SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® Dimming Module Energi TriPak® Series Wireless Lighting Control
369779c 2 08.19.16
Specifications
Regulatory Approvals
RMJ- and URMJ- models only
• UL
® Listed
• FCC approved. Complies with the limits for a Class B
device, pursuant to Part15 of the FCC rules
• Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
• Listed in accordance to CAN/ULC S102.2-2010 with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
• cUL
® and IC (Canada)
• COFETEL (Mexico) (RMJ- models only)
• NOM (Mexico) (RMJ- models only)
RMN- model
• WPC Type Approved (India)
RMK- model
• CE (European Union)
• TRA Type Approved (United Arab Emirates)
RMP- model
• PSE certified (Japan)
Power
• Operating voltage
– RMJ-, URMJ- models: 120 / 277V~ 50/60Hz
– RMQ- model: 110 –127 / 220 – 240V~ 50/60Hz
– RMM- model: 220 –240V~ 50/60Hz
– RMK- model: 220 –240V~ 50/60 Hz
– RMN- model: 220 –240V~ 50/60 Hz
– RMP- model: 100 –200V~ 50/60Hz
Output Ratings
• Switch rating of 5 AX. Rated for resistive or capacitive
loads as defined by IEC/EN 60669-2-1
• 0 –10 V- control link for 60 mA maximum output,
source or sink automatically configures
Other Power Specifications
• Standby power:
– 240 – 277 V~ 610 mW
– 120 V~ 550 mW
• BTU/hour when fully loaded: 9
• Works with all ballasts and drivers that provide a
current source that is compliant to IEC 60629 Annex
E.2, and whose inrush current does not exceed
NEMA410 standards for electronic ballast/driver
System Communication
• Operates using Clear Connect
® RF Technology for
reliable wireless communication; refer to model
number chart on page 1 for frequency band details
• RF range is 30ft (9m)
Environment
• Ambient operating temperature: 32°F to 104°F (0°C
to 40°C)
• 0% to 90% humidity, non-condensing
• For indoor use only
0 –10 V- Control Link
• Communicates with up to 60 mA of fixtures
• Control link is IEC SELV/NEC
® Class 2
• 0 –10V- control can be installed using NEC
® Class1
or Class2 wiring methods. Alternately, it can be wired
to basic or double-insulated devices
• Terminals accept one 18 to 16AWG
(0.75 to 1.5mm
2
) solid wire
• Always consult local wiring codes
• Compatible with ANSI E1.3 2001 (R2006), IEC 60929
Annex E