(2) 1.0 mm
2
(#18 AWG)
twisted, shielded pair
from terminals 3 to 3,
and 4 to 4
1.0 mm
2
(#18 AWG)
(2) 2.5 mm
2
(#12 AWG)
Addressing
• Set Address Switches 1-4 to give the GRX-WCI the
unique system address from 1 to 16.
• Set Function Switches to specify function as shown
in Functionality chart.
Low-Voltage PELV (Class 2) Wiring
• Use low-voltage PELV (Class 2) wiring to daisy-
chain GRX-WCI to Control Units and other
components.
• Lutron recommends that all connections be made
in the wallbox.
• If a remote connection (T-tap) must be made, the
maximum wire length from the communication link
to the connected unit must be 2.5m (8 ft.).
When used with GRX-3000 Control Units
• Two 1.0mm
2
(#18 AWG) conductors for common
(terminal 1) and 12VDC (terminal 2). Ensure that
the terminal 2 connection is wired correctly. Refer
to GRX-3000 Specification Submittal for more
details.
• One shielded, twisted pair 1.0mm
2
(#18 AWG) for
data (terminals 3 and 4).
When used with GRX-4000 Control Units
• Two 2.5mm
2
(#12 AWG) conductors for common
(terminal 1) and 24VDC (terminal 2). Connect as
shown below.
• One shielded, twisted pair #1.0mm
2
(#18 AWG)
for data (terminals 3 and 4).
• Connect Drain as shown.
- Do not connect to Ground (Earth) or Wallstation.
- Connect the drain and cut off the outside shield.