Specifications (continued)
Output Zone Ratings
•
No Derating is required if all the conditions below are met:
– Calibration point maximum is 70 ºC (158 ºF).
– Room ambient temperature is between 0 ºC and 30 ºC
(32 ºF and 86 ºF).
– Panel ambient temperature, within 20 mm (0.80 in) of
unit, is between 0 ºC and 50 ºC (32 ºF and 122 ºF).
• 25 W (@120 V~) / 50 W (@240 V~): Derating on
all zones is required for a single module in a non-
ventilated enclosure if the room ambient temperature is
between 30 ºC and 40 ºC (86 ºF and 104 ºF).
• 50 W (@120 V~) / 100 W (@240 V~): Derating on
all zones is required in a multiple row non-ventilated
enclosure if the temperature is between 30 ºC and
40 ºC (86 ºF and 104 ºF).
• Each zone has a 5 W (incandescent) minimum
load requirement. For LED compatibility details,
see www.lutron.com/LEDTool and Application note
# 5 57.
• Does not support non-dimmable loads
• Automatically selects leading-edge or trailing-edge
dimming when configured to "Auto-detect". It can also
be configured for a specific load type.
• One load type per zone.
• This module is designed to control loads with ratings
as noted in the table below. Outputs cannot be used
to control general purpose receptacles.
• Special considerations:
– When controlling lamps, Lutron recommends using
permanently installed fixtures.
– If controlling plug-in lamps, installation must ensure a
method of preventing non-rated loads being plugged
into the unit. An example is a dedicated receptacle
with an alternate plug type.
– Controlling loads outside the parameters listed in the
table below, may damage the device and void the
warranty.
• Output must be directly connected to the load,
outputs are not compatible with load side switching
(i.e., breakers, switches, etc.).
• Run a separate neutral for each load circuit. A
common neutral connection is not recommended.
• Maximum wire length between Adaptive Power
Module and the load must be less than 30.5 m
(100 ft).
• Unit may be powered by Ground Fault Interrupter
(GFI) or Residual Current Circuit Breaker with
Overload (RCBO) protected circuit if required. Load
circuit wiring (from breaker to unit to load) must be
run in its own non-metallic conduit, or nuisance
tripping may occur.
• For applications requiring 0–10 V- control, use a
Ten Volt Interface (GRX-TVI) or a 0–10 V Adaptive
Power Module (LQSE-4T10-D).
• For applications requiring higher wattage ratings, use
NGRX-PB, NGRX-ELVI or LQSE-4A-D for 230 V~ or
PHPM-PA for 120 V~.
A
Refer to www.lutron.com/LEDtool and Application Note #557 for compatibility with dimmable CFL / LED light sources.
B
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1.
C
Actual lamp wattage.
Each zone is rated for the following wattage and load types
A
:
Load Type
Zones 1 – 4
120 V~ 220 V~ 230 V~ 240 V~
Incandescent / Halogen 120 W 220 W 230 W 240 W
Electronic Low-Voltage 120 W 220 W 230 W 240 W
Magnetic Low-Voltage
B
120 VA (90 W
C
) 220 VA (165 W
C
) 230 VA (172 W
C
) 240 VA (180 W
C
)
Neon / Cold Cathode
B
120 VA (90 W
C
) 220 VA (165 W
C
) 230 VA (172 W
C
) 240 VA (180 W
C
)
Hi-lume® A-Series LTE
120 VA 1-6 drivers
N/A N/A N/A