SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Pico® PX Series Wired Control
369439d 2 08.21.12
Specifications
Regulatory
•
Designed for IEC PELV/NECR Class 2 operation only
•
Complies with requirements of NFPA 70, of the
National Electrical CodeR IEC PELV/NECR Class 2
device wiring
•
Install according to all applicable national and local
wiring regulations
•
For regions requiring ULR listing on low-voltage devices,
install in a fully enclosed wallbox. Low- voltage wallboxes
are acceptible for regions that do not require ULR listing
on low-voltage devices
Power
•
Do not exceed 35 V-
•
Operating Voltage: 20 V- (IEC PELV/NECR Class 2)
•
Current Draw: 20 mA maximum
System Communication and Capacity
•
Total wire length from control to device must not
exceed 500 ft (152 m)
•
Not a wireless device
Mounting
•
Mounts easily in any single-gang wallbox (not included)
•
Lutron suggests using LutronR ClaroR wallplates to
ensure proper compatibility. Wallplates sold serparately.
PicoR Wired control may not be compatible with non-
LutronR wallplates, test fit non-LutronR parts before use.
Environment
•
Temperature: 32 ºF to 104 ºF (0 °C to 40 °C)
•
Relative Humidity: Less than 90% non-condensing
Wiring
•
PicoR Wired control does not receive IR input from
hand-held transmitters
•
PicoR Wired control does not connect to QS Link
•
A PicoR Wired control can only be wired to a single
control module or a single sensor interface
•
Each input on a control module or sensor interface can
be connected to only one control or one input device
Warranty
1-year limited warranty
For additional Warranty information, please visit
www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
Red = 20 V-
Black = Common
White = IR Signal (IR input terminal of ballast or module)