SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet® PIC Statement for Quantum® Subsystem Main Devices
using Quantum
® Version 1.9
Software
License
Quantum®
Object Name Type Instance Read Write COV Units Min
PV
Max
PV
Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
{SystemName}
{Instance}
DEVICE {Base} +
{System} + 1
X — — — — — — — — The System Name is the logical name of
one of the Quantum
® system’s
subsystems that typically corresponds
to a physical portion of the building such
as a floor. The Instance is the same as
the unique Device ID assigned to each
subsystem.
Master Loadshed
Enabled
BV 2 X X X — 0 1 Disabled Enabled — This value determines whether all of the
areas in the Quantum
® subsystem are
being controlled via load shedding.
When this value is set to Enabled, for all
areas in the subsystem that have
loadshed allowed, any dimmable lights
in each area that are turned on will have
their light level reduced by the
percentage specified in the Loadshed
Goal value. When Disabled, the lights
will dim to their commanded level.
Master
Hyperion
TM
Enabled
BV 3 X X — — 0 1 Disabled Enabled — When the Master HyperionTM Enabled
feature is set to Enabled, for all areas in
the Quantum® subsystem that have
HyperionTM configured, the HyperionTM
feature will control the Lutron® Sivoia®
QS roller shades and set their level
automatically depending on the position
of the sun. When the Master HyperionTM
feature is set to Disabled, in all areas of
the subsystem, the shades will not be
controlled automatically by the
HyperionTM feature.
{TimeclockName}
Enabled
BV 1000 to 1999 X X — — 0 1 Disabled Enabled — For each timeclock created within the
Quantum
® system, there will be one
instance from 1000 to 1999 that can
Enable or Disable that timeclock for that
particular subsystem. When Disabled,
the timeclock will not affect the lights.
When Enabled, the timeclock will affect
the lights as programmed in the
Quantum® system. Please note that if
there are multiple subsystems in the
Quantum® system, each timeclock will
be represented in each subsystem’s
BACnet® device. To enable or disable the
timeclock for all subsystems, each
subsystem device will need to be
commanded to do so.
BV = Binary-Value
{SystemName} is a text string defined in the Lutron
® Quantum® system configuration software
{Instance} is a number defined in the Lutron® Quantum® system configuration software that is equal to the {Base} number + {System} number +1
{Base} is a 22-bit value set in the Lutron® Quantum® system configuration software (default 1760000)
{System} is an 8-bit value set in the Lutron® Quantum® system configuration software (0 to 127)
{TimeclockName} is a text string defined in the Lutron® Quantum® system configuration software
PV = Present-Value
369-322c 3 07.04.12