R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-1 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
Description
• Used with GRAFIK 5000/6000/7000
Centralized Lighting Control Systems.
• Supplies power and dimming for up to six
zones of lighting
1
.
• Provides pushbutton recall of four preset
lighting scenes, plus Off.
• Controls many light source types directly, and
others using power interfaces.
• Provides lockout options to prevent
accidental changes.
• Includes built-in infrared receiver for
operation with an optional remote control.
Models available to:
• Accept 120V, 220-240V (non-CE), 230V (CE)
and 100V input power.
• Control two to six zones of lighting
1
.
OMX-3600 Control Unit
Cover (shown open)
Infrared Receiver
Scene Selection
Buttons
ZoneBase
1
These do not count towards the maximum number of Processor zones. Processor can only control via scene selection. Individual
OMX-3600 zone contr
ol is not possible thr
ough the GRAFIK 5000/6000/7000 Centralized Lighting Contr
ol System.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-2 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electrostatic discharge without damage or
memory loss.
• Compensates in real time for incoming line voltage
variations: No visible flicker with +/-2% change in
RMS voltage/cycle and +/-2% Hz change in
frequency/second.
• 10-year power failure memory automatically
restores lighting to levels prior to power interruption.
• Faceplate snaps on with no visible means of
attachment.
System Communications and Capacities
• Low-voltage type Class 2 (PELV) wiring connects
Control Units to other system components.
• The OMX-3600 Control Unit counts as one of 32
maximum Wallstations and/or Control Interfaces
allowed on a Class 2 (PELV) Control Station Device
Link.
Environment
• 32-104°F (0-40°C). Relative humidity less than
90% non-condensing.
Specifications
Input Power
• 120V, 220-240V (non-CE), 230V (CE) or 100V,
50/60Hz.
• Lightning Strike Protection: Meets ANSI/IEEE
standard 62.41-1980. Can withstand voltage surges
of up to 6000V and current surges of up to 3000A.
Lighting Sources/Load Types
Controls the following lighting sources with a
smooth, continuous Square Law dimming curve or
on a full conduction non-dim basis:
• Incandescent, Tungsten, Magnetic Low Voltage
Transformer
• Lutron Tu-Wire
® Electronic Fluorescent Dimming
Ballast
• Neon and Cold Cathode
Controls the following lighting sources with a smooth
continuous Square Law dimming curve through
separate power interfaces:
• Electronic Low Voltage Transformer
• Lutron Electronic Fluorescent Dimming Ballast
Preset Control
4 preset lighting scenes and off are accessible from
the Control Unit front panel.
• 12 additional scenes are stored in the Control Unit.
These scenes are accessible via Wallstations,
Control Interfaces, and/or PC.
• Light levels fade smoothly between scenes. Fade
time can be set dif
ferently for each scene, between
0-59 sec. or 1-60 min. Fade time from Off is
capped at 5 sec.
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-3 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
O M X - 3 6 0 2 - T - A U - W H
Prefix
Number
of Zones
Input
Voltage
Cover
Option
Color
Option
Color Options
Architectural Matte Finishes
Standard – Ship in 48 hours
Cover Option: A or T
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Designer Gloss Finishes
Ship in 4 to 6 weeks
Cover Option: A only
White GWH
Light Almond GLA
Almond GAL
Ivory GIV
Satin Color Matte Finishes
Cover Option: A or T
Hot HT
Ochre OC
Terracotta TC
Desert Stone DS
Stone ST
Limestone LS
Blue Mist BT
Midnight MN
Taupe TP
Biscuit BI
Eggshell ES
Snow SW
Architectural Metal Finishes
Cover Option: T only
Bright Brass
BB
Bright Chrome BC
Satin Brass
SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Bright Nickel
BN
Anodized Aluminum Finishes
Cover Option: T only
Clear CLA
Black BLA
Brass BRA
Bronze BZA
Prefix:
OMX
for Contr
ol Units used with
GRAFIK 5000/6000/7000 systems.
Number of Zones:
2, 3, 4, or 6
Cover Option:
A
for Opaque
T for Translucent Black
Input Voltage
__
(no code) for 120V Single Feed
AU for 220-240V (non-CE)
CE for 230V (CE)
JA for 100V
Color Option:
See Color Options list
Cover Options
Opaque A
Cover and Base will match.
Translucent Black T
Black Cover and choice of
base color.
Also available:
- Custom controls
- Color matching
- Engraving
These options ship in 4 to 6
weeks
How to Build a Model Number
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-4 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
Model Numbers
120V Input Power
100V Input Power
230V (CE) Input Power
220–240V (non-CE) Input Power
Number
of Zones
2
3
4
6
Model Number
OMX-3602-_-__
OMX-3603-_-__
OMX-3604-_-__
OMX-3606-_-__
Unit Capacity
(Watts/VA)
1200
1500
2000
2000
Zone Capacity
(Watts/VA)
800
800
800
800
Number
of Zones
2
3
4
6
Model Number
OMX-3602-_-AU-__
OMX-3603-_-AU-__
OMX-3604-_-AU-__
OMX-3606-_-AU-__
Unit Capacity
(Watts/VA)
1600
2400
3000
3000
Zone Capacity
(Watts/VA)
1200
1200
1200
1200
Number
of Zones
2
3
4
6
Model Number
OMX-3602-_-CE-__
OMX-3603-_-CE-__
OMX-3604-_-CE-__
OMX-3606-_-CE-__
Unit Capacity
(Watts/VA)
1600
2300
2300
2300
Zone Capacity
(Watts/VA)
800
800
800
800
Number
of Zones
2
3
4
6
Model Number
OMX-3602-_-JA-__
OMX-3603-_-JA-__
OMX-3604-_-JA-__
OMX-3606-_-JA-__
Unit Capacity
(Watts/VA)
1000
1250
1600
1600
Zone Capacity
(Watts/VA)
600
600
600
600
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-5 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
B
3 5/16"
(85mm)
3 1/2" (89mm) wallbox
depth recommended
C
A
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 4 ZONE 1 ZONE 6ZONE 5
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 4ZONE 1 ZONE 6ZONE 5
1
Can be ordered from Lutron.
Dimensions and Mounting - All Voltages Except 230V (CE)
5/16"
(8 mm)
1 15/16"
(49 mm)
4 9/16"
(116 mm)
Model
2-Zone:
OMX-3602
3-Zone:
OMX-3603
4-Zone:
OMX-3604
6-Zone:
OMX-3606
Side V
iew
A
4 5/16"
(123mm)
6 11/16”
(168mm)
8 5/16”
(208mm)
8 5/16”
(208mm)
B
1 13/16”
(46mm)
3 5/8”
(92mm)
5 7/16”
(138mm)
5 7/16”
(138mm)
C
5.56”
(141mm)
7.25”
(184mm)
8.94”
(227mm)
8.94”
(227)
W
allbox
1
U.S. Size
2 Gang
3 Gang
4 Gang
4 Gang
Depth
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-6 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
B
3 5/16"
(85mm)
C
A
F
M S
FADE TEMPORARY
MASTER
ZONES
ZONE 3
ZONE 4
ZONE 1
ZONE 2
ZONE 6ZONE 5
F
M S
FADE
TEMPORARY
MASTER
ZONES
ZONE 3
ZONE 4
ZONE 1
ZONE 2
ZONE 6ZONE 5
F
M S
FADE
TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
F
M S
FADE
TEMPORARY
MASTER
ZONES
ZONE 3 ZONE 4ZONE 1 ZONE 2 ZONE 6ZONE 5
1
Can be or
der
ed from Lutron.
Dimensions and Mounting - 230V (CE) Only
3 1/2" (89mm) wallbox depth
recommended
Model
2-Zone:
OMX-3602-CE
3-Zone:
OMX-3603-CE
4-Zone:
OMX-3604-CE
6-Zone:
OMX-3606-CE
Side View
A
8 5/16"
(208mm)
8 5/16”
(208mm)
8 5/16”
(208mm)
8 5/16”
(208mm)
B
5 7/16”
(138mm)
5 7/16”
(138mm)
5 7/16”
(138mm)
5 7/16”
(138mm)
C
8.94”
(227mm)
8.94”
(227mm)
8.94”
(227mm)
8.94”
(227mm)
Wallbox
1
U.S. Size
4 Gang
4 Gang
4 Gang
4 Gang
Depth
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
3.5”
(89mm)
4 9/16"
(116 mm)
5/16"
(8 mm)
1 15/16"
(49 mm)
6
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-7 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
• Pull power wiring from distribution panel and to light fixtures.
• Each line voltage terminal can accept up to two #12 AWG (2.5mm
2
) wires.
Consult Lutron for:
• Non-dim relay wiring.
• Load side emergency transfer wiring.
Distribution Panel
Earth/Ground from Distribution Panel
Rear View of OMX-3606 Control Unit
Hot/Live
Hot/Live
Load 1
Load 3
Load 5
Load 2
Load 4
Load 6
(2) #12 A
WG
(2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
Neutral
Neutral
Line Voltage Wiring - 120V, 100V, 220-240V Models
7
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-8 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
Consult Lutron for:
• Non-dim relay wiring.
• Load side emergency transfer wiring.
Distribution Panel
Earth/Ground from Distribution Panel
Rear View of OMX-3606 Control Unit
Hot/Live
Load 1
Load 3
Load 5
Load 2
Load 4
Load 6
(2) #12 AWG
(2.5 mm
2
)
(2) #12 A
WG (2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
Neutral from Distribution
Panel
Input Power from
Distribution Panel
Neutral
• Pull power wiring from distribution panel and to light fixtures.
• Each line voltage terminal can accept up to two #12 AWG (2.5mm
2
) wires.
• For phase-to-phase wiring, connect one phase to Hot/Live and the other phase to
Neutral. When wired phase-to-phase,
there is no air gap when the Control Unit is Off.
The MCB(s)
must be turned off when servicing the Control Unit or associated loads.
Mains Voltage Wiring - 230V CE Models
8
CLASS 2
USA
Class 2
IEC
PELV
1 2 3 4
CLASS 2
1 2 3 4
USA
Class 2
IEC
PELV
ZONE 2
ZONE 4
ZONE 6
SSA
HOT/LIVE
NEUTRAL
ZONE 1
ZONE 3
ZONE 5
CU WIRE ONLY
1 2 3 4 5
34
34
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
3600-9 01.10.06
Preset Dimming ControlsOMX-3600
GRAFIK
Systems
Low-Voltage Class 2 (PELV) Wiring
• All wiring must be daisy-chained.
• Make connections in the Control Unit’s wallbox or in a
switch/junction box with a maximum wire length of 8 feet
(2.5m) from the link to the Control Unit.
• Pigtail the #12 AWG (2.5mm
2
) conductors. Each Class 2
PELV terminal can accept only two #18 AWG (1.0mm
2
)
wires. The #12 AWG (2.5mm
2
) wires will not fit. Connect as
shown.
• Keep Shield/Drain continuous but do not
ground. Connect the bare drain wires and
cut off the outside shield. Do not connect to
Ground (Earth) or Wallstations/Control
Interfaces.
• Begin and end the wiring link with Link
Terminators.
Data Link
(1) shielded, twisted pair
#18 AWG (1.0mm2)
3: MUX
4: MUX
Link
Terminator
Control Wiring
(2) #12 AWG
(2.5mm
2
)
1: Common
2: 32VDC
Data Link
(1) shielded, twisted pair
#18 AWG (1.0mm
2
)
3: MUX
4: MUX
Ceiling Receiver
Link
Terminator
Last Wallstation/Control Interface
OMX-3606 Control Unit
(1) #18 AWG
(1.0mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
D: Drain/
Shield
9