R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntomx-lb-3 03.26.04
Wallstations
Large-Button Style
GRAFIK Systems
NTOMX-LB6-RL-__-_
6-Button Wallstation with Large Buttons
and Raise/Lower
Description
• Features easy to use large buttons.
• Mounts in a standard 1-gang U.S.
wallbox.
• Allows user to select and adjust three
scenes.
• Scene selection buttons activate scenes.
• Status LEDs indicate which scene is
selected.
• Raise button brightens selected scene.
• Lower button dims selected scene.
• Lower right button turns all lights off.
• May be custom-configured for other
functions.
• Works with GRAFIK 5000/6000/7000
Systems.
Finish and Engraving Options
• Available with custom engraving to meet
specific project needs.
• Amber LEDs are standard. Green LEDs
are optional.
LEDs
Off
Lower
Raise
Scene
selection
buttons
Color and Finish Codes
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntomx-lb-5 03.26.04
Wallstations
Large-Button Style
GRAFIK Systems
5/16"
(8mm)
7/8"
(21mm)
4 9/16"
(116mm)
2 3/4”
(70 mm)
Color and Finish Codes
Matte Finishes
Standard – Ship in 48 hours
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finish.
Dimensions
Mounting
Power
Low-voltage type Class 2 (PELV).
Operating voltage: 32 V Direct Current.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
• Can be ganged to share a common face
plate with NovaT*
® and Vareo
® Dimmers.
Counts as a “small control” for ganging.
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Processor Panel.
• Up to 32 Wallstations, Control Units, and/or
Control Interfaces may be connected per
Class 2 (PELV) wiring link.
Terminals
Accept up to two #18 AWG (1.0mm
2
)
typical.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Side View
Back View
1234567
4
3
2
1
DIP Switches
1-4 used to set address
5-7 used to
select function
Terminals for
Class 2 (PELV)
wiring
Specifications - LB6
Wallbox
Wallstation
Faceplate
Front View
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntomx-lb-7 03.26.04
Wallstations
Large-Button Style
GRAFIK Systems
Low-voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain Wallstations
to the Processor Panel.
• Make connections inside the wallbox or in a switch/junction box
with a maximum wire length of 8 feet (2.5m) from the link to the
Wallstation.
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1) and
32VDC (terminal 2). These will not fit in terminals. Connect as
shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground (Earth)
or Wallstation. Connect the bare drain wires and cut off the outside
shield.
Note: Some Wallstations have a “D” terminal for Drain. The
Drain/Shield wire may be connected to this terminal.
Wallstation Rear View
Wallstation Installation
Note: Use appropriate wire connecting devices
as specified by local codes.
123456
4
3
2
1
Data Link
(1) Shielded, twisted
pair #18 AWG (1.0mm
2
)
3: MUX
4: MUX
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
Class 2/PELV
Control Wiring
1: Common
2: 32VDC
3