SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node DALI® Digital Fixture Controller - CPN6916
369794g 4 10.15.19
Specifications (continued)
Occupancy Sensors
• Use Lutron LOS series of wired occupancy sensors in
occupancy mode to control one or more areas.
• Use Lutron occupancy sensors in vacancy mode
to automatically turn the lights off in an area after it
becomes vacant.
• Use Lutron occupancy sensors to automatically turn
the lights on in area when it becomes occupied and
to automatically turn the lights off in an area after it
becomes vacant.
• Each of the four occupancy inputs can power one
Lutron occupancy sensor.
• Up to four additional Lutron wired occupancy
sensors or ten additional Radio Powr Savr
occupancy / vacancy sensors can be assigned per QS
Sensor Module (QSM) on the QS link.
seeTouch QS Controls
• Refer to seeTouch QS spec submittal for further
information.
• Configurable seeTouch QS wallstations, refer to the
QS wallstation programming guide for configuration
options
IR Controls
• Use Lutron IR receivers or wired Pico keypads for
personal control of individual lighting zones.
• Four IR devices can connect directly to the
Energi Savr Node unit with DALI
®.
Daylight Sensors
• Lutron daylight sensors allow daylight harvesting with
programmable effect on light output.
• Four daylight sensors can be connected directly to the
Energi Savr Node unit with DALI
®.
• Use Lutron EC-DIR-WH sensors to control one or
more daylight rows.
• Alternatively, up to four additional Lutron wired daylight
sensors or ten additional Radio Powr Savr daylight
sensors can be assigned per QSM on the QS link.
Contact Closure Input (CCI)
• Inputs must be dry contact closure, solid state, open
collector, or active-low (NPN) / active high (PNP)
output.
– Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
– Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
– Open circuit voltage: 24 V maximum.
– Off-state leakage current must be less than 100 μA.
– Accepts maintained inputs and momentary inputs
with 40 msec minimum pulse times
• Configurable for normally open (NO) or normally
closed (NC) operation.
• Input is miswire-protected up to 36 V-.
• Functionality defined by Quantum system
programming.
Emergency Contact Closure Input
• By default, contact closure input from Lutron
Emergency Lighting Interface (LUT-ELI-3PH), security,
or fire alarm systems turns all zones on to full output
when emergency state is detected.
• Emergency contact closure input is normally closed
(NC). The Energi Savr Node unit with DALI
® is shipped
with a jumper pre-installed.
• Response of each zone is configurable.
• Attached devices, by default, will go to maximum
output and ignore control inputs.
• No operations will be allowed until emergency signal
is cleared.
• Inputs must be dry contact closure, solid state, open
collector, or active-low (NPN) / active high (PNP)
output.
– Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
– Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
– Open circuit voltage: 24 V maximum.
– Off-state leakage current must be less than 100 μA.
– Accepts maintained inputs and momentary inputs
with 40 msec minimum pulse times
• Input is miswire-protected up to 36 V-.
• Emergency CCI cannot control other
Energi Savr Node units.
• See Application Note #106, (P/N 048106) “Emergency
Lighting” at www.lutron.com for more details.