SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
3691130a 3 10.08.19
Lutron Fan Coil Unit Controller
Specifications
Regulatory Approvals
• cULus Listed
• CE Certified
• NOM certified
• RoHS compliant
• FCC 15 / ICES-003 Class B
Input Characteristics
• Power supply (not isolated): 12 – 24 V~ 50 / 60 Hz
±10% or 24 V- ±10%, listed Class 2, LPS, or SELV
limited energy supply <15 W
• Maximum power consumption: 4 W / 6 VA / 5 PDUs
1
• Analog Inputs: (2) Thermistor inputs
– Type: NTC (103 AT)
– Value: 10 K at 77 ˚F (25 ˚C)
– Range: -58 ˚F–212 ˚F (-50 ˚C–100 C)
– Resolution: 0.18 ˚F (0.1 ˚C)
– Accuracy: 1% full scale
Output Characteristics
• Relay Outputs: (5) SPST relays Normally Open rated for:
– 2 A at 24 V~ / 100 V~ / 120 V~ / 220–240 V~
general purpose
– 2 FLA / 12 LRA at 100 V~ / 120 V~ / 220–240 V~
motor load
• Analog Outputs: (3) 0–10 V- outputs
2
– Maximum 28 mA at 10 V- per output
3
– Resolution: 1%
– Accuracy: 2% full-scale
Environment
• Ambient operating temperature: -4 ˚F to 122 ˚F
(-20˚C to 50 ˚C)
• Storage temperature: −40 °F to 185 °F
(−40 °C to 85 °C)
• 0% to 90% relative humidity, non-condensing
• Indoor use only
• Product rated for IP20
• Pollution degree 2
Enclosure
• Controller must be installed in a listed
NEMA Type-1 enclosure or IP20 rated
enclosure with conformance to IEC 61439-3
(or equivalent standard)
• Enclosure should be secured by a keyed or tooled
locking mechanism
• Enclosure must comply with spacing listed in the
Mounting section
1
See Power Draw Units on the QS Link (P/N 369405) at www.lutron.com
for more information.
2
When using 0–10 V- fan or valve control, a different power supply must be
used to power the FCU controller and the 0–10 V- fan / valve actuators. For
more information, see Application Note #651 (048651) at www.lutron.com
3
All three 0–10 V- outputs, together, cannot deliver more than 40 mA.