369776a 1 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi TriPakR Basic Packages
The Energi TriPakR Basic Package incorporates
Maestro
R load controls and wireless sensors which
provides a system that delivers energy savings,
convenience, and ease of installation.
Maestro Wireless
R switches use LutronR patented
Clear Connect
R RF Technology, which enables
wireless communication with Radio Powr SavrT
sensors for light control.
Features
• The Energi TriPak
R Basic package provides switching
and occupancy/vacancy sensing of multiple load
types.
• Lutron
R patented Clear ConnectR RF Technology
works through walls and floors.
• Controls include Front Accessible Service Switch
(FASST) for safe lamp replacement.
• Two-wire installation for any retrofit application.
• Power failure memory: If power is interrupted, the
control will return to its previously set level prior to
interruption.
Receiving Devices
Maestro WirelessR Control
Transmitting Devices
Radio Powr SavrT Sensors
RF Switch
Ceiling-Mounted Occupancy
and Vacancy Sensor
Wall, Corner, or
Hall Mounted
Occupancy and
Vacancy Sensor
Model Numbers
MRF2-1S8A-1OC (1) 8 A Switch
(1) Radio Powr SavrT ceiling sensor
MRF2-1S8A-1OH (1) 8 A Switch
(1) Radio Powr SavrT hallway sensor
MRF2-1S8A-1OK (1) 8 A Switch
(1) Radio Powr SavrT corner sensor
MRF2-1S8A-1OW (1) 8 A Switch
(1) Radio Powr SavrT wall sensor
MRF2-1S8A-1VC (1) 8 A Switch
(1) Radio Powr SavrT ceiling
vacancy sensor
MRF2-2S8A-1OW (2) 8 A Switches
(1) Radio Powr SavrT wall sensor
1
369776a 2 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro WirelessR Switch
Model Number
Switch
Lighting and motor loads
MRF2-8S-DV-XX 8 A Lighting, 3 A Fan (1/10 HP
motor, 120 V~ only), Spec
Grade Electronic Switch
120–277 V~, NO NEUTRAL
WIRE REQUIRED
Companion Controls
ClaroR Gloss Finishes
MA-AS-XX Companion Switch 120 V~
MA-AS-277-XX Companion Switch 277 V~
Satin ColorsR Satin Finishes
MSC-AS-XX Companion Switch 120 V~
MSC-AS-277-XX Companion Switch 277 V~
“XX” in the model number represents color/finish code.
Switch
Companion Switch
Switch Load Type and Capacity
No Neutral Required
Control Voltage Load Type Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2-8S-DV
1,2
120–277 V~
Incandescent/
Halogen
25 W 8 A 8 A / 7 A
3
7 A
120–277 V~
Fluorescent/
LED/CFL
40 W
(LUT-MLC)
4
8 A 8 A / 7 A
3
7 A
120 V~
Fan
Motor
0.4 A
1/10 HP
3 A
1/10 HP
3 A
1/10 HP
3 A
1
Switch Load Type: MRF2-8S-DV is designed for use with permanently installed lighting loads and with fan motor loads up to 1/10 HP (3 A, 120 V~ only).
2
Switch Load Type: MRF2-8S-DV are designed for use with permanently installed lighting loads.
3
Maximum load for double gang application is 8 A. Triple gang application derates maximum load to 7 A.
4
The LUT-MLC (included) ensures proper function with certain fluorescent, CFL, and LED load types.
MRF2-8S-DV-XX MA-AS-XX
2
369776a 3 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals
• ULR Listed.
• CSA Certified.
• FCC Approved. Complies with the limits for a
Class B digital device, pursuant to Part 15 of the
FCC Rules.
• Industry Canada Certified.
Power
Operating voltage:
120 – 277 V~ 50/60 Hz
Key Design Features
Switch
• On a single-tap, lights turn ON or OFF.
All RF Local Controls
• Tested to withstand electrostatic discharge without
damage or memory loss, in accordance with IEC
61000-4-2.
• Tested to withstand surge voltages without damage
or loss of operation, in accordance with IEEE
C62.41-1991 Recommended Practice on Surge
Voltages in Low-Voltage AC Power Circuits.
• Controls always operate locally and do not require
system control.
• Power failure memory: should power be interrupted,
the control will return to its previously set level prior
to the interruption when power is restored.
• Uses conventional Single-pole, 3-way and 4-way
wiring.
• Multiple location control from Switch and up to 9
Companion Switches.
• Use LutronR Designer (ClaroR and Satin ColorsR)
wallplates or designer-style wallplates from other
manufacturers. Wallplates are sold separately.
• Lutron ClaroR
and Satin ColorsR wallplates snap on
with no visible means of attachment.
• Requires a 1-gang U.S. wallbox. 3
1
2 in (89 mm) deep
recommended, 2
1
4 in (57 mm) deep minimum.
• Green indicator light.
System Communications and Capacity
• Maestro WirelessR controls communicate with the
PicoR wireless controls and Radio Power SavrT
sensors through radio frequency (RF).
• Maestro WirelessR local controls must be located
within 60 ft (18 m) line of sight or 30 ft (9 m)
through walls, of Radio Power SavrT sensors.
• Maestro WirelessR local controls must be located
within 60 ft (18 m) line of sight or 30 ft (9 m)
through walls, of a Pico
R wireless control.
• Up to 10 sensors or PicoR wireless controls can
be assigned to each switch.
• Sensors can be assigned to multiple switches.
Environment
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%-90% humidity, non-
condensing. Indoor use only.
3
369776a 4 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
Wallbox
Control
Adapter
Mounting
Screws
Control
Mounting
Screws
Wallplate / Adapter purchased
separately.
Operation
IMPORTANT NOTICE:
FASST - Front Accessible Service Switch - to service load, remove power by pulling the FASST switch out
completely on either the Switch or Companion Switch. After servicing load, push the FASST switch back in fully to
restore power to the control.
Tapswitch
Tap on / off
FASST
Front
Accessible
Service
Switch
Switch
Status LED
Indicates load status; glows softly as
night light when light is off
Dimensions
Front View
Side View
5/16 in
(8 mm)
1
1
8 in
(30 mm)
4
11
16 in
(119 mm)
2
15
16 in
(75 mm)
4
369776a 5 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Single Location Installation
MRF2-8S-DV
Brass
Black
Blue - unused, tighten
1
Optional
Green
Ground
Hot/Live
Neutral
Switch
Switch
Wiring Diagrams
Multi-Location Installation
2
MRF2-8S-DV
3
with MA-AS / MA-AS-277 or MSC-AS / MSC-AS-277
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Companion Switch Companion Switch
Load
Load
120 V277 V~ 50/60 Hz
120 V277 V~ 50/60 Hz
LUT-MLC*
1
When using controls in single location installations, tighten the blue terminal without any wires attached. DO NOT connect the blue terminal to any other wiring or
to ground.
2
Up to 9 MaestroR Companion Switches may be connected to the Maestro WirelessR Switch. Total blue terminal wire length may be up to 250 ft (76 m).
3
Requires MA-AS / MSC-AS for 120 V~ applications, and MA-AS-277 / MSC-AS-277 for 277 V~ applications.
Optional
*
A LUT-MLC ensures proper function when fl uorescent, CFL, or LED
loads are used. Install the LUT-MLC inside a load fixture or in a
separate J-box of the circuit.
LUT-MLC*
5
369776a 6 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Colors and Finishes
Gloss Finishes Satin Finishes
Metal Finish
(wallplate only)
Stainless Steel
SS
Taupe
TP
Turquoise
TQ
Plum
PL
Merlot
MR
Terracotta
TC
Sienna
SI
Midnight
MN
Hot
HT
Desert Stone
DS
Due to printing limitations, colors
and fi nishes shown cannot be
guaranteed to perfectly match
actual product colors.
Eggshell
ES
Biscuit
BI
Snow
SW
Palladium
PD
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Stone
ST
Limestone
LS
White
WH
Ivory
IV
Almond
AL
Light
Almond
LA
Gray
GR
Brown
BR
Black
BL
When using Stainless Steel wallplates, it
is recommended to order the controls in
Black (BL) or Midnight (MN).
6
369776a 7 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr SavrT Wireless
Occupancy / Vacancy Ceiling Sensor
LutronR Radio Powr SavrT occupancy/vacancy sensors
are wireless, battery-powered passive infrared (PIR)
sensors that automatically control lights via RF
communication to compatible dimming and switching
devices. These sensors detect the heat from people
moving within an area to determine when the space is
occupied. The sensors then wirelessly transmit the
appropriate commands to the associated dimming and
switching devices to turn the lights on or
off automatically. They combine both convenience and
exceptional energy savings potential along with ease
of installation.
Features
Wireless occupancy sensor has 3 settings available:
Auto-On/Auto-Off, Auto-On Low-Light/Auto-Off, and
Manual-On/Auto-Off
Auto-On Low-Light feature will only turn lights on
automatically if there is less than approximately 10 Lux
(1 fc) of ambient light
Vacancy only model available to meet California (U.S.A.) Title
24 requirements
Uses Clear Connect
R technology
Passive infrared motion detection with exclusive LutronR
XCTTM Technology for fi ne motion detection
360˚ coverage ranges from 324 ft
2
(30.2 m
2
) to 676 ft
2
(62.4 m
2
), depending on mounting height. See range
diagrams for more details.
Simple and intuitive adjustments available for Timeout,
Auto-On, and Activity settings
Supports advanced occupancy features, such as
dependent occupancy groups and customizable
occupied/unoccupied presets in some systems
Multiple sensors can be added for extended coverage
refer to product specifi cation submittal of receiving device
to determine system limits
Lens illuminates during test mode to verify ideal locations
Multiple ceiling-mount methods available for different
ceiling materials
Front accessible test buttons make programming easy
10-year battery life design
• RoHS compliant
7
369776a 8 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifi cations
Regulatory
• LutronR Quality Systems Registered to ISO 9001:2008
Standards Approved
• FCC certifi ed
• IC certifi ed
Meets CA (U.S.A.) Energy Commission Title 24
requirements
• COFETEL
• ANATEL
• SUTEL
Power/Performance
Operating voltage: 3 V -
Operating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life
Non-volatile memory (saved changes are stored during
power loss)
Environment
Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
For indoor use only
Range
Local load controls must be located within 60 ft (18 m)
line of sight, or 30 ft (9 m), through walls, of a sensor.
Sensor Coverage Test
Front accessible test button
Lens illuminates orange in response to motion during test
mode and is visible from 60 ft (18 m)
Wireless Communication Test
Front accessible test button
Turn associated loads on and off
Timeout Options
1 minute *
• 5 minutes
15 minutes – default setting
• 30 minutes
Auto-On Options (Occupancy Versions Only)
“Enabled” – Sensor turns lights ON and OFF
automatically – default setting.
“Low Light” – Sensor turns lights ON automatically only
in low ambient light conditions. Sensor turns lights OFF
automatically.
“Disabled” ** – Lights must be turned ON manually from
dimming or switching device. Sensor turns lights OFF
automatically.
Activity Options
Low Activity ( ) – default setting
Medium Activity ( )
High Activity (
)
* Intended for use in high-activity, brie y occupied areas only
** There is a 15-second grace period that begins when the lights are
automatically turned off, during which the lights will automatically turn
back on in response to motion. This grace period is provided as a safety
and convenience feature in the event the lights turn off while the room is
still occupied, so that the user does not need to manually turn the lights
back on. After 15 seconds, the grace period expires and the lights must
be manually turned on.
8
369776a 9 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Installation Overview
Sensor Setup
Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning service document
(LutronR P/N 3601235).
Sensor Placement
The ability of the sensor to detect motion requires line of sight of room occupants. The sensor must have an unobstructed
view of the room.
DO NOT mount behind or near tall cabinets, shelves, hanging fi xtures, ceiling fans, etc. The sensor cannot
see through glass objects such as patio or shower doors.
Hot objects and moving air currents can affect the performance of the sensor. To ensure proper operation, the sensor should
be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs that are below the ceiling line.
The performance of the sensor depends on a temperature differential between the ambient room temperature and that of
room occupants. Warmer rooms may reduce the ability of the sensor to detect occupants.
Mounting
Temporary mounting is optional to test sensor coverage and wireless communication before permanently installing the sensor.
Drop Ceiling (Compressed Fiber Ceiling Tile)
The mounting wire is provided for both temporary and permanent mounting of the sensor to ceiling tiles. It is designed to
allow temporary mounting, testing, and repositioning (if necessary) of the sensor without damaging a ceiling tile. Once the
nal position of the sensor has been chosen, the mounting wire should be twisted together to permanently secure the
sensor in place.
Solid Ceiling (Drywall, Plaster, Concrete, or Wood)
Temporary mounting: Ten (10) temporary mounting strips can be purchased in the kit L-CMDPIRKIT for temporarily mounting
and testing the sensor.
Permanent mounting: Screws and anchors (for drywall or plaster) provided to mount the sensor.
Recess Mount
• Do not recess mount sensor in a metal surface.
• Recess mounting ring requires an opening of 3 in (76 mm) in diameter.
• Recess mounting ring secures internally to ceiling. Sensor twists into
the recess mounting ring and sits fl ush with ceiling (see image to right).
• Recess mounting ring purchased as a separate kit: L-CRMK-WH.
9
369776a 10 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
3.57 in
(90.7 mm)
2.85 in
(72.4 mm)
1.13 in
(28.7 mm)
0.40 in *
(10.2 mm)
0.60 in
(15.2 mm)
1.00 in
(25.4 mm)
* With the recess mounting kit 0.46 (11.7 mm) is below the plane of the ceiling.
10
369776a 11 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* 12 ft (3.7 m) is the recommended maximum mounting height
Range Diagrams
8 ft
(2.4 m)
Ceiling
height
9 ft
(2.7 m)
9 ft
(2.7 m)
0 ft
(0 m)
12 ft
(3.7 m)
6 ft
(1.8 m)
3 ft
(0.9 m)
15 ft
(4.6 m)
15 ft
(4.6 m)
3 ft
(0.9 m)
6 ft
(1.8 m)
12 ft
(3.7 m)
Radius of Coverage at Floor
Sensor
Floor
Ceiling
Occupant
18 ft x 18 ft (5.5 m x 5.5 m) Maximum
room dimensions for complete coverage
when mounted on an 8 ft (2.4 m) ceiling
13 ft (4.0 m) Radius of coverage at fl oor
when mounted on an 8 ft (2.4 m) ceiling
Sensor Coverage Chart (for sensor mounted in center of room)
Ceiling Height Maximum Room Dimensions for Complete Floor
Coverage*
8 ft (2.4 m) 18 ft x 18 ft (5.5 m × 5.5 m) 324 ft
2
(30.2 m
2
)
9 ft (2.7 m) 20 ft x 20 ft (6.1 m × 6.1 m) 400 ft
2
(37.2 m
2
)
10 ft (3.0 m) 22 ft x 22 ft (6.7 m × 6.7 m) 484 ft
2
(44.9 m
2
)
12 ft (3.7 m) 26 ft x 26 ft (7.9 m × 7.9 m) 676 ft
2
(62.4 m
2
)
11
369776a 12 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lens Masking
Whenever possible, the sensor should be installed in a location where it cannot view areas outside the intended space,
such as hallways or adjacent rooms. If this situation cannot be avoided, portions of the lens may be masked to block the
view of the sensor into undesired areas. Ten (10) PIR Lens Masks can be purchased in the kit L-CMDPIRKIT.
Lens sections
shown in white are
masked with labels
Lens sections
shown in gray
have not been
masked
PIR Lens Mask
sold separately
(L-CMDPIRKIT)
Hallway falls
within Sensors
coverage area.
12
369776a 13 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wireless Wall-Mount Sensor
LutronR wall-mounted occupancy and vacancy sensors are
wireless battery-powered passive infrared (PIR) sensors that
automatically control lights via RF communication to
compatible dimming or switching devices. These sensors
detect the heat from people moving within an area to
determine when the space is occupied. The sensors then
wirelessly transmit the appropriate commands to the
associated dimming or switching devices to turn the lights on
or off automatically. They combine both convenience and
exceptional energy savings along with ease of installation.
Features
Wireless occupancy/vacancy sensor has 2 settings available:
Auto-On/Auto-Off, and Manual-On/Auto-Off
Vacancy model meets California Title 24 requirements
Passive infrared motion detection with exclusive LutronR XCTT
Technology for fi ne motion detection
180˚ fi eld of view model:
Minor motion = 1500 ft
2
(139.4 m
2
)
Major motion = 3000 ft
2
(278.7 m
2
)
90˚ fi eld of view model:
Minor motion = 1225 ft
2
(113.8 m
2
)
Major motion = 2500 ft
2
(232.3 m
2
)
Hallway model with long, narrow fi eld of view:
Major motion = coverage of up to 150 ft (45.7 m)
Simple and intuitive adjustments available for Timeout, Activity,
and Auto-On settings
Accessible test buttons make setup easy
Lens illuminates during test mode to verify ideal locations
Multiple sensors can be added for extended coveragerefer to
product specifi cation submittal of receiving device to determine
system limits
10-year battery life design
• RoHS compliant
Compatible RF Devices
For use with LutronR products only
Communicates to various wireless LutronR Clear ConnectR
systems*
* Contact Lutron Customer Service at www.lutron.com for
frequency/channel code compatibility with your particular
geographic region, and for integrating with other LutronR
lighting and shading products.
13
369776a 14 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifi cations
Regulatory
Lutron Quality Systems Registered to
ISO 9001:2008
Regulatory Approvals
• cULus Listed
• FCC certifi ed
• IC certifi ed
• COFETEL certifi ed
• ANATEL certifi ed
• SUTEL certifi ed
Meets CA (U.S.A.) Energy Commission Title 24
requirements
Power/Performance
Operating voltage: 3 V
-
Operating current: 14 μA nominal
Requires one CR 123 lithium battery
10-year battery life design
Non-volatile memory (saved changes are stored
during power loss)
Environment
Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
For indoor use only
RF Range
Distance between local load controls and sensor
should not exceed 60 ft (18 m) line of sight or 30 ft
(9 m) through walls.
Sensor Coverage Test
Dedicated test button
Lens illuminates orange in response to motion
during test mode
Wireless Communication Test
Dedicated test button
Turn associated loads on and off
Timeout Options
1 minute *
• 5 minutes
15 minutes – default setting
• 30 minutes
Auto-On Options (Occupancy Versions Only)
“Enabled” – Sensor turns lights ON and OFF
automatically – default setting.
“Disabled” ** – Lights must be turned ON manually
from dimming or switching device. Sensor turns
lights OFF automatically.
Sensitivity Options
Low Activity (
) – default setting
Medium Activity (
)
High Activity (
)
* Intended for use in high-activity, brie y occupied areas only
** There is a 15-second grace period that begins when the lights are
automatically turned off, during which the lights will automatically turn
back on in response to motion. This grace period is provided as a safety
and convenience feature in the event the lights turn off while the room is
still occupied, so that the user does not need to manually turn the lights
back on. After 15 seconds, the grace period expires and the lights must
be manually turned on.
14
369776a 15 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
4.35 in
(110 mm)
1.35 in
(34 mm)
1.8 in
(46 mm)
15
369776a 16 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
180° Wall-Mount Sensors
(Models: LRFX-OWLB-P-WH and LRFX-VWLB-P-WH)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.6 m and 2.4 m).
Horizontal Beam Diagram
Vertical Beam Diagram *
0 ft
(0 m)
7 ft
(2.1 m)
0 ft
(0 m)
60 ft
(18.3 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
50 ft
(15.2 m)
0 ft
(0 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
25 ft
(7.6 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
25 ft
(7.6 m)
0 ft
(0 m)
60 ft
(18.3 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
50 ft
(15.2 m)
Compliant to NEMA WD7 test grid shown below
Tested Coverage Area
Major Motion 3000 ft
2
(278.7 m
2
) coverage
Minor Motion 1500 ft
2
(139.4 m
2
) coverage
25 ft
(7.6 m)
15 ft
(4.6 m)
50 ft
(15.2 m)
60 ft
(18.3 m)
16
369776a 17 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
90° Corner-Mount Sensors
(Models: LRFX-OKLB-P-WH and LRFX-VKLB-P-WH)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.6 m and 2.4 m).
50 ft (15.2 m)
35 ft (10.7 m)
0 ft
(0 m)
7 ft
(2.1 m)
0 ft
(0 m)
20 ft
(6.1 m)
10 ft
(3.0 m)
30 ft
(9.1 m)
40 ft
(12.2 m)
56 ft
(17.1 m)
Horizontal Beam Diagram
Vertical Beam Diagram *
Compliant to NEMA WD7 test grid shown below
Tested Coverage Area
Major Motion 2500 ft
2
(232.3 m
2
) coverage
Minor Motion 1225 ft
2
(113.8 m
2
) coverage
50 ft
(15.2 m)
35 ft
(10.7 m)
35 ft
(10.7 m)
50 ft
(15.2 m)
17
369776a 18 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Coverage Diagrams
Hallway Sensors
(Models: LRFX-OHLB-P-WH and LRFX-VHLB-P-WH)
• Designed to mount at the end of a hallway with a clear view down the length of a hall.
• Detection at longer distances is best when motion occurs at right angles to the sensor.
• Multiple sensors can be used to extend coverage.
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 ft and 8 ft (1.8 m and 2.4 m) and centered within hallway.
Width of Hall Length of Hall
6 ft (1.8 m) or less 50 ft (15.2 m)
8 ft (2.4 m) 100 ft (30.5 m)
10 ft (3.0 m) or more 150 ft (45.7 m)
Maximum Recommended Hallway Length
5 ft
(1.5 m)
0 ft
(0 m)
5 ft
(1.5 m)
0 ft
(0 m)
25 ft
(7.6 m)
50 ft
(15.2 m)
75 ft
(22.9 m)
100 ft
(30.5 m)
150 ft
(45.7 m)
125 ft
(38.1 m)
0 ft
(0 m)
25 ft
(7.6 m)
50 ft
(15.2 m)
75 ft
(22.9 m)
100 ft
(30.5 m)
150 ft
(45.7 m)
125 ft
(38.1 m)
0 ft
(0 m)
7 ft
(2.1 m)
Top View
Side View
18
369776a 19 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Installation Overview
Sensor Placement
The mounting height of the sensor should be between 6 ft and 8 ft (1.6 m and 2.4 m)
For smaller rooms less than 12 ft x 12 ft (3.7 m x 3.7 m), detection may be improved by mounting the sensor at
6 ft (1.8 m) from the fl oor.
The ability to detect motion requires that the sensor have line-of-sight of all room occupants. The sensor must
have an unobstructed view of the room. DO NOT mount behind or near tall cabinets, shelves, hanging fi xtures,
etc. The sensor cannot detect occupants through glass objects such as patio or shower doors.
Hot objects and moving air currents can affect the performance of the sensor. To ensure proper operation, the
sensor should be mounted at least 4 ft (1.2 m) away from light bulbs and HVAC vents.
The performance of the sensor depends on a temperature differential between the ambient room temperature
and that of room occupants. Warmer rooms may reduce the sensor’s ability to detect occupants.
Distance between local load controls and sensor should not exceed 60 ft (18 m) line of sight or 30 ft (9 m)
through walls.
19
369776a 20 08.12.13
Energi TriPakR Energy Retrofit Packages
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
180˚ and hallway sensors mount directly to wall with mounting bracket (included). See fi gure below.
90˚ sensors mount directly in corner or on wall offset away from corner with mounting bracket (included).
See fi gure below.
Temporary mounting is recommended to test sensor coverage and wireless communication before permanently
installing the sensor.
Temporary mounting: A 3MT CommandT adhesive strip is provided for temporarily mounting and testing
the sensor. This strip is designed for easy, damage-free removal and is not reusable.
Permanent mounting: Mounting bracket, screws and anchors are provided to mount sensor.
• Flexible Armature Mounting Kit - P/N LRF2-MTG-KIT-CPN5991 (sold separately): A fl exible sensor mounting
bracket which allows sensor to be mounted at right angles and at greater heights to increas coverage area.
3M and Command are trademarks of 3M Company.
180˚ Wall-Mount Sensor & Hallway Sensor
90˚ Corner-Mount Sensor
20