
7'
Wiring to an EcoSystem Ballast
• Connect the IR Receiver’s wires as described:
W
ire Terminal
Red 20VDC
Black Common
White IR Signal
• Make sure that the supply breaker to the control
system is OFF
• Only #22AWG solid wire for ballast terminals
.