SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 1 10.15.19
Energi Savr Node with DALI® for Quantum
The Energi Savr Node family is a group of intelligent, modular products
for the control of lighting loads. This document describes the Energi
Savr Node with DALI
®-compliant Digital Addressable loads. It provides
DALI
® loop power and control for two independent DALI® loops with up
to 64 ballasts each. The Energi Savr Node unit with DALI
® also provides
direct connections and power for the following Lutron devices in a
Quantum system:
Occupancy sensors
Daylight sensors
IR receivers
QS devices
Features
Includes QS control link for seamless integration of lights in a Quantum system.
Provides communication power for up to 2 loops of DALI
® compliant digitally
addressable loads (up to 250 mA per loop).
Each DALI
® loop can control a maximum of 16 zones.
Provides power for two buses of DALI
®-compliant digital addressable loads. 128 mA guaranteed current,
250 mA maximum supply current per bus.
Power failure memory retains control unit programming in the event of a power loss.
Four occupancy sensor inputs for automated control of lights.
Four daylight sensor inputs automatically adjust light levels based on the amount
of natural light entering through the windows.
Four IR receiver inputs for personal control.
Model Numbers
• QSN-1DAL-S-CPN6916
• QSN-2DAL-S-CPN6916
QSN-2DAL-S
120-277 V~
50/60 Hz 500 mA
EcoSystem
Energi Savr Node
2 DALI Loops
2 bucles DALI
l
2 boucles DALI
Capacity
l
Capacidad
l
Capacité :
18 V- 250 mA
per loop | por bucle | par boucle
64 DALI Devices per loop
64 Dispositivos DALI por bucle
64 Dispositifs DALI par boucle
IEC PELV / NEC
®
Class 2
Input Groups | Grupos de entrada
Groupes d’entreés :
20 V- 4 X 65 mA
QS Link | Enlace | Liaison :
24 V- 1 A
Type 1
Enclosure
243C
LISTED
Ind.
Cont. Eq.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation.
CAN ICES-3 (A)/NMB-3(A)
Coopersburg, PA 18036, U.S.A.
24/7 Help | Ayuda | Aide lutron.com
U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.844.LUTRON1
México +1.888.235.2910
Others | Otros | Autres +1.610.282.3800
Assembled in Mexico
Assemblé aux Mexique
Ensamblado en México
saving energy since 1961
50017686a
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
requis an de proceder à la deconnection totale de l’unité.
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
Riesgo de choque eléctrico. Puede resultar en lesiones
graves o muerte. Puede necesitarse más de una desconexión
para desenergizar este dispositivo. Desconecte todas las
fuentes de alimentación antes de prestar servicio a la unidad.
DALI® Compatibility
The Lutron DALI® Energi Savr Node (ESN) is DALI-2® certified by the Digital Illumination Interface Alliance (DiiA)®. In order to
ensure compatibility with Lutron DALI® controllers, the connected DALI® LED drivers and fluorescent ballasts must be
DALI-2® certified and marked. In addition to compatibility, it is important to select high-quality and high-performance LED
drivers and fluorescent ballasts. DALI-2® certified devices are readily available from many manufacturers and are tested for
compatibility with the standard. For a complete list of available DALI-2® certified devices, see the DiiA® website at
https://www.digitalilluminationinterface.org/products. DALI® devices that are not listed on the DiiA® website and are not
marked DALI-2® cannot be considered DALI-2® certified.
The DALI® version-1 standard does not ensure compatibility. To apply the original DALI® version-1 mark on LED drivers
and fluorescent ballasts, no verification of the test results was required, and manufacturers could self-declare compliance
and apply the DALI® mark. If you would like to use an LED driver or fluorescent ballast that is not DALI-2® certified but
carries a DALI® version-1 logo, Lutron recommends that these devices be tested to ensure compatibility. Lutron is able to
perform this testing on request. Samples of the drivers and light engines must be submitted to Lutron and the expected
turnaround time is 6 to 8 weeks after the drivers are received. Fees for testing may apply. Lutron recommends that this
testing be performed before the fixtures and lighting controls are purchased and installed. Contact your Lutron sales
representative for more information.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 2 10.15.19
QP3-1PL-100-240
Type 1
Enclosure
Input:
1 A 120-240 V~ 50/60 Hz
Output:
2 A 24 V --- (IEC PELV/NECR Class 2)
Entree:
1 A 120-240 V~ 50/60 Hz
Sortie:
2 A 24 V --- (IEC PELV/NECR Class 2)
Entrada:
1 A 120-240 V~ 50/60 Hz
Salida:
2 A 24 V --- (IEC PELV/NECR Class 2)
QSN-2DAL-S
120-277 V~
50/60 Hz 500 mA
EcoSystem
Energi Savr Node
2 DALI Loops
2 bucles DALI
l
2 boucles DALI
Capacity
l
Capacidad
l
Capacité :
18 V-
250 mA
per
loop
| p
or bucle
| pa
r bo
ucle
64 DALI Devices per loop
64 Dispositivos DALI por bucle
64 Dispositifs DALI par boucle
IEC PELV / NEC
®
Class 2
Input Groups | Grupos de entrada
Groupes d’entreés :
20 V- 4 X 65 mA
QS Link | Enlace | Liaison :
24 V- 1 A
Type 1
Enclosure
243C
LISTED
Ind.
Cont. Eq.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause interference.
(2) This device must accept any interference, including interference that may cause undesired operation.
CAN ICES-3 (A)/NMB-3(A)
Coopersburg, PA 18036, U.S.A.
24/7 Help | Ayuda | Aide l utron.com
U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.844.LUTRON1
México +1.888.235.2910
Others | Otros | Autres +1.610.282.3800
Assembled in Mexico
Assemblé aux Mexique
Ensamblado en México
saving energy since 1961
50017686a
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
requis an de proceder à la deconnection totale de l’unité.
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
Riesgo de choque eléctrico. Puede resultar en lesiones
graves o muerte. Puede necesitarse más de una desconexión
para desenergizar este dispositivo. Desconecte todas las
fuentes de alimentación antes de prestar servicio a la unidad.
QS link
Control power
120-277 V~
Emergency Contact
Closure Input
Programmable Contact
Closure Input
Wireless
Communication
Wired daylight
sensors (up to 4)
Wired daylight
sensors
(up to 4)
1
DALI® loops
(up to 64 ballasts
per loop)
Wired occupancy
sensors (up to 4)
Wired occupancy
sensors
(up to 4)
1
IR receivers
(up to 4)
IR receivers
(up to 4)
1
QSM
IR transmitter
IR transmitter
OR
OR
seeTouch QS
wallstation
Radio Powr Savr
occupancy sensor
(up to 10 per QSM)
Radio Powr Savr
daylight sensor (new!)
(up to 10 per QSM)
Pico wireless
controller (up to
10 per QSM)
Note:
1 Up to 4 wired inputs total (of any type).
System Example
Quantum hub
Note: This device is not compatible with the Energi Savr Node iPod programming app. It is only for use
in a Quantum system
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 3 10.15.19
Specifications
Regulatory Approvals
• UL
® Listed
• CSA
NOM Certified
Lutron Quality Systems registered to ISO 9001.2015
IEC 62386-101 Ed. 2
For commercial use, Class A only.
Power
Control Power: 120-277 V~ 50/60 Hz
Maximum current draw: 0.5 A
Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
• DALI
® loop output: 18 V- 250 mA maximum per loop
10-year power failure memory: restores lighting to
levels prior to power interruption.
Environment
Ambient temperature operating range: 32 ºF to
104 ºF (0 ºC to 40 ºC).
Relative humidity: less than 90% non-condensing.
For indoor use only.
Can be installed in accordance with NEC
®
Article 300.22(c) “Other spaces used for environmental air.
Terminals
Control power wiring: 14 AWG to 12 AWG
(2.5 mm
2
to 4.0 mm
2
)
• DALI
® digital loop wiring: 20 AWG to 16 AWG
(0.5 mm
2
to 1.5 mm
2
)
Input group wiring: 22 AWG to 12 AWG
(0.5 mm
2
to 4.0 mm
2
)
QS link wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
Physical Design
NEMA Type 1, IP-20 protection.
Mounting
• Surface-mount.
DALI
® Buses
Up to 64 DALI
® compliant loads on each loop can be
addressed and grouped into 16 zones.
Supplies a maximum of 250mA to power each bus.
Supplies a guaranteed current of 128 mA to power
each bus.
• DALI
® loop wires are polarity insensitive and topology
free.
Automatic shutdown and restart after short-circuit.
QS Link Limits
Each Energi Savr Node unit with DALI
® can provide up
to 30 Power Draw Units for other QS devices. Refer to
the QS link Power Draw Units specification submittal
(Lutron P/N 369405) at www.lutron.com for more
information concerning Power Draw Units.
The QS Link can have up to 100 devices and
100 zones.
Each Energi Savr Node unit with DALI
® counts as
1 device towards the 100 device limit.
Each Energi Savr Node unit with DALI
® can count as
1 to 32 zones towards the 100 zone limit, depending
on the number of zones created (up to 32 zones in a
Quantum system).
A maximum of 8 DALI
® digital links may be connected
to the QS link.
A maximum of 512 DALI
® ballasts may be connected
to the QS link.
QS Link Sensor Limits
100 wired and wireless occupancy sensors.
100 wired and wireless daylight sensors.
100 wired wallstations or Pico wireless controllers.
Sensors Connected to the Energi Savr Node
unit with DALI
®
Four power supply outputs
20 V- 65 mA maximum
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 4 10.15.19
Specifications (continued)
Occupancy Sensors
Use Lutron LOS series of wired occupancy sensors in
occupancy mode to control one or more areas.
Use Lutron occupancy sensors in vacancy mode
to automatically turn the lights off in an area after it
becomes vacant.
Use Lutron occupancy sensors to automatically turn
the lights on in area when it becomes occupied and
to automatically turn the lights off in an area after it
becomes vacant.
Each of the four occupancy inputs can power one
Lutron occupancy sensor.
Up to four additional Lutron wired occupancy
sensors or ten additional Radio Powr Savr
occupancy / vacancy sensors can be assigned per QS
Sensor Module (QSM) on the QS link.
seeTouch QS Controls
Refer to seeTouch QS spec submittal for further
information.
Configurable seeTouch QS wallstations, refer to the
QS wallstation programming guide for configuration
options
IR Controls
Use Lutron IR receivers or wired Pico keypads for
personal control of individual lighting zones.
Four IR devices can connect directly to the
Energi Savr Node unit with DALI
®.
Daylight Sensors
Lutron daylight sensors allow daylight harvesting with
programmable effect on light output.
Four daylight sensors can be connected directly to the
Energi Savr Node unit with DALI
®.
Use Lutron EC-DIR-WH sensors to control one or
more daylight rows.
Alternatively, up to four additional Lutron wired daylight
sensors or ten additional Radio Powr Savr daylight
sensors can be assigned per QSM on the QS link.
Contact Closure Input (CCI)
Inputs must be dry contact closure, solid state, open
collector, or active-low (NPN) / active high (PNP)
output.
Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
Open circuit voltage: 24 V maximum.
Off-state leakage current must be less than 100 μA.
Accepts maintained inputs and momentary inputs
with 40 msec minimum pulse times
Configurable for normally open (NO) or normally
closed (NC) operation.
Input is miswire-protected up to 36 V-.
Functionality defined by Quantum system
programming.
Emergency Contact Closure Input
By default, contact closure input from Lutron
Emergency Lighting Interface (LUT-ELI-3PH), security,
or fire alarm systems turns all zones on to full output
when emergency state is detected.
Emergency contact closure input is normally closed
(NC). The Energi Savr Node unit with DALI
® is shipped
with a jumper pre-installed.
Response of each zone is configurable.
Attached devices, by default, will go to maximum
output and ignore control inputs.
No operations will be allowed until emergency signal
is cleared.
Inputs must be dry contact closure, solid state, open
collector, or active-low (NPN) / active high (PNP)
output.
Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
Open circuit voltage: 24 V maximum.
Off-state leakage current must be less than 100 μA.
Accepts maintained inputs and momentary inputs
with 40 msec minimum pulse times
Input is miswire-protected up to 36 V-.
Emergency CCI cannot control other
Energi Savr Node units.
See Application Note #106, (P/N 048106) “Emergency
Lighting” at www.lutron.com for more details.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 5 10.15.19
QS LINK
LOOP 2
LOOP 1
RESET
LOOP 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
LOOP 1
H/LN N/C
Mechanical Dimensions
All dimensions shown as in (mm)
11.25
(285.75)
0.20
(5.16) dia.
0.95
(24.13)
1.41
(35.81)
1.80
(45.72)
1.03
(26.16)
Do not
use side
knockouts
0.83
(21.08)
9.25
(234.95)
7.50
(190.50)
3.16
(80.26)
13.25
(336.55)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 6 10.15.19
Wiring: QS Link
QS link communication uses IEC PELV / NEC® Class 2
wiring. Follow all local and national electrical codes when
installing IEC PELV / NEC
® Class 2 wiring with line voltage
wiring.
The total distance of the QS link wiring must not exceed
2000 ft (610 m).
QS Link Wiring
Distance
Wire
Gauge
Available from Lutron
in one cable:
Less than 500ft
(152m)
Power (terminals 1 and 2):
1 pair 18 AWG (1.0mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4):
1 pair 22 AWG (0.5mm
2
),
twisted and shielded*
500ft to 2000ft
(152m to 610m)
Power (terminals 1 and 2):
1 pair 12 AWG (4.0mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4):
1 pair 22 AWG (0.5mm
2
),
twisted and shielded*
* Alternate Data-only cable: Use approved data link cable
22AWG (0.5mm
2
) twisted / shielded from Belden,
model #9461.
Energi Savr Node unit with DALI®
(4)
(3) MUX
(2) 24 V-
(1) COM
QS Link Wiring:
22AWG to 12AWG
(0.5mm
2
to 4.0mm
2
)
Drain
2 12 AWG
(4.0 mm
2
)
2 12 AWG
(4.0 mm
2
)
IEC PELV / NEC
® Class 2
control wiring
(2) 18 AWG (1.0 mm
2
)
1: Common
2: 24 V-
Control Link Wiring
Data link: (1) twisted,
shielded pair
22 AWG (0.5 mm
2
)
3: MUX
4: MUX
Wiring for QS link for 500 ft to
2000 ft (152m to 610 m).
Terminal block will not accept
12 AWG (4.0 mm
2
) directly.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 7 10.15.19
Wiring: QS Link (continued)
Only terminals 1, 3, and 4 connected
between devices that supply PDUs
Terminal 2 NEVER connected between
devices that supply PDUs
Terminal 2 (+24 V)
NEVER connected*
Devices that
supply PDUs
Devices that
consume PDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
Energi Savr
Node unit with
DALI®
Energi Savr
Node unit with
DALI®
QS Input /
Output
Interface
Wired QS
Keypad
QSM
QSMQSM
Wired QS
Keypad
Wired QS
Keypad
Wired QS
Keypad
QS Input /
Output
Interface
QS Link
power
supply
QS link;
all 4 terminals
QS link;
no terminal 2
QS link;
no terminal 2
QS link;
all 4 terminals
QS link;
all 4 terminals
Terminal 2 (+24 V)
NEVER connected*
Terminal 2 (+24 V)
NEVER connected*
**
All 4 terminals connected to QS link
devices that consume PDUs
QS Link Wiring Rules
* Terminal 2 (+24 V) should NEVER be connected between devices that supply PDUs.
** For QS Link power supply wiring connection details, refer to the installation instructions
for the specific power supply model being used.
NOTE: Refer to the QS Link Power Draw Units specification submittal (Lutron P/N 369405) at www.lutron.com for
information concerning Power Draw Units (PDUs)."
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 8 10.15.19
Wiring: IEC PELV / NEC® Class 2 Inputs
NOTE: There are four input groups. Each group has
the same inputs as shown in the diagram below.
Note: Maximum wire
run length to each
input not to exceed
150 ft (45.7 m).
Input Group Wiring:
22AWG to 12AWG
(0.5mm
2
to 4.0mm
2
)
* Note: Only one IR device may be connected per IR input. If the IR
signal from a daylight sensor is connected, a wall control may
not be connected to the same input, and vice-versa.
** Connect the gray wire on -R model occupancy sensors.
Occupancy Sensor
IR Receiver*
Red
Red
20V
Black
Black COM
Yellow
Blue**
Black
Red
White*
20 V: 20 V-
OCC: Occupancy Sensor
PHOTO: Daylight Sensor
IR: IR Receiver*
COM: Common
Group 1 shown Group 2 shown
White* IR
LUTRON
Daylight / IR Sensor*
LUTRO
N
R
IR Transmitter
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 9 10.15.19
Wiring Diagram: DALI® Loop
The Energi Savr Node unit with DALI® will supply
power to an independent DALI
® loop, which
supports a maximum of 64 ballasts per loop.
DALI
® Wiring
• DALI
® wiring is not SELV.
• DALI® wiring is treated as line voltage, and thus may
be run within the same sheathing.
Ensure that there is not greater than a 2 V- drop
between the Energi Savr Node unit with DALI® and
the end of the DALI® loop.
Consult all national and local electrical codes for
separation requirements.
Wire Gauge
Maximum DALI® Compliant
Bus Wire Length
16 AWG (1.5 mm
2
) 980 ft (300 m)
18 AWG (1.0 mm
2
) 490 ft (150 m)
20 AWG (0.5 mm
2
) 325 ft (100 m)
QS LINK
Loop 1
Loop 1
RESET
DALI
Loop 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
DALI
Loop 1
HNG
N/C
QS LINK
Loop 1
Loop 1
RESET
DALI
Loop 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
DALI
Loop 1
HNG
N/C
DALI
Loop 1
DALI
Loop 2
DA2
DA1
DA2
DA1
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 10 10.15.19
QS LINK
Loop 1
Loop 1
RESET
DALI
Loop 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
DALI
Loop 1
HNG
N/C
Wiring: Control Power
Hot / Line (H/L)
Neutral (N)
Ground (
)
Do not use (N / C)
Wiring Notes
Control Power wiring should be from a normal,
non-emergency feed for proper operation of the
Energi Savr Node unit with DALI
®.
Power terminals accept (1) or (2) 14 AWG to
12 AWG (2.5 mm
2
to 4.0 mm
2
) solid or
stranded wire.
Energi Savr Node unit with DALI
QS LINK
Loop 1
Loop 1
RESET
DALI
Loop 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
DALI
Loop 1
HNG
N/C
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 11 10.15.19
Wiring: Contact Closure Inputs
COM: Common
COM: Common
CCI: Contact Closure Input
EMERG: Emergency Contact Closure Input
Emergency CCI
The attached device must provide a closed dry
contact closure or solid-state output.
Input is miswire-protected up to 36 V-.
• The Energi Savr Node unit with DALI
® is shipped
with a jumper pre-installed in the Emergency Contact
Closure Input.
Emergency mode is activated by opening the
Emergency Contact Closure. Pre-installed jumper
must be removed to utilize this function.
See Application Note #106, (P/N 048106)
“Emergency Lighting” at www.lutron.com for more
details.
• Accepts 22 AWG to 12 AWG
(0.5 mm
2
to 4.0 mm
2
) solid or
stranded wires.
Maximum wire run distance:
250 ft (76 m).
Programmable CCI
The attached device must provide a dry contact
closure or solid-state output.
Input is miswire-protected up to 36 V-.
Energi Savr Node unit with DALI
®
Jumper
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 12 10.15.19
Typical Application: Requires Quantum system commissioning
Occupancy
Sensor
Daylight
Sensor
Loop 2
Loop 1
Versaplex
QS
LUTRO
N
Wired to
sensor
group 4
LUTRON
LUTRON
LUTRON
LU
TRON
LUTRO
N
Open Offices Corridor Private Offices
seeTouch QS Wallstation
seeTouch QS Wallstation
QS Link
QS Link
QS Link
WindowWindowWindow
DALI®
Loop
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Occupancy
Sensor
Energi Savr
Node unit
with DALI
®
Energi Savr
Node unit
with DALI®
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
DALI®
Loop
DALI
®
Loop
DALI®
Loop
DALI
®
Loop
DALI
Loop
Quantum
Hub
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 13 10.15.19
Troubleshooting and Maintenance Features
Maintains redundant memory of ballast programming for ease of single or multiple ballast replacement.
After installation, "TEST" button verifies DALI
® wiring on all fixtures.
Status LEDs verify connections to control stations and sensors.
After installation, Energi Savr Node unit with DALI
® identifies ballast communication failures.