SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 1 02.07.13
Dual Technology Ceiling Mount Sensor
The LOS-CDT Series dual technology ceiling-mount
sensors can integrate into LutronR systems or function
as stand-alone controls using a LutronR power pack.
The technology eliminates manual sensitivity and timer
adjustments during installation and over the life of the
product.
Features
Intelligent, continually adapting sensor
Ultrasonic (US) combined with Passive Infrared (PIR)
sensing provide high sensitivity, high noise immunity,
and excellent false tripping immunity
Suited for complex environments that are difficult to
control with single-technology sensors
Snap-locks to ceiling-mounted cover plate
Non-Volatile Memory: settings saved in protected
memory are not lost during power outages
500 ft( to 2000 ft( (46 m( to 186 m() coverage when
mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling
Affords choice of turning lights off or dimming to a
preset level in the unoccupied state when integrated
with a LutronR system.
Models Available
Model Color Coverage Field of
View
LOS-CDT-500-WH White 500 ft( (46m() 180°
LOS-CDT-500R-WH White 500 ft( (46m() 180°
LOS-CDT-1000-WH White 1000 ft( (93m() 180°
LOS-CDT-1000R-WH White 1000 ft( (93m() 180°
LOS-CDT-2000-WH White 2000 ft( (186m() 360°
LOS-CDT-2000R-WH White 2000 ft( (186m() 360°
Self-Adaptive Feature
The LOS-CDT Series sensors combine both Ultrasonic
(US) motion detection for maximum sensitivity and
Passive Infrared (PIR) motion detection for false
triggering immunity. The self-adapting internal
microprocessor analyzes the composite sum of both
signals to eliminate time-consuming adjustments and
callbacks found in non-intelligent sensors.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 2 02.07.13
Specifications
Dimensions
Front View
4.5 in
(114 mm)
1.4 in
(38 mm)
Side View
Regulatory Approvals
ULR and cULR listed
Power
Operating voltage: 20 24 V-, IEC PELV/NECR
Class2
Operating current: 33 mA nominal
Control output: 20 24 V- active high logic control
signal with short-circuit protection, open collector
when unoccupied
Environment
Temperature: 32 °F to 104 °F (0 °C to 40 °C)
Relative humidity: less than 95%, non-condensing
For indoor use only
Timer Adjustment
Automatic mode: Continually adapting sensor
automatically adjusts settings to the space
Manual mode: 8 to 30 minutes
Test mode: 8 seconds
LED Lamp
Red: infrared motion detected
Green: ultrasonic motion detected
Housing
Rugged, high-impact, injection-molded plastic
Color-coded leads 6 in (15 cm)
Adaptive Functions
Installation: 60 minutes
Learning: 4 weeks for response to error conditions, air
current adaptation, and timer optimization
Post-learning occupancy periods
—24 hour circadian occupancy periods learned
—Weekly occupancy periods learned
Adjustments in post-learning period
Generally occupied periods
(threshold = high-sensitivity mode)
Generally unoccupied periods
(threshold = miser mode)
Contact Rating (R Models only)
SPDT 500 mA rated at 24 V- isolated relay
Photo Cell (R Models only)
Prevents light from turning on when there is sufficient
natural light
Sensitivity: 0 lx to 1000 lx adjustable
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 3 02.07.13
Power packs may be required when interfaced to LutronR lighting control systems. If more than 1 occupancy
sensor is connected to the same input, a power pack is required. A maximum of 3 occupancy sensors can be
connected to the same input. If more than 3 sensors are required per input, use one of the following models:
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, or LOS-CDT-2000R-WH.
Power Supply Options
LutronR Lighting Control System Power Pack Required?
Digital microWATTT No
EcoSystemR No
Energi Savr NodeT No*
GRAFIK 5000T/6000R/7000T No, when used with seeTouchR wallstations with occupancy sensor
connections.
GRAFIK EyeR 3000/4000 Yes
GRAFIK EyeR QS No*
HomeWorksR Yes
HomeWorksR QS No*
LCP128T No, when used with seeTouchR wallstations with occupancy sensor
connections.
microWATTR No
QuantumR No*
RadioRAR Yes
RadioRAR 2 Yes
Softswitch128R No, when used with seeTouchR wallstations with occupancy sensor
connections.
Wiring: System Control
* Some system components do not supply external power for occupancy sensors. Refer to individual product
specifications for more information.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 4 02.07.13
Neutral
Power
Pack
Lighting
Load
NOTE: Maximum 3 occupancy sensors.
Red (+20 – 24 V-)
Blue* (signal)
Black
(common)
Black
White
Red
Red
1 to 3 Sensors with Power Pack
Switching Multiple Loads with Auxiliary Power Packs
Line
Neutral
Line
Lighting
Load
Lighting
Load
Power
Pack
Auxiliary
Power
Pack
Red
Red
Red (+20 – 24 V-)
Blue* (signal)
Black
(common)
NOTE: Maximum of 3 devices total (occupancy sensors and auxiliary power packs) can be connected to a power pack.
*Use gray wire for LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH.
Black
White
Red
Red
120 / 277 / 347 V~ 60 Hz;
230 V~ 50 / 60 Hz
120 / 277 / 347V~ 60 Hz
230 V~ 50 / 60 Hz
Wiring: Stand-Alone Control
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 5 02.07.13
Wiring
Lighting
Control
system*
Red (+20 – 24 V-)
Gray (control: occupancy and photo cell signal)
Blue: Cap off
Black (common)
Yellow/White (NO)
Black/White (NC)
Blue/White (Relay, Common)
Gray wire logic with photo cell active:
Choose wire based on functionality):
Yellow/White: NO (normally open)
Open: Unoccupied
Closed: Occupied
Black/White: NC (normally closed)
Open: Occupied
Closed: Unoccupied
Cap off unused wire.
Relay Model Option
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
*May require power pack
Room First Occupied During Occupancy
Light level Lights Light level Lights
Below set value Turn on Falls below set value Turn on
Above set value Remain off Moves above set value Remain on
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 6 02.07.13
32 ft (9.8 m)
23 ft (7 m)
23 ft
(7 m)
32 ft
(9.8 m)
12 ft (3.7 m)
22 ft (6.7 m)
64 ft (19.5 m)
45 ft (13.7 m)
23 ft
(7 m)
32 ft
(9.8 m)
Installation
LOS-CDT-2000
Sensor Placement
Range Diagrams
Mount the sensor so the grilles face the open portion of the room and are not facing a nearby wall, window, or
other obstructing object.
Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause false
triggering.
If installing a 180° occupancy sensor (500 and 1000 models), place the sensor on the same wall as the doorway
so that traffic in a hallway will not affect the sensor; otherwise, place in center of room.
Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect major
motion (e.g. person taking a half-step) at a greater distance than it can detect minor motion (e.g. writing at a
desk or reading a book).
Decrease total coverage area by 15% for “soft” rooms (e.g. heavy draperies or thick carpeting).
LOS-CDT-1000
Sensor Setup
Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning
service document (LutronR P/N 3601235).
LOS-CDT-500
Major motion detection (Ultrasonic)
Minor motion detection (Ultrasonic)
Major motion detection (Passive Infrared)
Minor motion detection (Passive Infrared)
23 ft (7 m)
16 ft (4.9 m)
16 ft
(4.9 m)
23 ft
(7 m)
12 ft (3.7 m)
22 ft (6.7 m)
12 ft (3.7 m)
22 ft (6.7 m)
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 7 02.07.13
Using the Infrared Mask
Center Ceiling Mount
(Mask blocks sensor seeing
out doorway into hall)
Corner Ceiling Mount
(No mask needed)
Conference
Room Mask
180° Mask Full Mask
Rectangular
Areas
Over the Door Specific Areas
You Wish to
Mask
Typical Mask Patterns
Mounting
Normal Mounting
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using
cutter end of the threaded mounting post. Secure
with washer and nut.
Cutter
end
Mounting to Non-Standard Ceiling or Fixture
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.
Mounting Plate Dimensions
4.2 in
(106.6 mm)
2.5 in
(63 mm)
0.52 in
(13.3 mm)
13/16 in (21 mm)
Wire Lengths
Number of Sensors 1 2 3 1 2 1
Number of Auxiliary
Power Packs
0 0 0 1 1 2
22 AWG 750 ft 375 ft 250 ft 375 ft 250 ft 250 ft
0.5 mm( 365 m 180 m 120 m 90 m 120 m 120 m
20 AWG 1200 ft 600 ft 400 ft 600 ft 400 ft 400 ft
0.75 mm( 730 m 365 m 240 m 365 m 240 m 365 m
18 AWG 2400 ft 1200 ft 800 ft 1200 ft 800 ft 800 ft
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 8 02.07.13
ON
ON
A
1
2
3
4
B
1
2
3
4
Black:
Timer
8 min
Blue:
Photo cell
(R models only)
100% default
Red:
Infrared
sensitivity
75% default
Green:
Ultrasonic
range
50% default
Off (Default) On
Automatic (Normal) Manual on / off (Override)
Auto Threshold Adjustment High Sensitivity (Low turn-on threshold)
Lights indicate motion Disable LED Indicator
Retain Settings (Normal) Erase all learned settings; Restart Learning (Toggle On)
Sensor Adjustments
Timer Test Mode
Factory Settings
1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to about
midway (12 o’clock).
3. Return setting to minimum setting (full CCW).
NOTE: The timer will remain in the 8 second test mode
for 1 hour, then automatically reset to 8minutes.
4. To manually take the timer out of the 8 second test
mode, turn the timer adjustment approximately 1/16in
(1.5 mm) clockwise to make the setting slightly above
minimum (just above the 8 minute setting).
Factory Settings 12 o’clock
Full CCW
Auto/Manual
Threshold
LED Motion Indicator
Reset Learned Settings
Strong Airflow Compensation
Over Doorway Installation
Timer Adjust
Auto Sensitivity
ONOFF
ONOFF
ONOFF
ONOFF
A
1
2
3
4
B
1
2
3
4
Override Settings
Off (Default) On
Disable Compensation (Normal) Enable Compensation
No (Normal) Yes (Use increased turn-on threshold)
Adjust Timer Automatically Use Manual Setting (No adjustment)
Adjust Sensitivity Automatically Adjust Sensitivity Manually
Continued on next page...
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CDT Series Occupancy Sensors
369653c 9 02.07.13
Sensor Adjustments (continued)
Adjusting the “Lights Not On” Level
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
Control Settings (Blue Knob)
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
1. Place timer in Test Mode (see page 8).
2. Set photo cell to maximum. Turn the blue knob full
clockwise (lights on no matter how bright the natural
light is), then about 30° counterclockwise.
3. Check for Lights-Out. Move from underneath the
sensor, and remain still until the lights turn off. Move
around normally to turn the light on.
4. Adjust to desired level. If lights remain off, adjust the
blue knob another 30° counterclockwise and repeat
step 3 until the lights turn on.
NOTE: Set blue knob to 100% to disable photo cell
functionality and leave secondary dry contact closure
output functionality intact.
0 1000
0 1000
0 1000
Minimum (low):
Lights will never come on, even though
room is occupied.
Maximum (high):
Photo cell has no effect on operation
(factory setting).
Normal:
200 lx to 600 lx is normal range.
9