SPECIFICATION SUBMITTAL
C-R-M1-1 2.19.08
Infrared Receiver
C-R-M1-WH
EcoSystem
TM
Fixture Mountable Infrared Receiver
The EcoSystem Infrared Receiver provides personal
control input by wiring directly to the EcoSystem
ballast or module. The Infrared (IR) receiver functions
to both control one fixture or a group of fixtures. The
IR receiver can also be used as a programming port
for the system.
Features
• Mounts easily on any ceiling tile or fixture with 3/8 in.
(10mm) diameter hole
• Threaded mounting stud (may be shortened for
applications with limited fixture height)
• Receives IR signals and transfers them to an
EcoSystem Digital Ballast or Ballast Module
• Integral LED indicates signal reception
• IR reception from up to 8 ft away.
• Constructed of flame retardant material with UL94 HB
rating
• Meets IEC 801-2. Tested to withstand 15kV
electrostatic discharge without damage
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
C-R-M1-2 2.19.08
Infrared Receiver
C-R-M1-WH
EcoSystem
TM
Specifications
Standards
• Designed for Class 2 operation only. Voltages do not
exceed 35VDC. Complies with requirements of NFPA
70, of the National Electric Code (NEC)
• Follow all applicable national and/or local wiring
regulations when installing this IR receiver
• For use with Lutron EcoSystem products only
Power
• Operating Voltage: Low-voltage Class 2, 20VDC
• Current draw: less than 5 mA
• IR Output: 0-20VDC
Environment
• Temperature: 32-113°F (0-45°C)
• Relative humidity: less than 90% non-condensing
• Lead length = 4” (101mm) minimum beyond threaded
stud.
• Total wire length from IR receiver to device must not
exceed 100 ft (30 m).
• Threaded Stud Diameter = 3/8” (9.5mm) maximum.
• Use 3/8-16 nut (provided) for mounting.
1.25” (32 mm)
0.69” (17 mm)
1.18” (30 mm)
Dimensions
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
C-R-M1-3 2.19.08
Infrared Receiver
C-R-M1-WH
EcoSystem
TM
Mounting
Determine the proper location of the Infrared
Receiver using the adjacent diagram.
• The IR receiver responds to IR signals from up to 8'
away when mounted on a 10' ceiling.
• The cone of reception is entered upon the IR Receiver
as shown.
• The cone of reception is diminished when the receiver
is mounted less than 10' from the floor.
• The receiver requires a clear line of sight between
itself and the remote control for proper operation.
Mounting the IR Receiver
• Drill a 3/8 in. (10mm) diameter hole in the ceiling tile or
pendant fixture
• Thread the wires through the hole
• Install the IR Receiver into the hole
• Secure the IR Receiver with the mounting hardware
provided (hand tighten only).
Note - If the stem of the IR Receiver must be
shortened due to its location (for instance, in a
pendant fixture) this should be done prior to wiring.
3'
7'
Wiring to an EcoSystem Ballast
• Connect the IR Receiver’s wires as described:
W
ire Terminal
Red 20VDC
Black Common
White IR Signal
• Make sure that the supply breaker to the control
system is OFF
• Only #22AWG solid wire for ballast terminals
.
+20V
Daylight
Occ
IR
Common
Class 2 (#22 AWG Solid)
E2
E1
Class 2
Bus
DH
NEU
277 Volt
SH
Mounting and Wiring
Ceiling Tile or Fixture
Pendant Fixture
IR Receiver
#22AWG solid only
Radius = 8'
3