R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-1 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
SO-SVCN-___-___
GRAFIK Systems
Sivoia QEDTM Controller
Description
• Provides programming and control of one group of
Sivoia QED
TM Window Treatments.
• Allows selection of preset window treatment levels
from GRAFIK Systems.
• Connects to both the GRAFIKTM Systems link and the
Sivoia QED Electronic Drive Unit (EDU) link.
• One SO-SVC needed per group of Sivoia QED
Window Treatments (up to 96 devices).
• Maximum of 32 GRAFIK Systems Sivoia QED
Controllers per wallstation link.
• Large, rounded buttons are easy to use.
• Backlit buttons with optional engraving make it easy
to find and operate the control in low light conditions.
• Optional button engraving is angled up to the eye for
easy reading.
• Pressing the Open button once will cause the window
treatments move to their fully open position. If the
Open button is pressed again while the window
treatments are opening, the movement of the window
treatments will stop.
• Pressing the Preset 1, Preset 2, or Preset 3 button
once will cause the window treatments to move to the
first, second, and third preset level, respectively. If the
Preset 1, Preset 2, or Preset 3 button is pressed while
the window treatments are moving to that position,
the window treatments will stop.
• Pressing the Close button once will cause the window
treatments move to their fully closed position. If the
Close button is pressed again while the window
treatments are closing, the movement of the window
treatments will stop.
• Pressing the Raise/Lower buttons will cause the
window treatments to open/close while the button is
pressed.
• The LEDs next to each button are used during
programming and provide feedback of the current
Sivoia QED preset.
• Works with GRAFIK 5000
TM, 6000®, and 7000®
Systems.
Finish and Engraving Options
• Available with button engraving.
• Standard and Non-Standard text engraving available.
For more details, visit the website at
www.lutron.com/seetouch.
Color and Finish Codes
SO-SVCN-WH-E01
SO-SVCI-WH-___
(Insert version)
LEDs
Engraving
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-2 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
Specifications
Power
Low-voltage type PELV (Class 2: USA). Operating voltage: 24 V ,
supplied by Sivoia QED System.
Key Design Features
• Field-changeable button and faceplate assemblies allow easy customization.
• Front accessible DIP switches allow change of function without removing the
unit from the wall.
• Meets IEC 801-2. Tested to withstand 15 kV electro-static discharge without
damage or memory loss.
• Faceplate snaps on with no visible means of attachment.
• Available as an “insert” style control for multi-ganging.
• Can be ganged to share a common faceplate with NovaT*
® and Vareo®
Dimmers. To order new Wallplates for multi-ganging, specify “R3” openings
in a Lutron NovaT* multi-gang FB (fins broken) Series model number.
• Use Button Replacement Kits to change color, button configuration,
or engraving.
• Button Replacement Kits may also be used to convert between non-insert
and insert configurations.
System Communications and Capacity
• Low-voltage type PELV (Class 2: USA) wiring connects Wallstations and
Sivoia QED Controllers to GRAFIK Systems components.
• The Sivoia QED Controller is wired on the GRAFIK 5000
TM, 6000®, or 7000®
wallstation/CSD link.
• Up to 32 GRAFIK Systems Sivoia QED Controllers may be connected per
wallstation/CSD link.
• Each GRAFIK Systems Sivoia QED Controller is capable of controlling up to
96 Electronic Drive Units as a group.
• Each Sivoia QED Electronic Drive Unit requires its own 24 V transformer.
Terminals
Communications to GRAFIK Systems Central Processor: One 4-pin
removable terminal block. Each pin will accept one wire up to #18 AWG.
(1.0 mm
2
).
Communications to Sivoia QED EDU: One 5-pin removable terminal block.
Each pin will accept one wire up to #18 AWG (1.0 mm
2
).
Environment
32 - 104 °F (0 - 40 °C). Relative humidity less than 90% non-condensing.
Mounting
Typical backbox dimensions: 95 mm (3.74 in.) high, 55 mm (2.17 in.) wide,
70 mm (2.75 in.) deep.
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-3 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
Page
4
3
2
1
Wallbox
Control
Button
Kit
Faceplate
Adapter
Faceplate
Front View
Side View
Back View
Terminals
for Class 2
(PELV)
Wiring
1 1/16 in.
(27 mm)
2 3/4 in.
(70 mm)
4 9/16 in.
(116 mm)
5/16 in.
(8 mm)
3/4 in.
(19 mm)
Dimensions
Mounting
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-4 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
Matte Finishes
White WH
Ivory IV*
Beige BE
Gray GR*
Brown BR
Black BL
* GR, IV not currently backlighted
Color/Finish and Customizing Information
Color/Finish
Multi-ganging
Gloss Finishes
Available with Insert (I) style controls only.
Ship with Claro® faceplates.
White GWH
Light Almond GLA
• Order Insert (I) style controls.
• To order new Wallplates for multi-ganging, specify
“R3” openings in a Lutron NovaT*
® multi-gang FB
(fins broken) Series model number.
Metal Finishes
With Black Plastic Buttons (Standard)
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Clear CLA
Black BLA
Brass BRA
Backlighting Notes:
Illuminated text (translucent text
on buttons) is available for these
colors: BL and BR (including all
metal finishes).
Illuminated buttons (with black
text on buttons) are available for
these colors: WH, BE, GR, WH*,
GLA*.
* Insert (I) style controls only
Use Button Replacement Kits to change: colors, button
configuration, engraving, between insert and non-insert versions.
Each Kit includes
an adapter, button
assembly, and
wallplate
Non-Insert Kit
Examples:
Wallplate for 2 seeTouch Wallstations,
Model # NT-R3-R3-FB-(color)
Wallplate for other Lutron controls and
2 seeTouch Wallstations,
Model # NT-T8-R3-R3-FB-(color)
Note: New button inserts are not included with
multi-ganging Wallplates.
Button Replacement Kits
Insert Kit
4
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-5 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
Wiring to Sivoia QED Window Treatments
Refer to the Sivoia QED System instruction sheets for
more information on programming Sivoia QED Electronic
Drive Units.
Notes:
• Sivoia IR transmitters will not provide feedback to
GRAFIK 5000/6000/7000 Central Processors.
• Use Sivoia keypads to control individual window
treatments.
4
3
2
1
MUX
COM
COM
MUX
AC
AC
MUX
MUX
+V
EDU TERMINA L BLOC KEDU TERMINA L BLOC K
MUX
MUX
GND
AC 2
AC 1
COM
+12
MUX
MUX
GND
AC 2
AC 1
COM
+12
GND
AC
AC
GND
AC
AC
Sivoia QED Electronic Drive Unit
Sivoia QED Electronic Drive Unit
24 V~ Transformer
24 V~ Transformer
Connect pins 1, 3, and 4 only
for each additional Electronic
Drive Unit.
Pins 1, 3, and 4: (3) #18-24 AWG shielded
conductors + drain
Pins 5 and 6: (1) pair #18 AWG for power.
Lutron cable, model # SVQ-CBL-250 may be used.
All pins on SO-SVC are connected to
first Electronic Drive Unit.
To
GRAFIK
Systems
Central
Processor
SO-SVC
Sivoia QED Controller
One SO-SVC is needed per
group of Sivoia QED Window
Treatments (up to 96) moving
together.
5
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-6 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
• Use low-voltage PELV (Class 2: USA) wiring to daisy-
chain Wallstations to GRAFIK Systems components.
• Make connections inside the wallbox or in a switchbox
or junction box with a maximum wire length of 8 ft.
(2.5 m) from the link to the Wallstation.
• Two #12 AWG (2.5 mm
2
) conductors for common
(terminal 1) and 12 V (terminal 2). These will not fit
in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0 mm
2
) for
data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to
Ground (Earth) or Wallstation. Connect the bare drain
wires and cut off the outside shield.
Note: Use appropriate wire connecting devices as
specified by local codes.
4
3
2
1
Low Voltage PELV (Class 2: USA) Wiring
Data Link - (1) twisted,
shielded pair #18 AWG
(1.0 mm
2
)
3: MUX
4: MUX
PELV (Class 2: USA)
Control wiring
1: Common
2: 12 V
D: Drain/Shield
(2) #12 AWG
(2.5 mm
2
)
(2) #12 AWG
(2.5 mm
2
)
(1) #18 AWG
(1.0 mm
2
)
(1) #18 AWG
(1.0 mm
2
)
6
MUX
COM
MUX
24VAC2
24VAC1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
so-svc-7 10.20.07
Control Interfaces
SO-SVC
GRAFIK Systems
Sivoia QED Electronic Drive Unit Link
• Each SO-SVC may be wired in a daisy-chain, star, or
t-tap configuration to connect up to 96 Sivoia QED
Electronic Drive Units.
• Total length of wire on this link should not exceed 4000 ft.
(1220 m). Power (24 V ) is supplied to the Sivoia QED
Controller from the Sivoia QED Electronic Drive Unit’s
transformer.
• Each SO-SVC may be wired to only one group of Sivoia
QED Electronic Drive Units.
• The Sivoia QED communication link should not be
connected between groups of Electronic Drive Units
controlled by separate Sivoia QED Controllers.
• Use seven conductors (four shielded #18 AWG, two
power non-shielded #16 AWG, and one non-shielded #18
AWG with ground) Class 2. Lutron cable, model # SVQ-
CBL-250, may be used.
4
3
2
1
GRAFIK Systems Link
(Class 2/PELV) wiring connections
to GRAFIK Systems Central
Processor.
Low Voltage PELV (Class 2: USA) Wiring
Sivoia QED Electronic Drive Unit
Link (Class 2/PELV) wiring
connections to Sivoia QED
Electronic Drive Unit.
MUX
MUX
POWER
COM
7