SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 1 04.05.16
QSE-CI-NWK-E Control Interface
The QSE-CI-NWK-E is a versatile integration access
point for Lutron
® QS-based systems. Through either
RS232 or TCP / IP over Ethernet, third-party devices can
control and/or monitor a QS system.
Features
Easily integrate with touchscreens, PCs, A / V systems,
or other digital systems and devices.
Control and monitor GRAFIK Eye
® QS, Sivoia® QS,
Energi Savr Node
TM, and other products on the wired
QS link.
Monitor lighting scenes, levels, shade positions and
more. For a full list of commands see Integration
Protocol document (P/N 040249) at www.lutron.com
Up to 10 QSE-CI-NWK-E control interfaces are allowed
per QS link.
The QSE-CI-NWK-E is Quantum
® compatible. Refer to
the Quantum
® System Specification Sheet (P/N 369634)
at www.lutron.com for compatibility details.
1
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 2 04.05.16
Specifications
Power
SELV / PELV / NEC
® Class 2
Operating voltage: 24–36 V- 65 mA
QS Link Limits
The QS wired communications link is limited to
100 devices and 100 zones. Each QSE-CI-NWK-E
control interface counts as 1 device and 0 zones.
Each QSE-CI-NWK-E control interface consumes
2 Power Draw Units (PDU) on the QS link. Refer
to the QS Link Power Draw Units Specification
Submittal (P/N 369405) at www.lutron.com for more
information.
The maximum wiring length for the QS link is 2000 ft
(610 m).
Environment
32 °F to 104 °F (0 °C to 40 °C).
Relative humidity less than 90% non-condensing.
Indoor use only.
Unit generates heat, maximum 8 BTU / hr.
Integration Features
Monitoring: Current scene, zone level, button
presses, shade group levels.
Control: Scene selection, scene lockout, zone
lockout, sequencing, zone raise / lower, master
raise / lower, set shade group level, simulate button
press/release.
For the full list of features and commands, please
refer to the Integration Protocol document
(P/N 040249) on the accompanying CD or at
www.lutron.com
Compatible Components
Compatible with most QS devices. For a complete
list of compatible components see Integration
Protocol document (P/N 040249) at www.lutron.com
Requirements
QS Link Power Supply, such as a:
– GRAFIK Eye
® QS.
– QS Link power supply, such as the QSPS-P1-1-50 .
– Energi Savr Node
TM QS.
QS Communication Link - SELV / PELV / NEC
® Class 2
(see QS Link Wire Sizes table).
Protocol
Integration Protocol document (P/N 040249) included
on a CD accompanying the packaged
QSE-CI-NWK-E.
Also available for download, see Integration Protocol
document (P/N 040249) at www.lutron.com
RS232 Connection
Standard 9-pin female serial connector on interface.
50 ft (15 m) maximum serial cable length.
Dip switches are set at factory, all Off.
Dip switches are used to set RS232 baud rate:
DIP Switch Settings for RS232 Baud Rate
115200 (default)
38400
19200
9600
Ethernet Connection
Standard CAT5 (or better) cable, 328 ft (100 m)
maximum, connects the QSE-CI-NWK-E interface to a
PC or other Ethernet source.
Supports MDI / MDIX auto-crossover (no crossover
cable needed).
Auto-negotiation of 10 or 100 Mbps speed and full- or
half-duplex operation.
Default IP address is 192.168.250.1. Can be changed
using the Lutron
® DeviceIP tool located on the
accompanying CD.
Note: Either the RS232 or the Ethernet can be used,
but not both.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
2
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 3 04.05.16
Dimensions
Dimensions are in inches (mm)
2.5
(63)
3.75
(95)
4.25
(108)
5.25
(134)
1.0
(27)
Mounting holes
Terminal
blocks
on this side
LEDs and addressing
switches on this side
0.3125
(9) dia.
0.1875 (5)
dia.
0.1875
(5) dia.
0.25
(6)
#6 or #8 (M3 or M4)
screw recommended
Mounting Hole Detail
Mounting Options
Mounting Methods
LUT-19AV-1U
2
LUT-5x10-ENC
Control Interface
Wall
1
3
Mount where terminal blocks, switches, and LEDs
are accessible. Strip 3/8 in (10 mm) of insulation
from wires. Each data link terminal will accept up
to two 18 AWG (1.0 mm
2
) wires. Connect wiring as
shown on the Wiring page. LED 1 lights
continuously (Power) and LED 7 blinks rapidly
(Data Link RX) when the SELV / PELV / NEC® Class
2 Data Link is installed correctly. Choose from the
following mounting methods:
1 Direct Wall Mounting
Mount the control interface directly on a wall, as
shown in Mounting Methods at right, using screws
(not included). When mounting, provide sufficient
space for connecting cables.
2 Rack Mounting
Place the unit in the LUT-19AV-1U AV rack using
screws provided with the unit. The LUT-19AV-1U
will hold up to four units.
3 Enclosed Wall Mounting
If conduit is desired for wiring, use the
LUT-5x10-ENC to mount one unit.
3
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 4 04.05.16
Terminal Locations
LED and DIP Switch Locations
Ethernet Link
(to PC or AV
Equipment
Female 9-pin
RS232 Link (to
PC or AV
Equipment)
QS Link to
other wired
QS system
Devices
DIP Switches
LED 1: Power
LED 2: Ethernet Activity
LED 3: Unused
LED 4: RS232 Link Tx
LED 5: RS232 Link Rx
LED 6: QS Link Tx
LED 7: QS Link Rx
1 2 3 4 5 6 7
4
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 5 04.05.16
Wiring
RS232 Link
Standard 9-pin serial connector plugs into RS232
equipment, and to QSE-CI-NWK-E.
Must be 50 ft (15 m) or less.
RS232 Signals
Signals Pin on 9-Pin Cable
Com 5
TxD 3
RxD 2
1234
12
ABC
123456LN
4321
To additional QS devices
RS232 Cable
50 ft (15 m)
max.
Ethernet Link: CAT5 Cable: 328 ft (100 m) max.
COM
TxD
RxD
RS232 Link
To PC or AV
Equipment
Rear View of GRAFIK Eye® QS Control Unit
QS Link:
1: Common
2: V+
3: MUX
4: MUX
See next page.
Do not connect Pin 2 if using
external power supply.
QS Link
Ethernet Link Wiring
Standard CAT5 cable connects QSE-CI-NWK-E
Interface to PC, router, or other Ethernet source.
No crossover cable needed.
Must be 328 ft (100 m) or less.
Ethernet network and cable provided by others.
5
R
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373e 6 04.05.16
4321
Wiring (continued): QS Link Wiring Methods (choose one)
Powered by GRAFIK Eye® QS Control Unit
Powered by a QS Link Power Supply*
1234
12
ABC
123456LN
4321
To additional wallstations/
control interfaces
To additional wallstations/
control interfaces
Rear View of GRAFIK Eye
® QS
Control Unit
PDU supplying device
GRAFIK Eye
® QS
Control Unit shown
QS
Link
QS
Link
QS Link
1: Common
2: V+
3: MUX
4: MUX
Data Link:
4: MUX
3: MUX
See QS Link
Wire Sizes table
SELV / PELV / NEC® Class 2 Power wiring:
2: V+
1: Common
See QS Link Wire Sizes table
System communication uses SELV / PELV / NEC®
Class 2 wiring. Follow all local and national electrical
codes for installation.
Each terminal accepts up to two 18 AWG (1.0 mm²)
wires or one 12 AWG (4.0 mm²) wire.
Total length of control link must not exceed 2000 ft
(610 m).
Do not allow SELV / PELV / NEC
® Class 2 wires to
contact live / mains wire.
Typical Wire Sizes: See QS Link Wire Sizes table.
Connect the terminal 1, 3, and 4 connections to all
control units, wallstations, and control interfaces in the
QS system. For terminal 2 connectivity, see below.
Lutron® Cable
See QS Link Wire Sizes table
QS Power Supply*
(1) 18 AWG
(1.0 mm
2
)
Common
(1) twisted pair
22 AWG
(0.5 mm
2
)
QS Link Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge Lutron Cable Part Number
< 500 ft (153 m)
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
500 ft–2000 ft
(153 m610 m)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
2
)
GRX-CBL-46L
(non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
Do not use
external
power supply
if connecting
Pin 2
Do not use external power
supply if connecting Pin 2
* Note: For details regarding powering from the QS Link, please
refer to the QS Power Draw Units Specification Submittal
(P/N 369405) at www.Lutron.com
6