R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Q-BAC-SFT-LIC 1 07.10.08
Lighting Control Systems
Q-BAC-SFT-LIC
Quantum
BACnet IP for Quantum
Description:
License for Quantum lighting hub to enable BACnet IP integration which allows
control of EcoSystem ballasts and modules in Lutron’s Quantum lighting
control system. BACNet IP is embedded in the Quantum Lighting Hub.
Features:
Set Light Level - write to the present value of the object to send all ballasts in
an Area to the commanded level.
Get Light Level - read the present value of the object to get the average light
level in the Area.
On/Off Status - read the present value of the object to get a report of the
On/Off status of the Area, if any ballasts in the Area is on, the Area value is
ON. Fault event state of this object will notify the user of a ballast failure or
lamp outage in the Area.
• Fault - reading the present value will indicate a fault in the Area such as lamp
outage. The object name will indicate fault type.
Loadshed - write to the present value of the object to command an Area to
loadshed by a percentage, 0 is no loadshed.
• Afterhours - begin and end afterhours mode in the Area by writing to the
present value of this object.
• Occupancy Status - read the present value to determine if any occupancy
sensor in the Area is tripped, indicating that the Area is occupied.
• Reading commandable output objects will report last value written.
• Information will be given based on an Area on an EcoSystem Link. Areas
must be setup using a PDA. Ballasts that are not part of an Area will not be
accessible by BACnet.
Each Area will be discovered as a BACnet device. Each device (Area) will
have the objects listed below.
Feature Naming BACnet Object Present value Monitor/
Convention Type Command
Set Light Level Area Name, Target Intensity Analog Output 0-100% Command
Get Light Level Area Name, Average Intensity Analog Input 0-100% Monitor
On/Off Status Area Name, On/Off Binary Input On/Off (1,0) Monitor
Fault Event State Indicates Lamp Outage/Ballast Failure
Loadshed Area Name, Loadshed Analog Output 0-100% Loadshed (0 = Disabled) Command
Afterhours Area Name, Afterhours Binary Output Enable/Disable (1,0) Command
Occupancy Status Area Name, Occupancy Multi-state Value Occupied/Unoccupied/No Sensor (1,2,3) Monitor
Fault Area Name, Fault (Fault Type) Binary Input Fault/No Fault (1,0) Monitor
Lighting Hub
Includes BACnet IP Protocol
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Q-BAC-SFT-LIC 2 07.10.08
Lighting Control Systems
Q-BAC-SFT-LIC
Quantum
System Network Diagram:
Provided by Others
Provided by Others
Ethernet
Ethernet
Switch
QED
Link
EcoSystem
Link
Company A
BACnet IP
Controller
Company B
BACnet IP
Controller
BACnet
Workstation
BACnet IP
Lighting Hub
EcoSystem
TM
Ballast
Up to 64 Ballasts per Link
Up to 96 Devices
Shades
Includes BACnet IP Protocol
Q-Manager
TM
with Q-Admin
TM
(See Note 4)
Example Wiring Diagram
Notes:
11..
An Area may consist of 1 or more ballasts up to a maximum of 64.
22..
A maximum of 64 Areas per EcoSystem Link are allowed.
33..
A ballast may only belong to one Area.
44..
Shade control over BACnet is not available.
55..
Areas do not cross EcoSystem Links.
66..
Requires use of Q-Admin software package.
77..
The get light level may not match the set light level due to daylighting, loadshed and local or Q-Admin
control.
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Q-BAC-SFT-LIC 3 07.10.08
Lighting Control Systems
Q-BAC-SFT-LIC
Quantum
BACnet Protocol Implementation Conformance Statement (PICS)
Date: April 18, 2008
Vendor Name: Lutron Electronics Co., Inc.
Product Name: Quantum BACnet Integration
Product Model Number: Q-BAC-SFT-LIC
Applications Software Version: 04
Firmware Revision: 00.08
BACnet Protocol Revision: 2
Product Description:
License for Quantum lighting hub to enable BACnet IP Integration. Allows control of EcoSystem ballasts and
modules in Lutron’s Quantum lighting control system. BACNet IP is embedded in the Quantum Lighting Hub.
BACnet Interoperability Building Blocks Supported (Annex K):
K.1.1 BIBB Data Sharing ReadProperty-B (DS-RP-B)
K.1.8 BIBB Data Sharing WriteProperty-B (DS-WP-B)
K.1.4 BIBB Data Sharing ReadPropertyMultiple-B (DS-RPM-B)
K.1.10 BIBB Data Sharing WritePropertyMultiple-B (DS-WPM-B)
K.5.2 BIBB Device Management DynamicDeviceBinding-B (DM-DDB-B)
K.5.6 BIBB Device Management DeviceCommunicationControl-B (DM-DCC-B)
K.5.12 BIBB Device Management TimeSynchronization-B (DM-TS-B)
K.5.14 BIBB Device Management UTCTimeSynchronization-B (DM-UTC-B)
K.5.16 BIBB Device Management ReinitializeDevice-B (DM-RD-B)
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
Segmentation Capability:
Segmented requests supported? No. Window Size: n/a
Segmented responses supported? No. Window Size: n/a
Non-Standard Application Services:
Non-standard application services are not supported.
Standard Object Types Supported:
Device
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: Object Name.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Q-BAC-SFT-LIC 4 07.10.08
Lighting Control Systems
Q-BAC-SFT-LIC
Quantum
Analog Output
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: Present Value: 0 to 100 (%).
Analog Input
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Binary Output
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Binary Input
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Multi-State Value
1. Dynamically creatable using BACnet’s CreateObject service? No.
2. Dynamically deletable using BACnet’s DeleteObject service? No.
3. List of optional properties supported: None.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Data Link Layer Options:
BACnet IP
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
Q-BAC-SFT-LIC 5 07.10.08
Lighting Control Systems
Q-BAC-SFT-LIC
Quantum
Device Address Binding:
Is static device binding supported? No.
Networking Options:
None
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ANSI X3.4
If this product is a communication gateway, describe the types
of non-BACnet equipment/network(s) that the gateway supports:
The device is a communication gateway between the BACnet protocol and EcoSystem ballasts and modules in
Lutron’s Quantum lighting control system.
5