SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks® QS Switching Fixture Controller
369844a 2 07.10.15
Specifications
Regulatory Approvals
• IEC/EN 60669
• UL
® Listed
• cUL Listed
• NOM Certified
• Lutron
® Quality Systems registered to ISO9001.2008
Power
• 120 –240V~ 50/60Hz
• Single input feed
• 4 A maximum input current
• Lightning strike protection meets ANSI/IEEE standard
C62.41 and IEC 61000-4-5. Can withstand voltage
surges up to 6 000V~ and current surges up to
3 000A.
• ESD-protection exceeds agency requirements per
IEC-61000-4-2
• For ungrounded delta feed applications, contact Lutron.
Environment
• For thermal specifications, see Mounting section
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
• CCI / CCO
wiring: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
• Zone wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
• QS Link: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
Manual Mode Operation
• Zone button on the unit can be used to turn loads on
and off.
Manual Override Contact Closure Input (CCI)
• When the CCI is open, the Switching Power Module
will enter Manual Override Mode, which will turn on
all loads to their override level and disable control of
all local zones and QS devices.
• When the CCI is closed or jumpered (factory default),
the Switching Power Module zones will return to
the settings or levels they were at prior to entering
Manual Override Mode.
Contact Closure Output (CCO)
• Accepts voltages of 0 –24V~ / 0 –24V-; see chart
below for load switching capacities:
Switching Voltage
Resistive Load
R
0 –24 V- 1.0 A
0 –24 V~ 0.5 A
• Provides both normally open (N.O.) and normally
closed (N.C.) dry contacts.
• Maintained or momentary output type.
• Output relay is non-latching (if relay is closed and
power is lost, relay will open).
• The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited to,
relays, solenoids, and motors. To control these types
of equipment, a flyback diode (not included) must be
used (DC voltages only). See diagram below.
Inductive
Load
Flyback Diode
(required for
inductive loads)
CCO Output
N.O. N.C.
COM
+
–
24 V-
maximum