SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Wallbox Closure Interface QSE-CI-WCI Control Interface
369681b 1 08.26.15
QS Wallbox Closure Interface
The QSE-CI-WCI (WCI) is a control interface for use
with HomeWorks
® QS systems, Quantum® systems,
and QS standalone applications. The WCI integrates a
contact closure keypad with a Lutron
® lighting control
system. The contact closure keypad must be provided
by the customer. The WCI provides up to eight
contact closure inputs (CCIs). The CCIs accept
maintained or momentary signals. The CCIs are
programmable through the HomeWorks
® QS and
Quantum
® system setup software. For QS standalone
applications, the CCIs are programmable using the
button, DIP switch, and LEDs on the WCI.
Features
• Provides 8 contact closure inputs (CCIs), maintained
or momentary.
Works with SELV / PELV / NEC® Class 2, low-voltage,
dry contact closures.
• The CCI can be set up to simulate existing Lutron
®
keypad functionality or custom-configured to meet
project-specific requirements.
• Place in the wallbox behind a contact closure keypad
(See Mounting).
• Provides a 1-way interface between the Lutron
®
lighting system and a contact closure keypad (not
supplied).
• For use in HomeWorks
® QS systems, Quantum®
systems, and QS standalone applications.
Additional Programming Details
• In HomeWorks
® QS and Quantum® systems, the
8 CCIs are individually programmable through the
appropriate setup software.
• For QS standalone applications, the DIP switch allows
for selection of CCI control options:
- With or without raise/lower controls.
- With all momentary or all maintained CCIs.
• LEDs provide instant feedback during setup and
diagnostics;
- Confirmation when programming.
Shown actual size.
- Verification of which contacts are closed.
- Indication of communication miswire/malfunction.
• Programming button allows for ease of programming
and resetting to factory default.
Functionality in QS Standalone Systems
GRAFIK Eye® QS (QSGRx-)
- Inputs activate Scenes.
- Toggle Zones between a Preset and Off.
- Cannot be used as a partion controller.
• Energi Savr Node
TM (QSN- or QSNE-)
- Inputs activate Scenes.
- Toggle Zones between a Preset and Off.
- Cannot be used as a partion controller.
• Motor Module (QSE-CI-4M)
- Window treatment Open/Stop/Close.
- Toggle assigned windows treatments between
Open and Close.
• Contact Closure Interface (QSE-IO)
• Sivoia
® QS
- Window treatment Open/Preset/Close.
- Supports venetian window treatments.
- Supports 6 default presets (4 presets when applying
Raise/Lower).
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Wallbox Closure Interface QSE-CI-WCI Control Interface
369681b 2 08.26.15
Specifications
Regulatory Approvals
• CE marked
• Complies with IEC standards 60669-2-1 and
50428:2005
• If UL listing is required, please contact Lutron
Input Power
• Operating Voltage: 24–36 V- 20 mA
Low Voltage SELV / PELV / NEC® Class 2 wiring provides
power, derived from QS link. Consumes one Power
Draw Unit (PDU).
Contact Closure Input Types
• The QSE-CI-WCI (WCI) is compatible with both
momentary and maintained contact closure inputs
(CCIs).
• Contact closure keypad must have a low voltage, dry
contact closure rating.
• CCIs must have an on-state saturation voltage less
than 1 V at 1 mA and an off-state leakage current of
less than 100 uA. Contact manufacturer of the contact
closure keypad for details.
• The signal pulse for the CCI must be greater than
40 ms. Contact manufacturer of the contact closure
keypad for details.
• The WCI is not designed or rated to work with line/
mains voltage switches. Use with line/mains voltage
switches will result in premature failure.
Environment
• Ambient Operating Temperature: 0 °C to 40 °C
(32 °F to 104 °F)
• Relative Humidity less than 90%, non-condensing
• For indoor use only
Terminals
• Each terminal accepts up to two 1.0 mm
2
(18 AWG)
wires, one twisted shielded pair 0.5 mm
2
(22 AWG)
wire or one 4.0 mm
2
(12 AWG) wire typical.
Mounting
• Recommended to be placed in the wallbox behind a
contact closure keypad.
• Lutron recommends using a wallbox which is 60 mm
(2
1
2 in) deep x 60 mm (2
1
2 in) wide, when installing
the WCI. Note: Some applications may require a
deeper wallbox.
• If alternative mounting is required, do not extend wiring
harness more than 45 m (150 ft).
QS Link Limits
• Please refer to the system spec for details regarding
your application.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Wallbox Closure Interface QSE-CI-WCI Control Interface
369681b 3 08.26.15
Mechanical Dimensions
Front View Side View Back View
52 mm
(2.0625 in)
21 mm
(.8125 in)
60 mm
(2.375 in)
1
COM
2
V+
3
MUX
4
MUX
®
47 mm (1.875 in)
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Wallbox Closure Interface QSE-CI-WCI Control Interface
369681b 4 08.26.15
Contact Closure Wiring
• Connect the contact closures to the contact
closure inputs (CCIs) and shared common
using supplied wiring harness.
• Ensure proper function, and cap all unused
CCI wires together, away from other
circuitry.
Note: All contact closures must share the
provided common. (Black)
Common (Black)
Wiring
1
COM
2
V+
3
MUX
4
MUX
®
QS Link Wiring
MUX (White)
MUX (Purple)
V+ (Red)
COM (Black)
Contact closure input
Communication
link wiring
Wallbox
Input Wiring Harness:
Approximately 178 mm (7 in) long with 13 mm (1/2 in) pre-stripped end.
1 2 3 4 5 6 7 8
LEDs
Contact Closure Inputs
2 (Orange)
3 (Yellow)
4 (Green)
5 (Blue)
6 (Purple)
7 (Gray)
8
9 (Black)
1 (Red)
Note: Connect CCI wires
appropriately
QS Wiring
ON
12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
®
COM
QSE-CI-WCI
INPUTS
ENTRADA
ENTRÉES
Contact
Closure
CCI 8
(White)
CCI 1 (Red)
Contact
Closure
1 2 3 4 5 6 7 8 COM
Red
Orange
Yellow
Green
Blue
Purple
Grey
White
Black
Contact closure wire colors
1 2 3 4 5 6 7 8
LEDs
1 2 3 4 5 6 7 8
COM
Contact Closure Inputs
4