R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxwstns-1 03.08.04
Wallstations
Architectural Style
GRAFIK Systems
NTOMX-2B-__-_
2-Button Wallstation
Description
• Often used in entryways to select Scene 1 and Off.
• Recalls preset light levels for two scenes.
• Reflects door status of one or two partitions.
• Enables or disables Wallstations.
• Starts or stops one sequence.
• Enables or disables timeclock/security override
Scene 1.
• Allows fine-tuning of zones.
• May be custom-configured for other functions.
• Works with GRAFIK 5000/6000/7000 Systems.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Green LEDs are standard. Amber LEDs are
optional.
Status LED
Status LED
Color and Finish Codes
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxwstns-7 03.08.04
Wallstations
Architectural Style
GRAFIK Systems
2 3/4"
(70mm)
5/16"
(8mm)
1 3/8"
(35mm)
4 9/16"
(116mm)
1234567
4
3
2
1
Color and Finish Codes
Matte Finishes
Standard – Ship in 48 hours
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
No Insert NI
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finishes.
Dimensions
Front View
Mounting
Power
Low-voltage type Class 2 (PELV).
Operating voltage: 32 V Direct Current.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
• Can be ganged to share a common faceplate
with NovaT* and Vareo Dimmers. Counts as a
“small control” for ganging.
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Processor Panel.
• Up to 32 Wallstations, Control Units, and/or
Control Interfaces may be connected per Class
2 (PELV) wiring link.
Terminals
Accept up to two #18 AWG (1.0mm
2
) typical.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Side View
Back View
Do not change
DIP Switches.
Lutron sets them
at the factory.
Terminals for
Class 2
(PELV) wiring
Class 2 (PELV)
wiring
1-Gang U.S.
Wallbox
Faceplate
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
omxwstns-8 03.08.04
Wallstations
Architectural Style
GRAFIK Systems
Low-voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain Wallstations
to the Processor Panel.
• Make connections inside the wallbox or in a switch/junction box
with a maximum wire length of 8 feet (2.5m) from the link to the
Wallstation.
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1) and
32VDC (terminal 2). These will not fit in terminals. Connect as
shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground
(Earth) or Wallstation. Connect the bare drain wires and cut
off the outside shield.
Note: Some Wallstations have a “D” terminal for Drain. The
Drain/Shield wire may be connected to this terminal.
Wallstation Rear View
Wallstation Installation
Note: Use appropriate wire connecting devices
as specified by local codes.
123456
4
3
2
1
Data Link
(1) Shielded, twisted
pair #18 AWG (1.0mm
2
)
3: MUX
4: MUX
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
Class 2/PELV
Control Wiring
1: Common
2: 32VDC
3