SPECIFICATION SUBMITTAL
omx-wci-1 06.01.04
Control Interfaces
OMX-WCI
GRAFIK Systems
OMX-WCI
Wallbox Closure Input Interface
Description
• The OMX-WCI provides 7 control inputs to the
Lutron Lighting Control System.
• The control inputs can be set up to simulate
existing Lutron keypad functionality or custom
configured to project-specific requirements.
• The OMX-WCI mounts behind the user-supplied
switch to control the Lutron Lighting Control
System.
• Works with a PELV (Class 2), low-voltage, dry
contact switch that meets the Power
requirements found in the Specifications section
of this document.
• The power LED provides feedback:
— Lit dimly under normal operation
— Flashing indicates communication miswire
• The recommended wallbox depth is 61mm. The
wallbox depth requirements vary with the depth
of the switch in use.
• The OMX-WCI uses one address on the
Communication Link.
• Can be custom-configured for other functions.
• The OMX-WCI is not designed to work with
line/mains voltage switches.
Addressing Switches
Power LED
Input Wiring Harness
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omx-wci-2 06.01.04
Control Interfaces
OMX-WCI
GRAFIK Systems
Power
• Low-voltage PELV (Class 2)
Operating voltage: 32 VDC.
• Provides 1-way input interface between GRAFIK Lighting
Control Systems and a switch provided by others.
• If using a mechanical switch, it must be a low-voltage, dry
contact closure rated switch.
• If using a solid-state input switch, it must have an on-state
saturation voltage less than 1VDC at 1mA and an off-state
leakage current of less than 1 mA.
• Use with line/mains voltage switches could result in premature
failure of the switch being used.
• If there is any question as to whether a switch is compatible
with these specifications, contact the manufacturer of the
switch.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV electrostatic
discharge without damage or memory loss.
System Communications and Capacity
• Low-voltage PELV (Class 2) wiring connects OMX-WCI to
Control Units and other components.
• Up to 32 Wallstations, Control Units, and/or Control Interfaces
may be connected on a PELV (Class 2) Communication Link.
Terminals
Accept up to two 1.0mm
2
(#18 AWG) typical.
Environment
0-40°C (32-104°F). Relative humidity less than 90% non-
condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omx-wci-3 06.01.04
Control Interfaces
OMX-WCI
GRAFIK Systems
Dimensions and Mounting
Wallbox
OMX-WCI
Low-Voltage
Contact
Closure Switch
Provided by
Others
Communication
Link Wiring
4321
Side View
Back View
20mm (13/16”)
59mm
(2-5/16”)
59mm
(2-5/16”)
119mm
(4-11/16”)
Data
Data
Power
Common
Front View
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omx-wci-4 06.01.04
Control Interfaces
OMX-WCI
GRAFIK Systems
4321
(2) 1.0 mm
2
(#18 AWG)
twisted, shielded pair
from terminals 3 to 3,
and 4 to 4
1.0 mm
2
(#18 AWG)
(2) 2.5 mm
2
(#12 AWG)
Addressing
• Set Address Switches 1-5 to give the OMX-WCI the
unique system address from 1 to 32.
Low-Voltage PELV (Class 2) Wiring
• Use low-voltage PELV (Class 2) wiring to daisy-
chain OMX-WCI to the Processor Panel.
• Lutron recommends that all connections be made
in the wallbox.
If a remote connection (T-tap) must be made, the
maximum wire length from the communication link
to the connected unit must be 2.5m (8 ft.).
Two 2.5mm
2
(#12 AWG) conductors for common
(terminal 1) and 24VDC (terminal 2). Connect as
shown below.
One shielded, twisted pair #1.0mm
2
(#18 AWG)
for data (terminals 3 and 4).
Connect Drain as shown.
- Do not connect to Ground (Earth) or Wallstation.
- Connect the drain and cut off the outside shield.
Drain Wires
Note: Use appropriate wire connecting
devices as specified by local codes.
Installation
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
26
27
28
25
30
31
32
29
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
18
19
20
17
22
23
24
21
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
10
11
12
9
14
15
16
13
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
12345
ON
2
3
4
1
6
7
8
5
Address
Switch Setting
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omx-wci-5 06.01.04
Control Interfaces
OMX-WCI
GRAFIK Systems
Contact Closure Wiring
• Connect the desired input(s) and common wire(s) to the switch(es)
provided by others.
• Ensure proper function then cap or cut off unused input wires.
Input 1
Common
Switch
Input 7
Switch
All switch
closure inputs
must share the
same common.
5