SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet® PIC Statement for Quantum® Subsystem Main Devices
using Quantum
® Version 1.9
Software
License
Quantum®
BACnet® Protocol Implementation Conformance Statement (PICS)
Date: July 4, 2012
Vendor Name: Lutron Electronics Co., Inc.
Product Name: Quantum
® BACnet® Integration
Applications Software Version: 2.0
Firmware Revision: 1.9
BACnet
® Protocol Revision: 4
Vendor ID: 176
Product Description
BACnet® IP is embedded in the Quantum® processor. There are two types of BACnet® devices available in
Quantum
®: subsystem devices and area devices. The subsystem devices are main BACnet® devices; typically, one
main device per floor of the building. The area devices are virtual BACnet
® devices of the subsystem device,
typically one per room of the building. It is normal to have multiple subsystem devices and virtual devices in a
project.
BACnet® Interoperability Building Blocks Supported (Annex K):
K.1.2 BIBB Data Sharing ReadProperty-B (DS-RP-B)
K.1.4 B I B B Data Sharing ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BI B B Data Sharing WriteProperty-B (DS-WP-B)
K.1.10 B IBB Data Sharing WritePropertyMultiple-B (DS-WPM-B)
K.1.12 BIBB Data Sharing COV-B (DS-COV-B)
K.5.2 BIBB Device Management DynamicDeviceBinding-B (DM-DDB-B)
K.5.4 BIBB Device Management DynamicObjectBinding-B (DM-DOB-B)
K.5.6 BIBB Device Management DeviceCommunicationControl-B (DM-DCC-B)
BACnet® Standardized Device Profile (Annex L):
BACnet® Application Specific Controller (B-ASC)
Segmentation Capability:
Segmented requests supported? No. Window Size: n/a
Segmented responses supported? No
. Window Size: n/a
Non-Standard Application Services:
Non-standard application services are not supported.
369-322c 1 07.04.12
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test
products for compliance with ASHRAE standards. Compliance of listed products to the
requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI).
BTL is a registered trademark of BI.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet® PIC Statement for Quantum® Subsystem Main Devices
using Quantum
® Version 1.9
Software
License
Quantum®
Standard Object Types Supported:
Device
1. Dynamically creatable using BACnet® CreateObject service? No.
2. Dynamically deletable using BACnet® DeleteObject service? No.
3. List of optional properties supported: Active_COV_Subscriptions, Description, Location, Profile_Name.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Binary Value
1. Dynamically creatable using BACnet® CreateObject service? No.
2. Dynamically deletable using BACnet® DeleteObject service? No.
3. List of optional properties supported: Reliability, Active_Text, Inactive_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Multi-State Value
1. Dynamically creatable using BACnet® CreateObject service? No.
2. Dynamically deletable using BACnet® DeleteObject service? No.
3. List of optional properties supported: Reliability, State_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Data Link Layer Options:
BACnet® IP
Device Address Binding:
Is static device binding supported? No.
Networking Options:
BACnet®/IP Annex J non-BBMD functionality; the Quantum® processor is able to register as a foreign device.
The Quantum
® processor is able to initiate original-broadcast-NPDU.
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
• ANSIX3.4
Routing:
Routes packets between a physical LAN and one virtual LAN.
369-322c 2 07.04.12
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet® PIC Statement for Quantum® Subsystem Main Devices
using Quantum
® Version 1.9
Software
License
Quantum®
Object Name Type Instance Read Write COV Units Min
PV
Max
PV
Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
{SystemName}
{Instance}
DEVICE {Base} +
{System} + 1
X The System Name is the logical name of
one of the Quantum
® system’s
subsystems that typically corresponds
to a physical portion of the building such
as a floor. The Instance is the same as
the unique Device ID assigned to each
subsystem.
Master Loadshed
Enabled
BV 2 X X X 0 1 Disabled Enabled This value determines whether all of the
areas in the Quantum
® subsystem are
being controlled via load shedding.
When this value is set to Enabled, for all
areas in the subsystem that have
loadshed allowed, any dimmable lights
in each area that are turned on will have
their light level reduced by the
percentage specified in the Loadshed
Goal value. When Disabled, the lights
will dim to their commanded level.
Master
Hyperion
TM
Enabled
BV 3 X X 0 1 Disabled Enabled When the Master HyperionTM Enabled
feature is set to Enabled, for all areas in
the Quantum® subsystem that have
HyperionTM configured, the HyperionTM
feature will control the Lutron® Sivoia®
QS roller shades and set their level
automatically depending on the position
of the sun. When the Master HyperionTM
feature is set to Disabled, in all areas of
the subsystem, the shades will not be
controlled automatically by the
HyperionTM feature.
{TimeclockName}
Enabled
BV 1000 to 1999 X X 0 1 Disabled Enabled For each timeclock created within the
Quantum
® system, there will be one
instance from 1000 to 1999 that can
Enable or Disable that timeclock for that
particular subsystem. When Disabled,
the timeclock will not affect the lights.
When Enabled, the timeclock will affect
the lights as programmed in the
Quantum® system. Please note that if
there are multiple subsystems in the
Quantum® system, each timeclock will
be represented in each subsystem’s
BACnet® device. To enable or disable the
timeclock for all subsystems, each
subsystem device will need to be
commanded to do so.
BV = Binary-Value
{SystemName} is a text string defined in the Lutron
® Quantum® system configuration software
{Instance} is a number defined in the Lutron® Quantum® system configuration software that is equal to the {Base} number + {System} number +1
{Base} is a 22-bit value set in the Lutron® Quantum® system configuration software (default 1760000)
{System} is an 8-bit value set in the Lutron® Quantum® system configuration software (0 to 127)
{TimeclockName} is a text string defined in the Lutron® Quantum® system configuration software
PV = Present-Value
369-322c 3 07.04.12
3