369346c 3 01.23.14
Power Equipment
Softswitch128®
Switching Systems
Page
SPECIFICATION SUBMITTAL
Job Name:
Job Number:
Model Numbers:
Standards
• UL
R Listed
• CSA
• NOM
• Seismic Certified Available
1
(Test Method AC156.
Reference OSHPD Pre-approval OSP-0215-10)
Power
• Input power: 120 / 277 V~, 347 V~
2
and 480 V~
2
.
All voltages 50/60 Hz, phase-to-neutral.
• Branch Circuit Breakers: UL-rated thermal magnetic
AIC ratings:
120 V~ 10,000 A
277 V~ 18,000 A
347 V~ 14,000 A
• Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges up to
6000V~ and current surges up to 3000 A.
• 10-year power failure memory: restores lighting to
levels prior to power interruption.
Load Types (relay ratings)
Relay Rating
Load
Type
120 V~ 230 V~
(CE)
220-240 V~ 277 V~ 347 V~
Tungsten 20 A 16 A 16 A 20 A 16 A
AC General
Use
20 A 16 A 16 A 20 A 16 A
Electric
Discharge
Lamp
16 A 16 A 16 A 16 A 16 A
Electronic
Ballast
NEMA 410
16 A N/A N/A 16 A N/A
Resistive 20 A 16 A 16 A 20 A 16 A
Inductive 20 A 16 A 16 A 20 A 16 A
Motor
1.0 HP N/A N/A 2.0 HP N/A
Specifications
1
Contact your LutronR representative for details.
2
Contact your LutronR representative for details on 347 V~
and 480 V~ switching.
Load
•
When using the Switching Module to control
receptacles, it may be used with, but is not limited to,
the following:
– Monitors – Fans
– Humidifiers – Printers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
•
When using the Switching Module to control
receptacles, it may NOT be suitable for use with
devices that require any of the following:
– Shut-down process before power is interrupted,
such as computers.
– Cool-down process before power is interrupted,
such as projectors.
– Programming, such as clocks or DVRs.
– Long warm-up cycle.
•
Not for use with loads that present a hazard if
automatically energized, for example heaters.
•
Any receptacles that are controlled by an
automatic control device must be marked with “u”
located on the controlled receptacle outlet where
visible after installation as stated in 2014 NECR
Article 406.3(E).
Switching Modules (120, 277, 347 V~)
• Able to control 20 A receptacles.
• Switch legs rated at 20 A.
• Patented SoftswitchR circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to an average of 1,000,000 cycles at
16 A.
• 10 BTU / hour per module.
Continued on next page...