Vive PowPak CCO Module Wireless Lighting Control
3691047c 1 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive PowPak CCO Module
The PowPak CCO Module is a low-voltage radio
frequency (RF) control that provides a single dry contact
closure output based on input from Pico remote controls
and Radio Powr Savr occupancy and daylight sensors. It
can be powered by to 24 V~ or 24 V- for easy
connection and integration into building management,
HVAC, VAV, and other third-party systems.
Communication with RF input devices, such as Pico
remote controls and Radio Powr Savr sensors, is
accomplished using Lutron Clear Connect RF
Technology.
These products are also compatible with the Vive hub
which enables a simple setup process using a standard
web browser on any Wi-Fi enabled phone, tablet or
computer. It also enables control and monitoring of all
Vive devices. The Vive hub can be added at any time.
System reprogramming will be required. For a complete
list of features supported with the Vive hub, see
specification submittal 3691044.
Note for Replacement: RMKS - the “S” model can
replace the non-”S” model.
Features
Single contact closure output including both normally
open (NO) and normally closed (NC) dry contacts
Maintained output type
Operates at 24 V~ or 24 V-
Receives wireless inputs from up to 10 Pico remote
controls, 10 Radio Powr Savr occupancy / vacancy
sensors, and 1 Radio Powr Savr daylight sensor
Utilizes Lutron Clear Connect RF Technology – refer to
model number chart below for frequency band data
Screw tabs provided for surface mounting
(recommended); or mounts to a 100 mm x 100 mm
square junction box through a 20 mm knockout
RMKS-CCO1-24-B model shown
Models
Model Number Region Operating Voltage Frequency Band
RMKS-CCO1-24-B Europe 24 V~ or 24 V- 868.125 –868.850 MHz
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
1
Vive PowPak CCO Module Wireless Lighting Control
3691047c 2 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Environment
Ambient operating temperature: 0 °C to 55 °C
0% to 90 humidity, non-condensing
For indoor use only
All drivers and ballasts used with Vive wireless
controls must comply with EN 55015 / CISPR 15
Contact Closure Output
Accepts input voltages of 0 –24 V~ / 0–24 V-; see
chart below for load switching capacities
Provides both normally open (NO) and normally
closed (NC) dry contacts
Maintained output type
CCO terminals accept 0.5 mm
2
to 1.5mm
2
(20 AWG to 16 AWG) solid or stranded wire
Output is latching
The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited
to, relays, solenoids, and motors. To control these
types of equipment, a flyback diode must be used
(DC voltages only). See diagram below. For more
information, please see Application Note #434
(p/n 048434).
Specifications
Regulatory Approvals
CE (European Union)
Power
IEC SELV / PELV
Operating voltage: 24 V~ / 24 V-
Operating current, nominal: 45 mA (24 V~)
35 mA (24 V-)
Standby Power Consumption: < 1.0 W
System Communication
Operates using Clear Connect RF Technology for
reliable wireless communication; refer to model
number chart on page 1 for frequency band details
Wireless sensors and controls must be located
within 9 m of the associated control module.
Metal Ceiling Tile Mounting
Metal ceiling tile grids must have a > 3 mm gap
of non-metallic material which extends the entire
length of the tile on at least one edge. This is often
achieved by foam spacers that are used to prevent
tile-to-tile rattling.
Metal ceiling tile grids which are continuous (with no
gap) or those that are interlocked, must have a total
surface area that is less than 81 m
2
for each section.
The overall space can be larger as long as there are
non-metallic sections bordering or intersecting the
metal sections.
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
2
Vive PowPak CCO Module Wireless Lighting Control
3691047c 3 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions
Dimensions are shown as: mm
Range Diagrams
Test
9 m
Maximum
12 m
9 m
PowPak CCO
Module
Install in center of room to
maximize RF coverage.
Pico Remote
Control
Radio Powr Savr
Occupancy Sensor
21 mm trade size
knockout opening
100
87
72 32
NOTE: Wireless sensors and controls must be located within
9 m of the associated control module.
Metal ceiling tile grids must have a > 3 mm gap of non-metallic
material which extends the entire length of the tile on at least
one edge. This is often achieved by foam spacers that are used
to prevent tile-to-tile rattling.
Metal ceiling tile grids which are continuous (with no gap) or
those that are interlocked, must have a total surface area that
is less than 81 m
2
for each section. The overall space can be
larger as long as there are non-metallic sections bordering or
intersecting the metal sections.
3
Vive PowPak CCO Module Wireless Lighting Control
3691047c 4 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Default Operation
Transmitting Device Transmitted Command CCO Default Action
Pico
Remote Control
On NO = Close, NC = Open
Off NO = Open, NC = Close
Raise NO = Close, NC = Open
Lower No Action
Preset NO = Close, NC = Open
Radio Powr Savr
Occupancy Sensor
Occupied NO = Close, NC = Open
Unoccupied NO = Open, NC = Close
Radio Powr Savr
Vacancy Sensor
Occupied No Action
Unoccupied NO = Open, NC = Close
Radio Powr Savr
Daylight Sensor
Ambient Light Below
Target Level
NO = Close, NC = Open
Ambient Light Above
Target Level
NO = Open, NC = Close
System Diagram
Radio Powr Savr Occupancy Sensor (up to 10)
Radio Powr Savr Daylight Sensor (up to 1)
Pico Remote Control (up to 10)
To third-party
equipment
To power source
4
Vive PowPak CCO Module Wireless Lighting Control
3691047c 5 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring Diagram (Recommended)
Note: CCO Module supply wires can be
connected in any polarity.
Note: When wiring CCO output,
use 0.5 mm
2
to 1.5 mm
2
(20 AWG
to 16 AWG) solid or stranded wire.
To CCO-controlled device.
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
Supply Voltage
24 V~ / 24 V-
Wiring a Lever Operated Connector (shown)
When wiring lever operated
connectors (2 supplied) use
2.5 mm
2
to 4.0 mm
2
(14 AWG to 12 AWG) solid or
stranded copper wire.
1
2
3
10 mm
Mounting screw
(by others)
5
Vive PowPak CCO Module Wireless Lighting Control
3691047c 6 11.16.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring Diagram (Junction Box Optional)
Supply Voltage
24 V~ / 24 V-
Junction Box
*
To third-Party
Equipment
NC
NO
COM
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
)Lutron, Lutron, PowPak, Pico, and Clear Connect are trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries.
Vive and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc.
Adaptor
20 mm
trade size
knockout
opening
6