LUTRON®
Control Station Device (CSD) Link Wiring
• Use low-voltage PELV (Class 2: USA) wiring to
daisy-chain Wallstations to the Processor Panel.
• Make connections inside the wallbox or in a
switch/junction box with a maximum wire length of
8 feet (2.5m) from the link to the Wallstation.
• Two #12 AWG (2.5mm
2
) conductors for common
(terminal 1) and 24 V (terminal 2). These will not
fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for
data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to
Ground (Earth) or Wallstation. Connect the bare
drain wires and cut off the outside shield.
Note: Some Wallstations have a “D” terminal for
Drain. The Drain/Shield wire may be connected to
this terminal.
Data Link - (1) twisted, shielded pair
#18 AWG (1.0mm
2
)
3: MUX
4: MUX
PELV (Class 2: USA)
Control wiring
(2) #18 AWG (1.0mm
2
)
1: Common
2: 24 V
D:
Drain/Shield
Wiring to Control Link
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
Wallstation Installation
Note: Use appropriate wire connecting devices
as specified by local codes.
Rear of seeTouch Wallstation
Use Faceplate Replacement Kits to change:
colors, button configuration, engraving, between
insert and non-insert versions. Each Kit includes
an adapter, button assembly, and wallplate
Non-Insert Kit
Faceplate Replacement Kits
Insert Kit
Multi-ganging
• Order Insert (I) style controls.
• To order Wallplates for multi-ganging, specify
“R3” openings in a NovaT*
® multi-gang FB
(fins broken) Series model number.
Examples:
Wallplate for 2 seeTouch
Wallstations,
Model # NT-R3-R3-FB-(color)
Wallplate for other Lutron controls
and 2 seeTouch Wallstations,
Model # NT-T8-R3-R3-FB-(color)
• Order Claro
® Wallplates for multi-ganging
Wallstations in Gloss Finishes.
• Order Satin Colors
TM
Wallplates for multi-ganging
Wallstations in Satin Colors.
Note: New button inserts are not included with
multi-ganging Wallplates.
Faceplate Information