SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Quantum QSW-DEM-PP-A Software
369551c 2 03.22.19
Features
• The software allows the user to schedule and perform Functional Tests and Duration Tests for all DALI
Emergency devices that are part of the system.
· Functional Test - verifies that the DALI emergency devices are communicating with the system properly,
checks for lamp failures and verifies that the battery circuit is functional
· Duration Test - verifies that the batteries attached to the DALI emergency devices operate within their rated
limits
• The user can group the DALI emergency devices into 1 of 7 Emergency Groups.
• The user can define the day of the week that each Emergency Group will be tested.
• The user can schedule Functional Tests to occur Weekly, Bi-Weekly or Monthly. In addition, Functional Tests can
be manually initiated at any time.
• The user can schedule Duration Tests to occur Monthly, Quarterly, Bi-Annually or Annually. In addition, Duration
Tests can be manually initiated at any time.
• The user can configure the Prolong Time for all DALI Emergency devices in the system. The Prolong Time is the
amount of time that the DALI Emergency devices will stay at their emergency light level after an emergency event
has ended and normal power has been restored.
• The system software is designed to work with emergency devices that have a maximum battery life of 3 hours.
Contact Lutron if the battery life of your fixtures exceeds 3 hours.