SPECIFICATION SUBMITTAL
omxav-1 06.14.04
Control Interfaces
OMX-AV
GRAFIK Systems
OMX-AV Control Interface
Description
• Integrates GRAFIK 5000/6000/7000 Systems with
equipment that has contact-closure I/O, including:
– Motion and occupant sensors.
– Timeclocks and push buttons.
– Motorized projection screens, skylights, window shades,
and movable walls.
– AV equipment.
– Security systems.
• Use the GRAFIK Systems Processor Panel to setup the
OMX-AV Interface for different modes, functions, and
momentary/maintained inputs and outputs.
Inputs/Outputs
• Provides five inputs and five outputs.
• Using the inputs, contact closures in other
equipment can operate controls to:
– Select scenes.
– Run sequences (loop through scenes).
– Lock lighting controls to prevent changes.
– Activate panic mode (lights go full on).
– Adjust control logic to reflect status of movable walls.
– Turn lights on or off based on room occupancy.
• Using the outputs, scene changes in lighting controls can:
– Trigger outputs to control other equipment.
– Provide status feedback to other equipment.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxav-2 06.14.04
Control Interfaces
OMX-AV
GRAFIK Systems
Specifications
Power
• Low-voltage Class 2 (PELV).
Operating Voltage: 32 V Direct Current.
• Provides 2-way interface between lighting controls and dry contact closure devices.
• Provides 5 inputs and 5 outputs. Outputs can control other manufacturers’ equipment.
Operating Modes
• Scene selection
• Special functions
Partitioning
• Occupant sensor
Five Input Terminals
• Accept maintained inputs and momentary inputs with 40msec minimum pulse times.
• Inputs must be dry contact closure or open collector (NPN).
• On-state saturation voltage must be less than 2.0VDC.
• Off-state leakage current must be less than 10µA.
• Open circuit voltage: 36V maximum.
• Short circuit current: 4.0µA maximum.
Five Output Terminals
• Provide solid-state maintained or momentary (1-second) outputs.
• Outputs require an external relay and power supply (30VDC max., Class 2/PELV)
by others for contact closure devices.
• Maximum voltage: 38V
• Maximum current: 200mA
• Open collector (NPN) output: On-state saturation voltage 1.0V maximum,
off state leakage current 0.1µA maximum.
Status LEDs
Five Status LEDs light when associated output is active (on).
System Communications and Capacity
Low-voltage type Class 2 (PELV) wiring connects OMX-AV Interface to Processor Panel.
Environment
32-104°F (0-40°C). Relative humidity less than 90% non-condensing.
2
MUX LINK
INPUTS OUTPUTS
COM
+V
MUX
PROGRAM
SWITCH
COM
COM
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
MUX
MUX LINK
INPUTS OUTPUTS
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
1 2 3 4 5 6 7 8
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxav-3 06.14.04
Control Interfaces
OMX-AV
GRAFIK Systems
Front
Dimensions
Side
DIP
Switches
MUX Link to
Processor
Panel
6”
(127mm)
7 3/4”
(197mm)
2 1/2”
(84mm)
Class 2 (PELV)
Wiring
OMX-AV
4”x4”
Junction
Box
Insert Wires
Through
Punch-Outs
Wall
OMX-AV
Wall
• Mount on a 4" (10.2mm) square junction box.
• May also mount directly to the wall.
• Ensure that the metal casing is grounded. Connect a
ground wire to the ground screw.
• Note that wires do not feed through the back of the unit.
Mounting
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxav-4 06.14.04
Control Interfaces
OMX-AV
GRAFIK Systems
• Daisy-chain the OMX-AV Interface to the Class 2 (PELV)
Wallstation Link that connects to the Processor Panel.
• Make daisy-chain connections to the low-voltage Class 2 (PELV)
MUX Link terminals on front of OMX-AV Interface.
• Do not use T-taps. Run all wires in and out of the terminal block.
• Each terminal accepts up to two #18 AWG (1.0mm
2
) wires.
• Consult Processor Panel Specification Submittal for more details.
Low-Voltage Class 2 (PELV) Wiring
1 2 3 4
Inputs Outputs
MUX Link
C 1 2 3 4 5 1 2 3 4 5 C
+
V
1
2
35
4
Input 1
Input 2
Input 3
Input 4
Input 5
Output 1
Output 2
Output 3
Output 4
Output 5
Power
Supply
COM
+V
MUX
MUX
Program
Switch
To up to 31 additional Control Interfaces,
Control Units, or Wallstations
User-Supplied Equipment
To Processor Panel
OMX-AV
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxav-5 06.14.04
Control Interfaces
OMX-AV
GRAFIK Systems
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1) and 32VDC (terminal 2).
These will not fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground (Earth) or Wallstation/Control
Interfaces. Connect the bare drain wires and cut off the outside shield.
Class 2 (PELV) Terminal Connections
MUX LINK
INPUTS OUTPUTS
COM
+V
MUX
PROGRAM
SWITCH
COM
COM
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
MUX
MUX LINK
INPUTS OUTPUTS
C 1 2 3 4 5 1 2 3 4 5 C
1 2 3 4
1 2 3 4 5 6 7 8
Data Link - (1) twisted,
shielded pair #18 AWG
(1.0mm
2
)
3: MUX
4: MUX
Class 2/PELV
Control wiring
1: Common
2: 32VDC
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(1) #18 AWG
(1.0mm
2
)
OMX-AV
5