SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 1 08.13.15
Lutron® Tamper Resistant, Self-Testing
GFCI Receptacles
Features
Continuous self-test functionality – disconnects power to
receptacle if critical components are damaged and GFCI
protection is lost – providing “continuous self-testing”
that initiates within 2.5 seconds and is a continuous
cycle every 30 seconds or less.
Three provisions for providing protection:
- Continuous electronic sensing, testing and evaluation
utilizing diagnostic software located on the printed
circuit board.
- Traditional testing mode by manually operating the
“test and reset” buttons utilizing a supervisory circuit as
specified in UL 943 section 5.15.
- Auto-sensing mode for immediate interruption for a
ground fault condition for Class A protection
(4 – 6 mA).
Manual Test – this design incorporates a full system test
function. The GFCI, when manually tested, induces a
simulated ground fault leakage current to the printed
circuit board. This in turn causes the mechanical system
to react based on the action of the solenoid. The entire
mechanical and electronic GFCI system is reviewed for
functionality.
Reverse wire safety feature – if wired incorrectly there will
be no power to the face or to downstream receptacles
for added safety.
Clear visual indication of GFCI status —
LED indicating lights:
- Green LED (power to the device)
- Red LED (trip condition/ground fault condition)
- Flashing Red LED (end of life)
Permanently installed internal tamper-resistant shutter
mechanism capable of resisting insertion of foreign
elements into the device.
Internal back wiring clamp and guide pocket — quick
and dependable termination.
Receptacle face compatible with NEMA designer and
NovaT*
® designer-opening wallplates.
Compliant with NEC
® 406.12 and NEC® 517-18(c).
Models Available:
15 A
CAR-15-G FST-XX 15 A 125 V~ 60 Hz
SCR-15-GFST-XX 15 A 125 V~ 60 Hz
NTR-15- GFST-XX 15 A 125 V~ 60 Hz
20 A
SCR-20-GFST-XX 20 A 125 V~ 60 Hz
NTR-20-GFST-XX 20 A 125 V~ 60 Hz
(XX in model number represents color/finish code)
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 2 08.13.15
Specifications
Regulatory Approvals
Meets UL 943 Class A GFCIs and UL 498 for
Receptacles
Complies to NEC, CEC & OSHA, UL File E-41978,
CSA File LR-24886
UL Listed
CSA Certified
NOM Certified
UL 943 Dust Test: Meets performance requirement
section 6.20 UL 943 GFCI
Power
15 A & 20 A, 125 V~ (102 V~ – 132 V~) 60 Hz
Exceeds immunity level of 0.5 V over a frequency
range of 150 kHz to 230 MHz
Electrical
Trip Level: 4 – 6 mA
Trip Time: .025 seconds (nominal)
Frequency: 60 Hz
Max Interruption: 10,000 A
Environmental
Operating Temperature: -35 °C to 66 °C
(-30 °F to 150 °F)
Maximum Humidity: 95%
Emissions
Compliant for radiated emissions 30 – 1000 MHz
Compliant for conducted emissions 150 kHz –
30 MHz
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 3 08.13.15
Dimensions
Front View
NTR- models (with NovaT*® wallplate) CAR- and SCR- models (with Claro® wallplate) Bulk unit
Side View Rear View
all models all models
4.56 in
(116 m m)
4.69 in
(119 m m)
3.28 in
(83.3 mm)
2.75 in
(70 mm)
2.94 in
(75 mm)
1.75 in
(44.5 mm)
1.10 in
(27. 8 m m )
1.47 in
( 37. 3 m m)
2.78 in
(70.6 mm)
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 4 08.13.15
A: One cable entering the box OR B: Two cables entering the box
LINE cable brings
power to the GFCI
Grounding connection
to box (if box has a
grounding terminal)
Wire
connector
LINE cable brings
power to the GFCI
Wire
connector
Grounding connection
to box (if box has a
grounding terminal)
Electrical
box
LOAD
cable feeds
power to other
receptacle(s)
About wire connections
Clockwise, 2/3 of the way
around the screw
Wire
1 in
Wire
5/8 in
Insert wire to the
bottom of hole and
tighten down screw
Side Wire
Back Wire
About wire connections
Clockwise, 2/3 of the way
around the screw
Wire
Wire
Insert wire to the
bottom of hole and
tighten down screw
Side Wire
Back Wire
Electrical box
Yellow sticker
remains in
place to cover
the LOAD
terminals
(16 mm)
(25.4 mm)
1 in
(25.4 mm)
5/8 in
(16 mm)
Wiring Diagrams (choose one or the other)
Mounting
TEST
TEST
RESET
RESET
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® GFCI – Tamper Resistant, Self-Testing Receptacles
369964a 5 08.13.15
Colors and Finishes
Gloss Finishes Satin Finishes
Taupe
TP
Turquoise
TQ
Plum
PL
Merlot
MR
Terracotta
TC
Sienna
SI
Midnight
MN
Hot
HT
Desert Stone
DS
Eggshell
ES
Biscuit
BI
Snow
SW
Palladium
PD
Greenbriar
GB
Bluestone
BG
Mocha Stone
MS
Goldstone
GS
Stone
ST
Limestone
LS
White
WH
Ivory
IV
Almond
AL
Light Almond
LA
Gray
GR
Brown
BR
Black
BL
Due to printing limitations, colors
and finishes shown cannot be
guaranteed to perfectly match
actual product colors.
Color chip keychains are available
for more precise color matching:
Gloss Finishes: DG-CK-1
Satin Finishes: SC-CK-1
5