R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 2 04.05.16
Specifications
Power
• SELV / PELV / NEC
® Class 2
• Operating voltage: 24–36 V- 65 mA
QS Link Limits
• The QS wired communications link is limited to
100 devices and 100 zones. Each QSE-CI-NWK-E
control interface counts as 1 device and 0 zones.
• Each QSE-CI-NWK-E control interface consumes
2 Power Draw Units (PDU) on the QS link. Refer
to the QS Link Power Draw Units Specification
Submittal (P/N 369405) at www.lutron.com for more
information.
• The maximum wiring length for the QS link is 2000 ft
(610 m).
Environment
• 32 °F to 104 °F (0 °C to 40 °C).
• Relative humidity less than 90% non-condensing.
• Indoor use only.
• Unit generates heat, maximum 8 BTU / hr.
Integration Features
• Monitoring: Current scene, zone level, button
presses, shade group levels.
• Control: Scene selection, scene lockout, zone
lockout, sequencing, zone raise / lower, master
raise / lower, set shade group level, simulate button
press/release.
For the full list of features and commands, please
refer to the Integration Protocol document
(P/N 040249) on the accompanying CD or at
www.lutron.com
Compatible Components
• Compatible with most QS devices. For a complete
list of compatible components see Integration
Protocol document (P/N 040249) at www.lutron.com
Requirements
• QS Link Power Supply, such as a:
– GRAFIK Eye
® QS.
– QS Link power supply, such as the QSPS-P1-1-50 .
– Energi Savr Node
TM QS.
• QS Communication Link - SELV / PELV / NEC
® Class 2
(see QS Link Wire Sizes table).
Protocol
• Integration Protocol document (P/N 040249) included
on a CD accompanying the packaged
QSE-CI-NWK-E.
• Also available for download, see Integration Protocol
document (P/N 040249) at www.lutron.com
RS232 Connection
• Standard 9-pin female serial connector on interface.
• 50 ft (15 m) maximum serial cable length.
• Dip switches are set at factory, all Off.
• Dip switches are used to set RS232 baud rate:
DIP Switch Settings for RS232 Baud Rate
115200 (default)
38400
19200
9600
Ethernet Connection
• Standard CAT5 (or better) cable, 328 ft (100 m)
maximum, connects the QSE-CI-NWK-E interface to a
PC or other Ethernet source.
• Supports MDI / MDIX auto-crossover (no crossover
cable needed).
• Auto-negotiation of 10 or 100 Mbps speed and full- or
half-duplex operation.
• Default IP address is 192.168.250.1. Can be changed
using the Lutron
® DeviceIP tool located on the
accompanying CD.
Note: Either the RS232 or the Ethernet can be used,
but not both.