SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 1 08.18.11
Energi Savr NodeT for EcoSystemR
The Energi Savr NodeT unit is a DIN-rail mounted
Eco Link controller for EcoSystemR ballasts, drivers
and devices. It provides Eco Link power and control
for two independent Eco Links with up to 64 ballasts
each. The Energi Savr NodeT unit also provides
direct connections and power for the following
LutronR devices:
•Occupancysensors
•Daylight sensors
•IR receivers
•QS devices
Features
•ProvidesEcoSystemR Link power for either one
or two links of EcoSystemR ballasts or drivers
(up to 250 mA per link).
•Powerfailurememoryretainscontrolunitprogram-
ming in the event of a power loss.
•Defaultcongurationrequiresnocommissioning.
•Fouroccupancysensorinputsforautomatedcontrol
of lights in areas.
•Fourdaylightsensorinputsautomaticallyadjustlight
levels based on the amount of natural light entering
through the windows.
•FourIRreceiverinputsforpersonalcontrolor
compatible LutronR IR wallstation controls.
•Addmoreoccupancysensors,daylightsensors,or
IR receivers by connecting QS Sensor Modules
(QSMs).
•IncludesQSlinkforseamlessintegrationoflights,
motorized window treatments, control stations, and
QS Sensor Modules.
•EnergiSavrNodeT units and QS Sensor Modules
can be used in a QuantumR system to control and
manage light in an entire building.
LUTRON
LUTRO
N
R
LUTRON
LUTRON
R
Up to 64
ballasts on
each loop
QS Link
Eco Link 1
Eco Link 2
Ballast
Ballast
Energi Savr
NodeT unit
Energi Savr
NodeT unit
QuantumR
Panel
GRAFIK
EyeR QS
QS
Contact
Closure
Interface
seeTouchR QS
Wallstation
Ballast
Ballast
230 V
ControlPower
Up to 100
total QS
devices
Ethernet
ProgrammingLink
Oneinputgroupshown;
connections available for
up to four input groups.
Wireless
Communication
QSM
RadioPowrSavrTM
OccupancySensor
(up to 10 per QSM)
RadioPowrSavr
TM
Daylight Sensor
(up to 10 per QSM)
Pico
® Wireless
Controller (up
to 10 per QSM)
Wired
Daylight
Sensors*
Wired
Occupancy
Sensors*
Wired
IR Receivers*
* Up to 4 wired sensors total (of any type)
Note: Multiple QSMs can be added
to increase the number of
wirelesssensorsandPicoR
wireless controllers.
IR Transmitter
IR Transmitter
Wired IR Receiver
Wired Daylight
Sensor
WiredOccupancy
Sensor
QS
Power
Supply
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 2 08.18.11
Typical Application: Requires commissioning
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
OpenOfces Corridor PrivateOfces
seeTouch® QS Wallstation
seeTouchR QS Wallstation
QS Link
QS Link
QS Link
WindowWindowWindow
Eco
Link
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Occupancy
Sensor
Energi Savr
NodeT
unit
Energi Savr
NodeT
unit
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Wired to
input groups
Wired to
input groups
Occupancy
Sensor
Occupancy
Sensor
Eco
Link
Eco
Link
Eco
Link
Eco
Link
Eco
Link
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 3 08.18.11
LUTRON
LUTRON
Preconfigured Mode 2
Two Zones with Occupancy Sensors
* Six fixtures shown on each Link, however,
up to 64 fixtures can be connected per Link.
Preconfigured Mode 1
Perimeter Daylighting
* Four fixtures shown on Link 1 and eight
fixtures shown on Link 2, however, up to
64 fixtures can be connected per Link.
Occupancy Sensor Daylight Sensor
Connected to input group 1 Controls Link 1 only Controls Link 1 only
Connected to input group 2 Controls Link 2 only Controls Link 2 only
Connected to input group 3 Controls both Links ControlsbothLinkswithequaldaylightsetting
Connected to input group 4 Controls both Links ControlsbothLinkswithequaldaylightsetting
Default Behavior for Sensor Connections
Simple Applications: Preconfigured modes require no commissioning
Troubleshooting and Maintenance Features
•Maintainsredundantmemoryofballastprogrammingforeaseofsingleormultipleballastreplacement.
•Afterinstallation,“TEST”buttonveriesEcoLinkwiringonallxtures
•StatusLEDsverifyconnectionstocontrolstationsandsensors.
•Afterinstallation,EnergiSavrNodeT unitidentiesballastcommunicationfailures.
Perimeter PerimeterInterior Interior
Window
Window
Window
Window
Daylight
Sensor
Daylight
Sensor
Wired to
input
group 4
Wired to
input
group 2
Wired to
input
group 1
Wired to
input
group 2
Wired to
input
group 1
Energi Savr
NodeT
unit
Energi Savr
NodeT
unit
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Link 1
Link 1
Link 2
Link 2
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 4 08.18.11
Specifications
Power
•230V~ 50/60 Hz, 100 mA
•LightningstrikeprotectionmeetsANSI/IEEEstandard
62.31-1980. Can withstand voltage surges of up to
6 000 V~ and current surges of up to 3 000 A.
•EcoLinkOutput:18V- 250mAmaximumperLink.
Standards
•IEC60669-2-1
•LutronQualitySystemsregisteredtoISO9001.2008.
Environment
•AmbientTemperatureOperatingRange:0ºCto40ºC.
•Relativehumidity:lessthan90%non-condensing.
•Forindooruseonly.
Terminals
•Mainswiring:1,0mm
2
to 4,0 mm
2
•EcoLinkWiring:1,0mm
2
to 4,0 mm
2
•QSLinkWiring:0,5mm
2
to 4,0 mm
2
•InputWiring:0,5mm
2
to 2,5 mm
2
Mounting
•IntendedtomountwithinanIP20(minimum)rated
consumer panel or breaker panel with integrated
DIN rail and dead cover
•Width=9DINmodules(161,7mm).
Programming Requirements
•AnApple iPod touch or iPhone mobile digital
devicewiththeEnergiSavrappisrequiredfor
programming Energi Savr NodeT systems.
•TheEnergiSavr app is available from the AppStore
online store.
•TheEnergiSavr app cannot be used to program the
Energi Savr NodeT units when installed as part of a
Quantum
® system.
•TheApple iPod touch or iPhone communicates
with the Energi Savr NodeT unitviaaWiFirouter
(not included).
•See“Wiring:SystemProgrammingConnection”
section for further information.
EcoSystemR
•Controlupto64EcoSystemR-compatible devices (bal-
last, modules, or LED drivers) per EcoSystemR Digital
Link (up to 128 devices per Energi Savr NodeT with
EcoSystemR unit):
— EcoSystemR ballasts and modules
— EcoSystemR H-Series ballasts
— Hi-lumeR 3D ballasts
— Hi-lumeR LED drivers
— Hi-lumeR A-Series LED drivers
•Digitallydeneareasandzones.
•Congurewiredorwirelesssensorsandcontrolsto
control devices on multiple EcoSystemR Digital Links
and/or multiple Energi Savr NodeT units.
•Automaticreplacementofasinglefailedballast,
module, or driver.
•Simplemethodofreplacingmultiplefailed
ballasts, modules, or drivers.
•EcoSystemR Digital Link can be wired as Mains volt-
ageorIECPELVformaximumwiringexibility.
QS Link Limits
•AQSlinkcanhaveupto100zones(outputs),100
devices and 512 ballasts.
•EachEnergiSavrNodeT unit counts as one device
toward the 100 device limit.
•Eachassignedzonecountstowardthe100zonelimit
(up to 512 zones in a Quantum
® system).
•EachEnergi Savr NodeT(QSNE-2ECO-D)unitcan
supply 3 power draw units. RefertotheQSLinkPower
DrawUnitsspecificationsubmittal(LutronP/N369405)
formoreinformationconcerningPowerDrawUnits.
•Amaximumof8EcoSystemR digital links may be
connected to the QS link.
QS Link Sensor Limits:
•100wiredorwirelessoccupancysensors.
•100wiredorwirelessdaylightsensors.
•100wiredwallstationsorPico
® wireless controllers.
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredin
the U.S. and other countries. AppStore is a service mark of Apple Inc.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 5 08.18.11
Sensors Connected to the
Energi Savr NodeT Unit
•PowerSupplyOutputs(4)
— 20 V-50mAmaximum.
—Anauxiliarypowersupplymustbeusedifthe
devicerequiresmorethan50mA.
Occupancy/Vacancy Sensors
•Use vacancy sensors to automatically turn the lights
offinanareaaxedtimeafteritbecomesvacant.
•Use occupancy sensors to automatically turn the
lights on in area when it becomes occupied and
toautomaticallyturnthelightsoffinanareaaxed
time after it becomes vacant.
•Fouroccupancysensorscanconnectdirectlytothe
Energi Savr NodeT unit.
•Each area's occupied level and unoccupied level
can be programmed.
•Occupancysensormustprovideadrycontact
closure or solid-state output.
Daylight Sensors
LutronR daylight sensors allow daylight harvesting
with programmable gain settings in up to four gain
groups per area.
•Fourdaylightsensorscanconnectdirectlytothe
Energi Savr NodeT unit.
Infrared Receivers
•UseLutronR IR receivers for personal control of
individual lighting zones.
•FourIRreceiverscanconnectdirectlytothe
Energi Savr NodeT unit.
Other QS System Components
QSM (QS Sensor Module) - Integrating Wired and
Wireless Inputs
•UsetheQSMtointegrateRadioPowrSavrT
Occupancy/Vacancysensors,RadioPowrSavrT
Daylightsensors,andPico
® Wireless Controllers to
control zones on the Energi Savr NodeT unit.
•Assignupto10RadioPowrSavrTOccupancy/
Vacancy sensors per Energi Savr NodeT unit via QSM.
•Assignupto10RadioPowrSavrT Daylight sensors
per Energi Savr NodeT unit via QSM.
•Assignupto10Pico
® Wireless Controllers per
Energi Savr NodeT unit via QSM.
•Addadditionalwiredandwirelessinputsbyadding
QS Sensor Modules to the QS link.
Wire and power up to 4 wired inputs (of any type) total
— Daylight sensors
—Occupancysensors
— Infrared (IR) receivers
•TheRadioPowrSavrTsensorsandPico
® Wireless
Controllers associated with the QSM should be
mounted within 18 m line of sight, or 9 m through
walls, of the QSM.
•RefertoQSMSpecicationSubmittalformore
information.
seeTouchR QS Controls
•seeTouchRQSwallstationscanbeconguredto
control Energi Savr NodeT unit zones.
•Selectoneof16scenesandoffinEnergiSavrNodeT
unit areas.
•ControlindividuallightingzonesinEnergiSavrNodeT
unit areas.
•EachEnergiSavrNodeT unit can power up to three
seeTouchR QS controls.
•LEDindicatordisplaysthestatusofprogrammedlights.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 6 08.18.11
Other QS System Components
Communication with GRAFIK EyeR QS control
units
•EnergiSavrNodeTunitzonescanbeconguredto
respondtoGRAFIKEyeR QS scene changes, such
as scene button presses and timeclock events.
•EnergiSavrNodeTareascanbeconguredto
respond to scene commands initiated by
GrakEye
® QS astronomic time clock.
•EnergiSavrNodeT unit operates in afterhours mode
whenassociatedwithaGRAFIKEyeR QS that is in
afterhours mode.
Communication with QSE-IO
•EnergiSavrNodeT unit zones respond to scene
commandsinitiatedbytheQSE-IOinscene
selection mode or occupancy sensor mode.
•EnergiSavrNodeTunitcanbeconguredto
respond to zone toggle or occupancy sensor
commandsinitiatedbytheQSE-IOinzonetoggle
mode or occupancy sensor mode.
Communication with QSE-CI-NWK-E
•IntegrateEnergiSavrNodeT units with touchscreens,
PCs,A/Vsystemsorotherdigitalsystemsand
devices.
EcoSystemR Digital Link Limits
•Upto64EcoSystemR-compatible uorescentballasts
and/or LED drivers per EcoSystemR digital link.
•Sensorandcontrolcommunicationlimits
— 16 daylight sensors
— 32 occupancy sensors
— 64 infrared (IR) receivers or wallstations
A sensor or control counts as a device on the
EcoSystemR digital link if it is wired to an EcoSystemR
ballast on the same link, or is programmed to
communicatewithauorescentballastorLED
driver on the EcoSystemR digital link.
•EcoSystemR-compatibleuorescentballastsandLED
drivers on the EcoSystemR digital link do not count as
QS devices.
Note: 16 daylight sensors can communicate to
a given EcoSystemR digital link, up to 32
daylight sensors for a 2-link unit.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 7 08.18.11
Mechanical Dimensions
161,7mm
(6,36 in)
60,6 mm
(2,39 in)
500-13431 Rev. B
N1771
Z096
89,7mm
(3,53 in)
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 8 08.18.11
Overview of Wiring Terminals
Mains
Wiring
Eco
Link 1*
Eco
Link 2*
QS
Link
Inputs
Ethernet
Programming
Port
* Wire according to local codes.
PELV
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 9 08.18.11
Wiring: Mains Voltage
Wiring from Distribution to Link Supply
•Turnoffbreakeratdistributionpanel.
•Runlive,neutral,and
wires from a
230 V~ 50/60 Hz feed to the
Energi Savr NodeT unit.
Emergency Lighting Applications
•Usenormal(non-essential)poweronlytopower
the Energi Savr Node.
•Whennormalpowerdropsout,the
Energi Savr NodeT unit will not power the
Eco Links. When this occurs, ballasts powered
from emergency feeds go to their emergency
mode, full light output by default.
Mains Wiring and Low Voltage Separation
•TheEnergiSavrNodeT unit is designed to
separatemainswiringfromIEC/PELVcircuits.
•Followappropriatelocalandnationalcodesto
avoidviolatingrequiredseparationguidelines.
N
L
N
L
Distribution
Panel
– Earth/Ground
– Neutral
– Mains/Live
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 10 08.18.11
Wiring: Eco Link
The Energi Savr NodeT unit will supply power to two
independentEcoLinks,whichsupportamaximum
of 64 ballasts per link.
Eco Wiring
•EcowiringisnotSELV.
•Ecowiringistreatedasmainsvoltage,andthusmay
be run within the same sheathing.
•Consultallnationalandlocalelectricalcodesfor
separationrequirements.
Wire Cross-
Sectional Area
Maximum EcoSystemR-
compliant Link Wire Length
4,0 mm
2
829 m
2,5 mm
2
518 m
1,5 mm
2
311 m
1,0 mm
2
207m
Eco 1
Eco 1
Eco 2
Eco 2
Eco Link
1
Eco Link
2
EcoSystemR H-Series Ballast
EcoSystemR Digital Link
EcoSystemR LED
Up to 64 ballasts, modules, or
EcoSystemR LED drivers
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 11 08.18.11
Wiring: QS Link
IEC PELV QS Link Wiring
•LinkcommunicatesusingIECPELVwiring.
•Followallapplicablenationalandlocalcodesfor
proper circuit separation and protection.
•Wiringmaybedaisychainedort-tapped.
•TotallengthofQSlinkmustnotexceed600m.
QS Link Wiring
Length Wire Gauge
Available from
Lutron in one cable:
Less than 153 m
Power (terminals 1 and 2):
1 pair 1,0 mm
2
GRX-CBL-346S
(non plenum)
GRX-PCBL-346S
(plenum)
Data (terminals 3 and 4):
1 pair 0,5 mm
2
, twisted
and shielded*
153 m to 610 m
Power (terminals 1 and 2):
1 pair 4,0 mm
2
GRX-CBL-46L
(non plenum)
GRX-PCBL-46L
(plenum)
Data (terminals 3 and 4):
1 pair 0,5 mm
2
, twisted
and shielded*
•Useone,twisted-shieldedpairof0,5mm
2
for data
link (MUX, _).
(1)
(2)
(3)
(4)
COM
24 V-
MUX
MUX
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 12 08.18.11
Wiring: QS Link (continued)
Onlyterminals1,3,and4connected
betweendevicesthatsupplyPDUs
Terminal 2 NEVER connected
between devices that supply PDUs
Terminal 2 (+24 V)
NEVER connected*
Devices that
supplyPDUs
Devices that
consumePDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
Energi Savr
NodeT unit
Energi Savr
NodeT unit
QS
Input/
Output
Interface
Wired
QS
Keypad
QSM
QSMQSM
Wired
QS
Keypad
Wired
QS
Keypad
Wired
QS
Keypad
QS
Input/
Output
Interface
QS
Link
power
supply
QSLink;
all 4 terminals
QSLink;
no terminal 2
QSLink;
no terminal 2
QSLink;
all 4 terminals
QSLink;
all 4 terminals
Terminal 2 (+24 V)
NEVER connected*
Terminal 2 (+24 V)
NEVER connected*
**
All 4 terminals connected to QS link
devicesthatconsumePDUs
QS Link Wiring Rules
* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.
** ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructions
for the specific power supply model being used.
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 13 08.18.11
Wiring: Input Groups
Electrical Contractors and Engineers
•AllsensorwiringisIECPELV.Followallapplicable
national and local codes for proper circuit separation
and protection.
•IECPELVinputterminalsaccept1.0–2.5mm
2
solid
conductors.
•MainsvoltageandIECPELVwiringmustbekept
separate.
Wiring Instructions
•Turnoffcircuitbreakerorisolatoratdistributionpanel.
Occupancy Sensor
•Connectthreeconductorstothreeterminalsasshown.
•Oneoccupancysensorcanbewiredtoeachinputgroup.
•Sensormustbeplacedwithin30mofthe
Energi Savr NodeT.
IR Receiver
•Connectthethreeconductorstothethreeterminals
as shown.
IR Receiver (continued)
•Receivermustbeplacedwithin30mofthe
Energi Savr NodeT unit.
•OneIRReceivercanbewiredtoeachinputgroup.
•IfadaylightsensorandIRreceiverareconnected,
do not connect the daylight sensor's IR output
(white wire).
Daylight Sensor
•Connectthefourconductorstothefourterminalsas
shown.
•Terminals:
Red=20V- White=IR
Black=Common Yellow=Daylight
•DaylightSensormustbeplacedwithin30mofthe
Energi Savr NodeT unit.
•Onedaylightsensorcanbewiredtoeachinputgroup.
•Consultthedaylightsensorspecicationsheetto
properly locate the sensor.
•Donotplacethesensorabovependants,xtures,
directlybelowlightingxtures,orwithinskylightwells.
NOTE: There
are four sensor
groups. Each
group wires the
same and is
shown above.
Sensor Group 1
Sensor Group 3
Sensor Group 2
Sensor Group 4
* Note: Only one IR device may be connected per
input group. If the IR signal from a daylight sensor is
connected, another control may not be connected to
the same input, and vice-versa.
** Connect the gray wire on -R Occupancy Sensor
models.
IR Transmitter
20 V: 20 V-
IR: IR Receiver *
Photo: Daylight Sensor
Occ: Occupancy Sensor
Com: Common
20 V: 20 V
-
IR: IR Receiver *
Com: Common
Occupancy Sensor
Red
Red
Black
Black
Blue/Gray**
Yellow
Black
White*
LUTRO
N
R
LUTRON
IR Transmitter
Group 1 shown Group 2 shown
Daylight/IR Sensor*
IR Receiver*
White*
Red
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
International Energi Savr NodeT
for EcoSystemR
QSNE-2ECO-D EcoSystemR Controller
369-450a 14 08.18.11
Programming Options
Programming with Apple iPod touch or iPhone
•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with
multiple Energi Savr NodeT units and QSMs on the QS link.
•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.
•Wirelessroutermayberemovedfornormaloperation.
•EthernetconnectionmaybemadeviaintegralEthernetjack.
•LutronrecommendsthatintegralEthernetjackbewiredtoanEthernetjackinthespaceforeaseofaccessand
proximitytopowerforthewirelessrouter.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.
•Apple iPod touch or iPhone can program all Energi Savr NodeTunitsconnectedtotheQSlink(exceptwhen
part of a QuantumR system).
•Energi Savr appisrequiredandisavailablefromtheApple AppStore online marketplace.
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
AppStore is a service mark of Apple Inc.
* Note: Energi Savr NodeTunitsarenotdesignedtoexistonanopennetwork.
Connection to an open network could result in reduced performance and
Ethernet connectivity issues.
QS Link QS Link
Energi Savr
NodeT unit
QSM
Dedicated Ethernet
Connection for
Energi Savr NodeT
units*
Apple
iPod touch
or iPhone
mobile
digital
device
Wireless
Router
(by others)
Wire types:
1 Less than 153 m: LutronR cable
GRX-CBL-346S
153 m to 610 m: LutronR cable
GRX-CBL-46L
2 Standard CAT5/CAT5E cable: Total
lengthnottoexceed100m
1 1
2
2
14