SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for QuantumR Subsystem Main Devices
using Quantum
R Version 2.6
Software
License
QuantumR
369695a 3 08.12.13
Object Name Type Instance Read Write COV Units Min
PV
Max PV Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
{SystemName}
{Instance}
DEVICE {Base} +
{System}
+ 1
X — — — — — — — — The System Name is the logical name
of one of the Quantum
R system’s
subsystems that typically corresponds
to a physical portion of the building
such as a floor. The Instance is the
same as the unique Device ID assigned
to each subsystem.
Master Loadshed
Enabled
BV 2 X X X — 0 1 Disabled Enabled — This value determines whether all of
the areas in the Quantum
R subsystem
are being controlled via load shedding.
When this value is set to Enabled, for all
areas in the subsystem that have
loadshed allowed, any dimmable lights
in each area that are turned on will
have their light level reduced by the
percentage specified in the Loadshed
Goal value. When Disabled, the lights
will dim to their commanded level.
Master
HyperionT
Enabled
BV 3 X X — — 0 1 Disabled Enabled — When the Master HyperionT Enabled
feature is set to Enabled, for all Areas in
the Quantum
R subsystem that have
HyperionT configured, the HyperionT
feature will control the LutronR SivoiaR
QS roller shades and set their level
automatically depending on the position
of the sun. When the Master HyperionT
feature is set to Disabled, in all areas of
the subsystem, the shades will not be
controlled automatically by the
HyperionT feature.
Roof-Mount
Cloudy Day
Sensor:
Subsystem
Status
BV 4 X X — — 0 1 Dark Sunny — A Lutron
® roof-mounted, wired Cloudy
Day Sensor or a BMS system sensor is
used to override all HyperionT
controlled shades in the subsystem.
Sunny indicates that the HyperionT
feature is in control of the shades; Dark
indicates that the shades are
overridden to open. This feature is
independent of the Radio Window
Sensor feature.
(continued on next page)
BV = Binary-Value
{SystemName} is a text string defined in the Lutron
R QuantumR system configuration software
{Instance} is a number defined in the LutronR QuantumR system configuration software that is equal to the {Base} number + {System} number +1
{Base} is a 22-bit value set in the LutronR QuantumR system configuration software (default 1760000)
{System} is an 8-bit value set in the LutronR QuantumR system configuration software (0 to 127)
PV = Present-Value