SPECIFICATION SUBMITTAL
369371 Rev. B 1 06.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
OMX-IO Control Interface
Description
•IntegratesGRAFIK5000TM, GRAFIK 6000®, GRAFIK
7000TM, LCP128®, and Softswitch128® systems with
equipment that has a contact-closure I/O, including:
Motion and occupant sensors.
Timeclocks and push buttons.
Motorized projection screens, skylights, window
shades, and movable walls.
AV equipment.
Security systems.
•UsetheGRAFIKSystemsTM processor panel to set up
the OMX-IO interface for different modes, functions,
and momentary/maintained inputs and outputs.
Inputs/Outputs
•Providesfiveinputsandfiveoutputs.
•Providesbothnormallyopen(NO)andnormallyclosed
(NC)contacts.
•Usingtheinputs,contactclosuresinother
equipment can operate controls to:
Select scenes.
–Runsequences(loopthroughscenes).
Lock lighting controls to prevent changes.
–Activatepanicmode(lightsgofullon).
Adjust control logic to reflect status of movable walls.
Turn lights on or off based on room occupancy.
•Usingtheoutputs,scenechangesinlightingcontrols
can:
Trigger outputs to control other equipment.
Provide status feedback to other equipment.
1
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369371 Rev. B 2 06.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
Specifications
Power
•IECPELV/NEC® Class 2
•Operatingvoltage:12V 200 mA
24 V 100 mA
•Provides2-wayinterfacebetweenlighting
controls and dry contact closure devices.
•Provides5inputsand5outputs.Outputscan
control other manufacturers’ equipment.
Status LEDs
Five Status LEDs light when associated output is
active(on).
System Communications and Capacity
IEC PELV/NEC® Class 2 wiring connects OMX-IO
interface to processor panel.
Environment
32to104°F(0to40°C).Relativehumidityless
than 90% non-condensing.
Five Input Terminals
•Acceptmaintainedinputsandmomentaryinputs
with 40 msec minimum pulse times.
•Off-stateleakagecurrentmustbelessthan
100 µA.
•Opencircuitvoltage:24V maximum.
•Inputsmustbedrycontactclosure,solidstate,
opencollector,oractive-low(NPN)/activehigh
(PNP)output.
- Open collector NPN or active-low on-state
voltage must be less than 2 V and sink
3.0 mA.
- Open collector PNP or active-high on-state
voltage must be greater than 12 V and
source 3.0 mA.
Five Output Terminals
•Providemaintainedormomentary(1-second)
outputs.
•TheOMX-IOisnotratedtocontrolunclamped,
inductive loads. Inductive loads include, but are
not limited to, relays, solenoids, and motors. To
control these types of equipment, a flyback diode
mustbeused(DCvoltagesonly).Seediagram
below.
+
-
DC
Inductive
Load
Flyback
Diode
OMX-IO Output
Supply
Voltage
0-24 V
0-24 V
Resistive
Load
1.0 A
0.5A
R
2
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369371 Rev. B 3 06.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
Dimensions
2.47 in
(62.7 mm)
3.75 in
(95.3 mm)
4.26 in
(108.2 mm)
5.26 in
(133.6 mm)
1.06 in
(26.9 mm)
Mounting holes
Mounting
1. Mount the control interface directly on a wall, as
shown in the Mounting Diagram, using screws (not
included). When mounting, provide sufficient space
for connecting cables.
The unit can also be placed in the LUT-19AV-1U AV
rack using the screws provided with the unit. The
LUT-19AV-1U will hold up to four units.
If conduit is desired for wiring, the LUT-5x10-ENC
can be used to mount one unit.
2. Strip 4 in (10 mm) of insulation from wires. Each data
link terminal will accept up to two 18 AWG
(1.0 mm
2
) wires.
3. Connect wiring as shown in the Wiring Diagram
(next page). LED 1 lights continuously (Power) and
LED 7 blinks rapidly (Data Link RX) when the Class 2
(PELV) Data Link is installed correctly.
LUT-19AV-1U
Wire Strip Length
4 in
(10 mm)
5.26
4.263.75
2.50
1.06
Control Interface
Wall
Mounting Diagram
LUT-5x10-ENC
0.25
(6.4)
0.34 (8.6)
dia.
0.18 (4.6)
dia.
0.18 (4.6)
dia.
#6 or #8 (M3 or M4)
screw recommended
(not included)
Mounting Hole Detail
DImensions: in (mm)
3
1 2 3 4 5 6 7
4 3 2 1
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369371 Rev. B 4 06.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
•Daisy-chaintheOMX-IOInterfacetotheIECPELV/NEC® Class 2 wallstation link that
connects to the processor panel.
•Makedaisy-chainconnectionstotheIECPELV/NEC® Class 2 MUX Link terminals on
front of OMX-IO interface.
•DonotuseT-taps.Runallwiresinandoutoftheterminalblock.
•Eachterminalacceptsuptotwo18AWG(1.0mm
2
)wires.
•ConsultProcessorPanelSpecificationSubmittalformoredetails.
IEC PELV/NEC® Class 2 Wiring
To up to 31 additional control
interfaces, control units, or wallstations
OMX-IO
Not used
DIP switches
LED 1: Relay 1 status
LED 2: Relay 2 status
LED 3: Relay 3 status
LED 4: Relay 4 status
LED 5: Relay 5 status
LED 6: Unused
LED 7: Link status
1 2 3 4 5 6 7
Connectorsholdone28to16AWG
(0.08to1.5mm
2
)wire
Data Link (to control
units, processors, and
wallstations)
4: MUX
3: MUX
2: 24 V
1: Common
CCO 1 NC
CCO 1 NO
1-2 COM
CCO 2 NC
CCO 2 NO
CCO 3 NC
CCO 3 NO
3-4 COM
CCO 4 NC
CCO 4 NO
CCO 5 NC
CCO 5 NO
5 COM
CCI 1
CCI 2
CCI 3
CCI 4
CCI 5
COM
4
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369371Rev.B506.02.11
Control Interfaces
OMX-IO
GRAFIK SystemsTM
IEC PELV/NEC® Class 2 Terminal Connections
• Install in accordance with all applicable regulations.
• Do not connect line voltage/mains power to device.
• This control can use IEC PELV/NEC® Class 2 wiring methods. Check with your local electrical inspector for
compliance with national and local codes and wiring practices.
• Makedaisy-chainconnectionstotheIEC PELV/NEC® Class 2 data link terminals on the end of the control interface.
• DonotuseT-taps.Runallwiresinandoutoftheterminalblock.
• Eachterminalacceptsuptotwo18AWG(1.0mm
2
) wires.
IEC PELV/NEC® Class 2
Power wiring:
1: Common
2: 24 V Power
(2)18AWG(1.0mm
2
) pigtails,
6 in (152 mm) maximum length
D: Drain/Shield
(2)12AWG
(2.5 mm
2
)
(2)12AWG
(2.5 mm
2
)
Data Link: (1) shielded, twisted
pair18AWG(1.0mm
2
)
4: MUX
3: MUX
Note: 12AWG(2.5mm
2
) conductors for
Common (terminal 1) and 24 V Power (terminal
2)willnotfitinterminals;use18AWG(1.0mm
2
)
pigtails (< 6 in/152 mm).
Note: DonotconnectDrain/ShieldtoGround
(Earth)orWallstation/ControlInterfaces.Connect
the bare drain wires and cut off the outside
shield.
Use Lutron Cable
GRX-CBL-46L
5