SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 1 02.07.13
Infrared Ceiling Mount Sensor
The LOS-CIR Series passive infrared ceiling-mount
sensors can integrate into LutronR systems or function
as stand-alone controls using a LutronR power pack.
The sensor uses a small semiconductor heat detector
that resides behind a multi-zone optical lens. The
detector is sensitive to the heat emitted by the human
body. In order to trigger the sensor, the source of heat
must move from one range of detection to another.
Non-moving hot objects will not cause the lights to
turn on.
Features
Intelligent, continually adapting Passive Infrared (PIR)
sensor
Passive Infrared (PIR) sensing
Reliable motion detection with high error immunity
Snap-locks to ceiling-mounted cover plate
Non-Volatile Memory: settings saved in protected
memory are not lost during power outages
450 ft( to 1500 ft( (42 m( to 140 m() coverage when
mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling
Affords choice of turning lights off or dimming to a
preset level in the unoccupied state when integrated
with a LutronR system.
Models Available
Model Color Coverage Field of View
LOS-CIR-450-WH White 450 ft( (42m() 360°
LOS-CIR-1500-WH White 1500 ft( (140m() 360°
Self-Adaptive Feature
The LOS-CIR Series sensors provide reliable detection
with high error immunity. The internal microprocessor
analyzes the information from the PIR technology and
determines the optimum setting to use in order to
properly cover the space.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 2 02.07.13
Dimensions
Front View
4.5 in
(114 mm)
1.4 in
(38 mm)
Side View
Specifications
Regulatory Approvals
ULR and cULR listed
Power
Operating voltage: 20 24 V-, IEC PELV/NECR
Class2
Operating current: 33 mA nominal
Control output: 20 24 V- active high logic control
signal with short-circuit protection, open collector
when unoccupied
Environment
Temperature: 32 °F to 104 °F (0 °C to 40 °C)
Relative humidity: less than 95%, non-condensing
For indoor use only
Timer Adjustment
Automatic mode: Continually adapting sensor
automatically adjusts settings to the space
Manual mode: 8 to 30 minutes
Test mode: 8 seconds
LED Lamp
Red: infrared motion detected
Housing
Rugged, high-impact, injection-molded plastic
Color-coded leads 6 in (15 cm)
Adaptive Functions
Installation: 60 minutes
Learning: 4 weeks for response to error conditions, air
current adaptation, and timer optimization
Post-learning occupancy periods
—24 hour circadian occupancy periods learned
—Weekly occupancy periods learned
Adjustments in post-learning period
Generally occupied periods
(threshold = high-sensitivity mode)
Generally unoccupied periods
(threshold = miser mode)
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 3 02.07.13
Power packs may be required when interfaced to LutronR lighting control systems. If more than 1 occupancy
sensor is connected to the same input, a power pack is required. A maximum of 3 occupancy sensors can be
connected to the same input. If more than 3 sensors are required per input, use one of the following models:
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, or LOS-CDT-2000R-WH.
Power Supply Options
LutronR Lighting Control System Power Pack Required?
Digital microWATTT No
EcoSystemR No
Energi Savr NodeT No*
GRAFIK 5000T/6000R/7000T No, when used with seeTouchR wallstations with occupancy sensor
connections.
GRAFIK EyeR 3000/4000 Yes
GRAFIK EyeR QS No*
HomeWorksR Yes
HomeWorksR QS No*
LCP128T No, when used with seeTouchR wallstations with occupancy sensor
connections.
microWATTR No
QuantumR No*
RadioRAR Yes
RadioRAR 2 Yes
Softswitch128R No, when used with seeTouchR wallstations with occupancy sensor
connections.
Wiring: System Control
* Some system components do not supply external power for occupancy sensors. Refer to individual product
specifications for more information.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 4 02.07.13
Neutral
Power
Pack
Lighting
Load
NOTE: Maximum 3 occupancy sensors.
Red (+20 – 24 V-)
Blue (signal)
Black
(common)
Black
White
Red
Red
1 to 3 Sensors with Power Pack
Switching Multiple Loads with Auxiliary Power Packs
Line
Neutral
Line
Lighting
Load
Lighting
Load
Power
Pack
Auxiliary
Power
Pack
Red
Red
Red (+20 – 24 V-)
Blue (signal)
Black
(common)
NOTE: Maximum of 3 devices total (occupancy sensors and auxiliary power packs) can be connected to a power pack.
Black
White
Red
Red
120 / 277 / 347 V~ 60 Hz;
230 V~ 50 / 60 Hz
120 / 277 / 347V~ 60 Hz
230 V~ 50 / 60 Hz
Wiring: Stand-Alone Control
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 5 02.07.13
Major motion detection
Minor motion detection
6.5 ft
(1.9 m)
12 ft
(3.7 m)
LOS-CIR-1500
LOS-CIR-450
Installation
Sensor Placement
Range Diagrams
The occupancy sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets,
shelves, indirect hanging fixtures, etc.
Do not place sensor within 4 ft (1.2 m) of air vents, air handlers, windows, fans, etc., as this may cause false
triggering.
Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect major
motion (e.g. person taking a half-step) at a greater distance than it can detect minor motion (e.g. writing at a
desk or reading a book).
May not detect occupancy with no significant difference between ambient and body temperatures.
Sensor Setup
Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning
service document (LutronR P/N 3601235).
12 ft
(3.7 m)
22 ft
(6.7 m)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 6 02.07.13
Using the Infrared Mask
Center Ceiling Mount
(Mask blocks sensor seeing
out doorway into hall)
Corner Ceiling Mount
(No mask needed)
Conference
Room Mask
180° Mask Full Mask
Rectangular
Areas
Over the Door Specific Areas
You Wish to
Mask
Typical Mask Patterns
Mounting
Normal Mounting
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using
cutter end of the threaded mounting post. Secure
with washer and nut.
Cutter
end
Mounting to Non-Standard Ceiling or Fixture
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.
Mounting Plate Dimensions
4.2 in
(106.6 mm)
2.5 in
(63 mm)
0.52 in
(13.3 mm)
13/16 in (21 mm)
Wire Lengths
Number of Sensors 1 2 3 1 2 1
Number of Auxiliary
Power Packs
0 0 0 1 1 2
22 AWG 750 ft 375 ft 250 ft 375 ft 250 ft 250 ft
0.5 mm( 365 m 180 m 120 m 90 m 120 m 120 m
20 AWG 1200 ft 600 ft 400 ft 600 ft 400 ft 400 ft
0.75 mm( 730 m 365 m 240 m 365 m 240 m 365 m
18 AWG 2400 ft 1200 ft 800 ft 1200 ft 800 ft 800 ft
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CIR Series Occupancy Sensors
369655c 7 02.07.13
ON
ON
A
1
2
3
4
B
1
2
3
4
Black:
Timer
8 min
Red:
Infrared
sensitivity
75% default
Off (Default) On
Automatic (Normal) Manual on / off (Override)
Auto Threshold Adjustment High Sensitivity (Low turn-on threshold)
Lights indicate motion Disable LED Indicator
Retain Settings (Normal) Erase all learned settings; Restart Learning (Toggle On)
Sensor Adjustments
Timer Test Mode
Factory Settings
1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to about
midway (12 o’clock).
3. Return setting to minimum setting (full CCW).
NOTE: The timer will remain in the 8 second test mode
for 1 hour, then automatically reset to 8minutes.
4. To manually take the timer out of the 8 second test
mode, turn the timer adjustment approximately 1/16in
(1.5 mm) clockwise to make the setting slightly above
minimum (just above the 8 minute setting).
Factory Settings 12 o’clock
Full CCW
Auto/Manual
Threshold
LED Motion Indicator
Reset Learned Settings
Strong Airflow Compensation
Over Doorway Installation
Timer Adjust
Auto Sensitivity
ONOFF
ONOFF
ONOFF
ONOFF
A
1
2
3
4
B
1
2
3
4
Override Settings
Off (Default) On
Disable Compensation (Normal) Enable Compensation
No (Normal) Yes (Use increased turn-on threshold)
Adjust Timer Automatically Use Manual Setting (No adjustment)
Adjust Sensitivity Automatically Adjust Sensitivity Manually