Specifications
Power
•230V
50/60 Hz
•LightningstrikeprotectionmeetsANSI/IEEEstandard
62.31-1980. Can withstand voltage surges of up to
6 000 V
and current surges of up to 3 000 A.
•Currentdraw:50mAmax
•Standbypower:1W
•BTUs/hourwhenfullyloaded:4
Output Zone Ratings
•Eachzoneisratedat10AXforswitching.Ratedforre-
sistive, capacitive, or inductive lighting loads as defined
byIEC/EN60669-2-1.
• Switched outputs utilize latching relays to maintain
relay state if control power is lost.
• 0-10Vratedfor50mAmaximumoutput,sourceor
sinkperzone.
Standards
•IEC/EN60669-2-1,EN50428
•LutronQualitySystemsregisteredtoISO9001:2008
•CE
•C-TickS
Environment
•AmbientTemperatureOperatingRange(inside
mounting panel): 0 ºC to 40 ºC
•Calibrationpointmaximum:65ºC
•Relativehumidity:lessthan90%non-condensing
•Forindooruseonly
Terminals
•Mainswiring:0,5mm
2
to 6,0 mm
2
•0-10VWiring:0,5mm
2
to 2,5 mm
2
•CCIWiring:0,5mm
2
to 6,0 mm
2
•Zonewiring:0,5mm
2
to 6,0 mm
2
Mounting
•UseanIP20(minimum)ratedconsumerpanelor
breakerpanelwithintegratedDINrail
•Width=9modules(161,7mm)
Programming and Compatibility Requirements
•LQSE-4T10-DandLQSE-4S10-Dcanonlybeused
withtheHomeWorksRQS system.
•SetupandprogrammingoftheDALIR Power Module
isdonethroughtheHomeWorksRQS programming
software.
•HomeWorks
®QS software version 3,0 or higher
required.
HomeWorksR QS Wallstations
•HomeWorksR QS wallstations can be configured to
control Power Modules withtheHomeWorksR QS
programming utility.
•LEDindicatordisplaysthestatusofprogrammedlights.
QS Link Limits
•AQSlinkinaHomeWorksR QS system can have up to
512 zones (outputs) and 100devices.
•EachPowerModulecountsasonedevicetowardthe
100 device limit.
Manual Mode Operation
•Zonebuttons:
— selects zone to control
•Raise/Lowerbuttons:
— turns loads on and off
— dim loads up and down (LQSE-4T10-D only)
NOTE:Program,Input,andOptionbuttonsarenot
used in LQSE models.
Contact Closure Input (CCI)
•TheCCIbehavesasaManualOverrideClosureInput.
•IftheCCIisopen,thePowerModuleunitwillenter
ManualOverrideMode,whichwillturnonallloads
and disable control from other devices.
•WhentheCCIisclosedorjumpered(factorydefault),
Power Module unit zones will return to the settings or
levelstheywereatpriortoenteringManualOverride
Mode.