SPECIFICATION SUBMITTAL
369371 Rev. B 2 06.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
Specifications
Power
•IECPELV/NEC® Class 2
•Operatingvoltage:12V 200 mA
24 V 100 mA
•Provides2-wayinterfacebetweenlighting
controls and dry contact closure devices.
•Provides5inputsand5outputs.Outputscan
control other manufacturers’ equipment.
Status LEDs
Five Status LEDs light when associated output is
active(on).
System Communications and Capacity
IEC PELV/NEC® Class 2 wiring connects OMX-IO
interface to processor panel.
Environment
32to104°F(0to40°C).Relativehumidityless
than 90% non-condensing.
Five Input Terminals
•Acceptmaintainedinputsandmomentaryinputs
with 40 msec minimum pulse times.
•Off-stateleakagecurrentmustbelessthan
100 µA.
•Opencircuitvoltage:24V maximum.
•Inputsmustbedrycontactclosure,solidstate,
opencollector,oractive-low(NPN)/activehigh
(PNP)output.
- Open collector NPN or active-low on-state
voltage must be less than 2 V and sink
3.0 mA.
- Open collector PNP or active-high on-state
voltage must be greater than 12 V and
source 3.0 mA.
Five Output Terminals
•Providemaintainedormomentary(1-second)
outputs.
•TheOMX-IOisnotratedtocontrolunclamped,
inductive loads. Inductive loads include, but are
not limited to, relays, solenoids, and motors. To
control these types of equipment, a flyback diode
mustbeused(DCvoltagesonly).Seediagram
below.
+
-
DC
Inductive
Load
Flyback
Diode
OMX-IO Output
Supply
Voltage
0-24 V
0-24 V
Resistive
Load
1.0 A
0.5A
R