SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 1 06.04.2014
Ultrasonic Ceiling Mount Sensor
The LOS-CUS Series ultrasonic ceiling-mount sensors
can integrate into LutronR systems or function as
stand-alone controls using a LutronR power pack.
Any movement within the range of the sensor causes
a shift in the original emitted frequency. The receiver
on the sensor identifies any change in frequency as
motion and either turns the lights on or keeps the
lights on.
Features
• Intelligent, continually adapting ultrasonic sensor
• Snap-locks to ceiling-mounted cover plate
• Excellent minor motion sensitivity
Non-Volatile Memory: settings saved in protected
memory are not lost during power outages
500 ft( to 2000 ft( (46 m( to 186 m() coverage when
mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling
Affords choice of turning lights off or dimming to a
preset level in the unoccupied state when integrated
with a LutronR system.
Models Available
Model Color Coverage Field of View
LOS-CUS-500-WH White 500 ft( (46m() 180°
LOS-CUS-1000-WH White 1000 ft( (93m() 180°
LOS-CUS-2000-WH White 2000 ft( (186m() 360°
NOTE: BAA-compliant model numbers available. Add a “U” prefix
to the model number.
Self-Adaptive Feature
Designed to meet the challenges found in a wide
variety of spaces, the LOS-CUS Series sensors
provide reliable detection with high minor motion
detection. The intelligent, continually adapting sensor
technology eliminates manual sensitivity and timer
adjustments during installation and over the life of
the product. The internal microprocessor analyzes
the information from the ultrasonic technology and
determines the optimum setting to use in order
to properly cover the space. Should the room be
reconfigured (e.g. new furniture), the software will
adapt to continue to provide correct time out for the
lights.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 2 06.04.2014
Specifications
Dimensions
Front View
4.5 in
(114 mm)
1.4 in
(38 mm)
Side View
Regulatory Approvals
• ULR and cULR listed
Power
• Operating voltage: 20 – 24 V-, IEC PELV/NECR
Class2
• Operating current: 33 mA nominal
• Control output: 20 – 24 V- active high logic control
signal with short-circuit protection, open collector
when unoccupied
Environment
• Temperature: 32 °F to 104 °F (0 °C to 40 °C)
• Relative humidity: less than 95%, non-condensing
• For indoor use only
Timer Adjustment
• Automatic mode: Continually adapting sensor
automatically adjusts settings to the space
• Manual mode: 8 to 30 minutes
• Test mode: 8 seconds
LED Lamp
• Green: ultrasonic motion detected
Housing
• Rugged, high-impact, injection-molded plastic
• Color-coded leads 6 in (15 cm)
Adaptive Functions
Installation: 60 minutes
Learning: 4 weeks for response to error conditions, air
current adaptation, and timer optimization
• Post-learning occupancy periods
—24 hour circadian occupancy periods learned
—Weekly occupancy periods learned
• Adjustments in post-learning period
Generally occupied periods
(threshold = high-sensitivity mode)
Generally unoccupied periods
(threshold = miser mode)
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 3 06.04.2014
Power packs may be required when interfaced to LutronR lighting control systems. If more than 1 occupancy
sensor is connected to the same input, a power pack is required. A maximum of 3 occupancy sensors can be
connected to the same input. If more than 3 sensors are required per input, use one of the following models:
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, or LOS-CDT-2000R-WH.
Power Supply Options
LutronR Lighting Control System Power Pack Required?
Digital microWATTT No
EcoSystemR No
Energi Savr NodeT No*
GRAFIK 5000T/6000R/7000T No, when used with seeTouchR wallstations with occupancy sensor
connections.
GRAFIK EyeR 3000/4000 Yes
GRAFIK EyeR QS No*
HomeWorksR Yes
HomeWorksR QS No*
LCP128T No, when used with seeTouchR wallstations with occupancy sensor
connections.
microWATTR No
QuantumR No*
RadioRAR Yes
RadioRAR 2 Yes
Softswitch128R No, when used with seeTouchR wallstations with occupancy sensor
connections.
Wiring: System Control
* Some system components do not supply external power for occupancy sensors. Refer to individual product
specifications for more information.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 4 06.04.2014
Neutral
Power
Pack
Lighting
Load
NOTE: Maximum 3 occupancy sensors.
Red (+20 – 24 V-)
Blue (signal)
Black
(common)
Black
White
Red
Red
1 to 3 Sensors with Power Pack
Switching Multiple Loads with Auxiliary Power Packs
Line
Neutral
Line
Lighting
Load
Lighting
Load
Power
Pack
Auxiliary
Power
Pack
Red
Red
Red (+20 – 24 V-)
Blue (signal)
Black
(common)
NOTE: Maximum of 3 devices total (occupancy sensors and auxiliary power packs) can be connected to a power pack.
Black
White
Red
Red
120 / 277 / 347 V~ 60 Hz;
230 V~ 50 / 60 Hz
120 / 277 / 347V~ 60 Hz
230 V~ 50 / 60 Hz
Wiring: Stand-Alone Control
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 5 06.04.2014
Installation
LOS-CUS-500
LOS-CUS-2000
64 ft (19.5 m)
45 ft (13.7 m)
23 ft
(7 m)
32 ft
(9.8 m)
Sensor Placement
Range Diagrams
• Mount the sensor so the grilles face the open portion of the room and are not facing a nearby wall, window, or
other obstructing object.
• Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause false
triggering.
• If installing a 180° occupancy sensor (500 and 1000 models), place the sensor on the same wall as the doorway
so that traffic in a hallway will not affect the sensor; otherwise, place in center of room.
• Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect major
motion (e.g. person taking a half-step) at a greater distance than it can detect minor motion (e.g. writing at a
desk or reading a book).
• Decrease total coverage area by 15% for “soft” rooms (e.g. heavy draperies or thick carpeting).
23 ft (7 m)
16 ft (4.9 m)
16 ft
(4.9 m)
23 ft
(7 m)
32 ft (9.8 m)
23 ft (7 m)
23 ft
(7 m)
32 ft
(9.8 m)
LOS-CUS-1000
Sensor Setup
• Sensor setup is available as a service by Lutron. For more information see the Sensor Layout and Tuning
service document (LutronR P/N 3601235).
Major motion detection
Minor motion detection
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 6 06.04.2014
Mounting
Normal Mounting
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using
cutter end of the threaded mounting post. Secure
with washer and nut.
Cutter
end
Mounting to Non-Standard Ceiling or Fixture
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.
Mounting Plate Dimensions
4.2 in
(106.6 mm)
2.5 in
(63 mm)
0.52 in
(13.3 mm)
13/16 in (21 mm)
Wire Lengths
Number of Sensors 1 2 3 1 2 1
Number of Auxiliary
Power Packs
0 0 0 1 1 2
22 AWG 750 ft 375 ft 250 ft 375 ft 250 ft 250 ft
0.5 mm( 365 m 180 m 120 m 90 m 120 m 120 m
20 AWG 1200 ft 600 ft 400 ft 600 ft 400 ft 400 ft
0.75 mm( 730 m 365 m 240 m 365 m 240 m 365 m
18 AWG 2400 ft 1200 ft 800 ft 1200 ft 800 ft 800 ft
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Sensors LOS-CUS Series Occupancy Sensors
369651d 7 06.04.2014
Off (Default) On
Automatic (Normal) Manual on / off (Override)
Auto Threshold Adjustment High Sensitivity (Low turn-on threshold)
Lights indicate motion
Disable LED Indicator
Retain Settings (Normal) Erase all learned settings; Restart Learning (Toggle On)
Sensor Adjustments
Timer Test Mode
Factory Settings
1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to about
midway (12 o’clock).
3. Return setting to minimum setting (full CCW).
NOTE:
The timer will remain in the 8 second test
mode for 1 hour, then automatically reset to 8minutes.
4. To manually take the timer out of the 8 second test
mode, turn the timer adjustment approximately 1/16in
(1.5 mm) clockwise to make the setting slightly above
minimum (just above the 8 minute setting).
Factory Settings 12 o’clock
Full CCW
Auto/Manual
Threshold
LED Motion Indicator
Reset Learned Settings
Strong Airflow Compensation
Over Doorway Installation
Timer Adjust
Auto Sensitivity
ONOFF
ONOFF
ONOFF
ONOFF
A
1
2
3
4
B
1
2
3
4
Override Settings
ON
ON
A
1
2
3
4
B
1
2
3
4
Black:
Timer
8 minutes
Green:
Ultrasonic range
50% default
Off (Default) On
Disable Compensation (Normal) Enable Compensation
No (Normal) Yes (Use increased turn-on threshold)
Adjust Timer Automatically Use Manual Setting (No adjustment)
Adjust Sensitivity Automatically Adjust Sensitivity Manually
7