SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Quantum QSW-GGL-PP-A Software
369506c 1 03.22.19
GreenGlance software allows real-time and historical
Lutron lighting energy data to be displayed on an LCD
display or a computer terminal.
The screen displays lighting energy savings compared
to a full-on state, and equivalent savings expressed in
terms of coal not burned and CO2 not emitted. Data is
organized into a graphical format intended for public
viewing.
The computer display allows the user to select the time
period to be displayed for historical data. The LCD
display will display predefined views from user-selected
configurations.
Instantaneous Power Savings
GreenGlance compares the full-on state of lighting
loads to the instantaneous levels continuously reported
by the system. The comparison is displayed in a graph
form showing the percentage of instantaneous power
saved.
Historical Time Periods:
• 3 hour energy savings
• 1 day energy savings
• 1 week energy savings
• 1 month energy savings
• 1 year energy savings
• Compare historical periods (days, weeks, months, years)
Energy Savings Over Time Period Displayed in:
• KWh saved
• Dollars saved
• CO2 not emitted
• Coal not burned
Other Data Displayed
• Local weather conditions (internet connection required)
• Project specific information (entered by user in Q-Admin)
• Baseline for energy savings assumes lighting to be
full-on for 24/7
Information Displayed:
• Languages: U.S. English, French, Spanish, German,
Simplified Chinese.
• Currencies: U.S. Dollar, Euro, British Pound
Requirements
• Quantum light management system
• Lutron Q-Manager server (can be supplied by Lutron
or by customer)
• GreenGlance client PC must meet minimum
specification of Lutron model QS-A-CMP-DBO-0.
• User-supplied GreenGlance display with a minimum
resolution of 1024 x 768 (provided by others).
Licenses Required
• Model number: QSW-GGL-PP-A
- One GreenGlance license required for each
Quantum processor in the system.
• Model number: QSW-RPT-PP-A
- One Q-Reporting license required for each
Quantum processor in the system.
• Model number: QSW-L-PP-A
- One Q-Admin lighting license required for each
Quantum processor in the system.
Notes
• Maximum 6 concurrent GreenGlance displays.
• The GreenGlance software can display energy
savings using Quantum energy meters. For more
information, refer to the Quantum Class 500 Energy
Meter spec submittal (Lutron P/N 369490) or contact
your Lutron representative.
Quantum GreenGlance* Software
* GreenGlance is not available in Quantum 3.4 and above.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Quantum QSW-GGL-PP-A Software
369506c 2 03.22.19
Input:
2 A 120-240 V~ 50/60 Hz
Output:
2 A
24 V --- (IEC PELV/NEC Class 2)
Entree:
2 A 120-240 V~ 50/60 Hz
Sortie:
2 A
24 V --- (IEC PELV/NEC Class 2)
Entrada:
2 A 120-240 V~ 50/60 Hz
Salida:
2 A 24 V --- (IEC PELV/NEC Class 2)
Entrada:
2 A 120-240 V~ 50/60 Hz
Saida:
2 A 24 V --- (IEC PELV/NEC Class 2)
QP3-1PL-100-240
Type 1
Enclosure
®
®
®
®
Input:
2 A 120-240 V~ 50/60 Hz
Output:
2 A
24 V --- (IEC PELV/NEC Class 2)
Entree:
2 A 120-240 V~ 50/60 Hz
Sortie:
2 A 24 V --- (IEC PELV/NEC Class 2)
Entrada:
2 A 120-240 V~ 50/60 Hz
Salida:
2 A 24 V --- (IEC PELV/NEC Class 2)
Entrada:
2 A 120-240 V~ 50/60 Hz
Saida:
2 A 24 V --- (IEC PELV/NEC Class 2)
QP3-1PL-100-240
Type 1
Enclosure
®
®
®
®
GreenGlance client PC
Video signal
Internet connection required
for weather information
User-supplied
GreenGlance display
Corporate LAN
or VLAN
Internet
Q-Manager lighting
management server
Quantum lighting management hubs
Optional Quantum Class
500 Energy Meter
LAN or VLAN for server to lighting hub communication
Lutron, Lutron, Quantum, GreenGlance, Q-Admin, and Q-Manager are trademarks or registered trademarks of Lutron Electronics Co., Inc.
in the US and/or other countries.
2