Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
mux-rptr-4 01.05.06
AccessoriesLink Booster
GRAFIK Systems
Link Booster Wiring Detail
LT-1
LT-1
Common 1
+V 2
MUX
3
MUX 4
Drain/Shield
Sense* 5
End of
Power
Panel Link
Beginning
of Power
Panel Link
Extension
Power
Panel Link
Link Booster Terminals
*Dimming Panel
Link Only
Power
Cable
Data Cable
Shield
Common 1
+V
2
MUX 3
MUX 4
Shield
Sense* 5
Wiring Notes:
1. Connection of the Link Booster to the Control Station
Device/Power Panel Link should be made inside the Link
Booster or in a junction box (provided by others) located no
more than 8 ft. from device.
2. Control Station Device/Power Panel Link wiring must not be run
in the same raceway as line voltage (main voltage) wiring.
3. Neither the Control Station Device/Power Panel Link nor the
Control Station Device/Power Panel Link Extension may exceed
2000 ft. in length, as shown above.
4. Data cable shield must be maintained throughout the
Wallstation/Dimming Panel Link. DO NOT connect the shield to
earth ground.
5. Refer to the GRAFIK 5000/6000/7000 Installation Guide and
Lutron job drawings for power cable and data cable (Control
Station Device/Power Panel Link) wiring restrictions and
limitations.
6. Control Station Device/Power Link requires an LT-1 (Link
Termination Assembly) at each end of the Control Station
Device/Power Panel Link and each end of the Control Station
Device/Power Panel Link Extension.
Example Below: Power Panel Link Application