SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LMR-SAFLOK-PR Software LicenseLutron
369943c 1 01.08.19
Features
Guest Presence Detection
The door’s state (open/closed) is used in conjunction
with in-room motion sensor(s) and control buttons to
detect if someone is present in the room.
Occupant Differentiation
When the door is unlocked with a valid key, a
differentiation is made between a first-time guest
entry, a guest entry, and a staff entry.
Energy Saving
When the door is opened/closed, the room is
scanned for motion and checked for button presses
to determine if it is still occupied.
Thirty minutes (programmable) after the door closes,
if no motion or button activity is detected, the rooms
thermostat, drapery, and lighting settle into an
energy-saving state.
Thermostat Programming
The rooms thermostat can be programmed to return
from the energy-saving mode to normal operation
when the door of an unoccupied (no person present)
room is opened.
Normal Operation
If motion or button activity is detected in an
unoccupied room, the room thermostat can be
programmed to return from the energy-saving mode
to normal operation.
Turn on room lighting automatically when a guest
opens the door
Automatic lighting control can be achieved without a
door contact installed.
Activate a first-arrival “Welcome” setting in the
room for the guest
The guestrooms thermostat, drapery, and lighting
can be preset to a “Welcome” setting, activated by
the check-in message received from the hotel’s
Property Management System (PMS). An additional
license is required, such as LMR-OPERA-PR for an
OperaT PMS.
Summary of Guest Presence Features
Thermostat Lights Shades
Exiting a room using a SaflokR system can trigger a
programmed event to adjust:
Yes Yes Yes
Entering a room using a SaflokR system can trigger a
programmed event to adjust:
Yes Yes Yes
Entering a room using a SaflokR system can trigger
different events based on guest or staff entry to adjust:
Yes Yes Yes
LMR-SAFLOK-PR KABAR SaflokR Door Lock
Interface Software License for Lutron myRoom plus
The LMR-SAFLOK-PR interface software enables integration between Lutron myRoom plus systems and the
Saflok Messenger LENST online door lock system. Door lock events are sent from the SaflokR system to the
myRoom plus system to enable advanced control of the rooms thermostat, drapery, and lighting.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LMR-SAFLOK-PR Software LicenseLutron
369943c 2 01.08.19
Concept of Operation
• TheLutronmyRoomplussystemserverisinterfaced
with the Saflok Messenger LENST server via a server-
to-server interface.
• TheSaokR system wireless hubs, typically located
above access panels in the corridor, are connected to
the hotel’s network so they can communicate with the
Saflok Messenger LENST server.
Refer to the following numbered event sequence in
the diagram below.
1. The guestrooms door lock communicates with the
SaflokR system wireless hub.
2. The wireless hub relays the message to the Saflok
Messenger LENST server via the hotel network.
3. The Saflok system Messenger LENST server
sends door-event messages to the Lutron
myRoom plus system server.
4. The myRoom plus server software interprets the
SaflokR event message and then routes a Lutron
message via the hotel network to the myRoom
plus guestroom control unit (GCU-HOSP) located
in the guestroom where the door-event message
originated.
5. The myRoom plus GCU-HOSP controls the
rooms thermostat, drapery, and lighting as
programmed.
Typical System Diagram
Door Lock
Wireless message
Message sent over hotel network
Message sent over hotel network
Lighting
Drapery
Thermostat
Door Lock Door Lock
SaflokR System
Wireless Hub
Lutron
myRoom plus
Lutron
myRoom plus
Lutron
myRoom plus
Hotel Network: Wired Ethernet Cat 5/6 Cable
Hotel Room Hotel Room Hotel Room
Lutron myRoom plus
System Server
Saflok System Messenger
LENST Server
2
4
1
5
Message sent over hotel network
Server-to-server interface
3
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LMR-SAFLOK-PR Software LicenseLutron
369943c 3 01.08.19
SaflokR System Requirements
The Lutron myRoom plus system is compatible with
all wireless SaflokR access control systems that
operate using the Saflok Messenger LENST software.
SaflokR is responsible for the complete design,
installation, start-up, and maintenance of all system
components necessary for their wireless online
door-lock system to operate. This includes, but is not
limited to, the following:
• Electronicdoorlockswiththerequiredonline
hardware installed
• Wirelesshubsthatallowthedoorlocksto
communicate over the hotel network
• CoordinatingtherequiredwiringforallSaokR
equipment
• MessengerLENST server and software version
4.2.0.X or newer or SaflokR system 6000 version 4.13i
or newer.
• EnablingtheSaokR system interface on the
Messenger LENST server to allow communication to
the Lutron myRoom server
Lutron System Requirements
Only the Lutron myRoom plus system is compatible
with the Saflok Messenger LENST server.
The Lutron myRoom plus system BOM must include
the following:
• LMR-VSBO:myRoomserverbyothersor
Lutron-provided LMR-CMP-R: myRoom plus server
• LMR-SAFLOK-PR:myRoomplus-SaokR interface
software licenses; one license required per
guestroom
• LMR-EO:myRoomplusnetworkingrequirements
Network Requirements
To ensure acceptable end-to-end system response
time and a positive guest experience, the hotel
network must meet the following requirements:
• TheLutronserverandallGCU-HOSPunitsmust
sharethesamesubnetonadedicatedVLAN.
• TheSaokMessengerLENST server and all SaflokR
wireless hubs must share the same subnet on a
dedicatedVLAN.
• HTTPcommunicationusingacongurableportmust
be allowed from the Lutron myRoom plus server to
the Saflok Messenger LENST server.
Commissioning Requirements
• LutronshallbeprovidedwiththeIPandportfrom
which the Saflok system Messenger LENST server
will be communicating.
• Lutronshallbeprovidedwiththeexact,
commissioned names for all SaflokR system door
locks.
• Roomautomationusingdoorlocksystem
integration requires a fully commissioned door lock
system, servers (Lutron and SaflokR), and network
infrastructure.
Mock-Up Demonstrations
If integration with the SaflokR door locking system
must be demonstrated for a hotel mock-up room
review, it will require close coordination between the
local Lutron and SaflokR sales, project management,
and start-up teams. The SaflokR wireless hub, the
Saflok Messenger LENST server, and the Lutron
myRoom plus server all need to be included in the
mock-up.
)Lutron and Lutron are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
myRoom is a trademark of Lutron Electronics Co., Inc.
KABA, Saflok, and Messenger LENS are trademarks of the Kaba Group.
Opera is a trademark of MICROS Systems, Inc.
3